Plan Review Details - Permit 15030835
Plan Review Stops For Permit 15030835
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-06-24 Cont ID  
Sent By jgomez Date 2015-06-24 Time 13:26 Rev Time 0.00
Received By jgomez Date 2015-06-24 Time 13:05 Sent To  
Notes
2015-06-24 13:27:55RECEIVED E-MAIL FROM THOMAS TRUESDELL WITH SPECIFIC
 FLOOD VENTS MODELS TO BE USED. JG.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-06-22 Cont ID  
Sent By jgomez Date 2015-06-22 Time 11:16 Rev Time 0.00
Received By jgomez Date 2015-06-22 Time 11:12 Sent To  
Notes
2015-06-22 11:16:49NEW SINGLE FAMILY RESIDENCE (R3) REVISION, BUILDING
 REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE COMPLETE PRODUCT APPROVAL FOR THE FLOOD
 VENTS. ONLY THE FLORIDA PRODUCT APPROVAL FL5822-R2 WAS
 SUBMITTED. NEED TO PROVIDE ALL THE TECHNICAL DRAWINGS
 OF THE SPECIFIC MODEL TO BE INSTALLED. DCA RULE 9N-3.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-04-06 Cont ID  
Sent By jgomez Date 2015-04-06 Time 11:27 Rev Time 0.00
Received By jgomez Date 2015-04-06 Time 11:24 Sent To E
Notes
2015-04-06 11:51:38NEW SINGLE FAMILY RESIDENCE (R3) REVISION BUILDING
 REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR THE SMART VENTS SPECIFIED ON
 ARCHITECTURAL DRAWING A-1. NOTE: NEED PRODUCT APPROVAL
 FOR THE SMART VENT IN THE WALLS AND FOR SMART VENT IN
 THE GARAGE DOOR. (FOR YOUR INFORMATION, THERE IS A
 FLORIDA PRODUCT APPROVAL FL5822-R2).
  
 2- ARCHITECT TO REVIEW AND APPROVE IN WRITING ABOVE
 PRODUCT APPROVAL AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 3- ARCHITECT TO REVISE SIZE OF SMART VENT LOCATED IN
 THE GARAGE DOOR TO MATCH PRODUCT APPROVAL. SEE FLORIDA
 PRODUCT APPROVAL MENTIONED IN ITEM #1 ABOVE. SEC.
 107.2.1 CITY AMENDMENTS.
  
 4- THE FOLLOWING ITEM IS THE OUTSTANDING ITEM FROM
 PROVISO DATED 3/19/15:
 PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY DCA
 RULE 9N-3 FOR:
 A) USP TRUSS CONNECTOR TC-4 (HGAM10). FL819 IS NOT FOR
 2010 CODE VERSION. PROVIDE 2010 CODE VERSION OR APPLY
 FOR LOCAL PRODUCT APPROVAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-04-13 Cont ID  
Sent By jgomez Date 2015-04-13 Time 08:20 Rev Time 0.00
Received By dhayes Date 2015-04-13 Time 08:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-06-22 Cont ID  
Sent By jgomez Date 2015-06-22 Time 11:12 Rev Time 0.00
Received By jgomez Date 2015-05-28 Time 15:22 Sent To  
Notes
2015-05-28 15:22:43TO JG DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-04-13 Cont ID  
Sent By dhayes Date 2015-04-13 Time 08:21 Rev Time 0.00
Received By dhayes Date 2015-03-20 Time 17:35 Sent To  
Notes
2015-03-20 17:36:01REVISION SENT TO JULIO GOMEZ FOR REVIEW. JG.