Plan Review Details - Permit 15030821
Plan Review Stops For Permit 15030821
Review Stop E ELECTRICAL
Rev No 1 Status P Date   Cont ID  
Sent By   Date 2015-03-20 Time   Rev Time 0.00
Received By wlehnhar Date 2015-03-20 Time 13:37 Sent To  
Notes
2015-03-20 13:40:44OK TO ISSUE TO PER S CIARDIELLO

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2016-11-10 Cont ID  
Sent By wjolin Date 2016-11-10 Time 11:45 Rev Time 0.00
Received By wjolin Date 2016-11-10 Time 11:45 Sent To  
Notes
2016-11-10 11:45:45(1) THE ELECTRONIC SWITCH FOR RELEASING THE LOCK IS
 LISTED IN ACCORDANCE WITH UL 294, STANDARD FOR ACCESS
 CONTROL SYSTEM UNITS
 (2) THE BUILDING IS PROTECTED THROUGHOUT BY A FIRE
 ALARM SYSTEM
 (3) THE BUILDING IS PROTECTED THROUGHOUT BY AN
 APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM
 (4) WATERFLOW IN THE SPRINKLER SYSTEM REQUIRED BY
 7.2.1.6.3(3) IS ARRANGED TO INITIATE THE BUILDING FIRE
 ALARM SYSTEM.
 (5) THE ELEVATOR LOBBY IS PROTECTED BY AN APPROVED,
 SUPERVISED SMOKE DETECTION SYSTEM
 (6) DETECTION OF SMOKE BY THE DETECTION SYSTEM REQUIRED
 BY 7.2.1.6.3(5) IS ARRANGED TO INITIATE THE BUILDING
 FIRE ALARM SYSTEM.
 (7) INITIATION OF THE BUILDING FIRE ALARM SYSTEM BY
 OTHER THAN MANUAL FIRE ALARM BOXES UNLOCKS THE ELEVATOR
 LOBBY DOOR ASSEMBLY.
 (8) LOSS OF POWER TO THE ELEVATOR LOBBY ELECTRONIC LOCK
 SYSTEM UNLOCKS THE ELEVATOR LOBBY DOOR ASSEMBLIES.
 (9) THE ELEVATOR LOBBY ELECTRONIC LOCK SYSTEM IS NOT
 SUPPLIED WITH EMERGENCY OR STANDBY ELECTRICAL POWER.
 (10) ONCE UNLOCKED, THE ELEVATOR LOBBY DOOR ASSEMBLIES
 REMAIN UNLOCKED UNTIL THE BUILDING FIRE ALARM SYSTEM
 HAS BEEN MANUALLY RESET.
 (11) WHERE THE ELEVATOR LOBBY DOOR ASSEMBLIES REMAIN
 LATCHED AFTER BEING UNLOCKED, LATCH-RELEASING HARDWARE
 IS AFFIXED TO THE DOOR LEAVES.
 (12) A TWO-WAY COMMUNICATION SYSTEM IS PROVIDED FOR
 COMMUNICATION BETWEEN THE ELEVATOR LOBBY AND A CENTRAL
 CONTROL POINT THAT IS CONSTANTLY STAFFED.
 (13) THE CENTRAL CONTROL POINT STAFF REQUIRED BY
 7.2.1.6.3(12) IS CAPABLE, TRAINED, AND AUTHORIZED TO
 PROVIDE EMERGENCY ASSISTANCE.
 (14) THE PROVISIONS OF DELAYED-EGRESS LOCKING SYSTEMS
 ARE NOT APPLIED TO THE ELEVATOR LOBBY DOOR ASSEMBLIES.
 (15) THE PROVISIONS OF ACCESS-CONTROLLED EGRESS DOOR
 ASSEMBLIES ARE NOT APPLIED TO THE ELEVATOR LOBBY DOOR
 ASSEMBLIES.
  