| 2016-11-10 11:45:45 | (1) THE ELECTRONIC SWITCH FOR RELEASING THE LOCK IS |
| | LISTED IN ACCORDANCE WITH UL 294, STANDARD FOR ACCESS |
| | CONTROL SYSTEM UNITS |
| | (2) THE BUILDING IS PROTECTED THROUGHOUT BY A FIRE |
| | ALARM SYSTEM |
| | (3) THE BUILDING IS PROTECTED THROUGHOUT BY AN |
| | APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM |
| | (4) WATERFLOW IN THE SPRINKLER SYSTEM REQUIRED BY |
| | 7.2.1.6.3(3) IS ARRANGED TO INITIATE THE BUILDING FIRE |
| | ALARM SYSTEM. |
| | (5) THE ELEVATOR LOBBY IS PROTECTED BY AN APPROVED, |
| | SUPERVISED SMOKE DETECTION SYSTEM |
| | (6) DETECTION OF SMOKE BY THE DETECTION SYSTEM REQUIRED |
| | BY 7.2.1.6.3(5) IS ARRANGED TO INITIATE THE BUILDING |
| | FIRE ALARM SYSTEM. |
| | (7) INITIATION OF THE BUILDING FIRE ALARM SYSTEM BY |
| | OTHER THAN MANUAL FIRE ALARM BOXES UNLOCKS THE ELEVATOR |
| | LOBBY DOOR ASSEMBLY. |
| | (8) LOSS OF POWER TO THE ELEVATOR LOBBY ELECTRONIC LOCK |
| | SYSTEM UNLOCKS THE ELEVATOR LOBBY DOOR ASSEMBLIES. |
| | (9) THE ELEVATOR LOBBY ELECTRONIC LOCK SYSTEM IS NOT |
| | SUPPLIED WITH EMERGENCY OR STANDBY ELECTRICAL POWER. |
| | (10) ONCE UNLOCKED, THE ELEVATOR LOBBY DOOR ASSEMBLIES |
| | REMAIN UNLOCKED UNTIL THE BUILDING FIRE ALARM SYSTEM |
| | HAS BEEN MANUALLY RESET. |
| | (11) WHERE THE ELEVATOR LOBBY DOOR ASSEMBLIES REMAIN |
| | LATCHED AFTER BEING UNLOCKED, LATCH-RELEASING HARDWARE |
| | IS AFFIXED TO THE DOOR LEAVES. |
| | (12) A TWO-WAY COMMUNICATION SYSTEM IS PROVIDED FOR |
| | COMMUNICATION BETWEEN THE ELEVATOR LOBBY AND A CENTRAL |
| | CONTROL POINT THAT IS CONSTANTLY STAFFED. |
| | (13) THE CENTRAL CONTROL POINT STAFF REQUIRED BY |
| | 7.2.1.6.3(12) IS CAPABLE, TRAINED, AND AUTHORIZED TO |
| | PROVIDE EMERGENCY ASSISTANCE. |
| | (14) THE PROVISIONS OF DELAYED-EGRESS LOCKING SYSTEMS |
| | ARE NOT APPLIED TO THE ELEVATOR LOBBY DOOR ASSEMBLIES. |
| | (15) THE PROVISIONS OF ACCESS-CONTROLLED EGRESS DOOR |
| | ASSEMBLIES ARE NOT APPLIED TO THE ELEVATOR LOBBY DOOR |
| | ASSEMBLIES. |
| | |