| Plan Review Stops For Permit 15030804 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2015-07-27 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-07-27 |
Time |
15:30 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-07-27 |
Time |
15:30 |
Sent To |
|
|
| Notes |
| 2015-07-14 14:18:44 | SEE PREVIOUS COMMENTS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2015-04-22 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-04-22 |
Time |
07:59 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-04-22 |
Time |
07:30 |
Sent To |
|
|
| Notes |
| 2015-04-22 07:51:29 | BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 15030804 | | | ADD: 1270 PALM BEACH LAKES | | | CONT: EVANS PETROLEUM | | | TEL: ( 305)796-9695 | | | E-MAIL: | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015 | | | ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED | | | ELECTRONICALLY | | | UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS | | | SUBMISSION OPTIONS ARE AS FOLLOWS: | | | 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL | | | SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE | | | THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT | | | 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL | | | SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED | | | NAMING CONVENTION FOR EACH DOCUMENT | | | 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER | | | DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE | | | REQUIRED NAMING CONVENTION FOR EACH DOCUMENT | | | 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT | | | TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS | | | ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES | | | AVAILABLE | | | | | | 1ST REVIEW | | | DATE: WED. MARCH 25/ 2015 | | | ACTION: DENIED | | | | | | 1) SHEET C-1.0 SHOWS THE ACCESSIBLE PARKING SPACE AND | | | ACCESS AISLE NEXT TO THE PARKING SPACE AND IN FRONT A | | | RAISED SIDEWALK WITH NO CURB CUT. SHEET C-2.0 DOES SHOW | | | DETAILS FOR CURB CUTS BUT NONE IS SHOWN ON SHEET C-1.0, | | | SHOW COMPLIANCE WITH 2010 FBC-ACCESSIBILITY CODE 406 | | | CURB RAMPS. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2015-03-25 |
|
|
Cont ID |
|
| Sent By |
JWITMER |
Date |
2015-03-25 |
Time |
07:32 |
Rev Time |
|
| Received By |
jwitmer |
Date |
2015-03-25 |
Time |
|
Sent To |
|
|
| Notes |
| 2015-03-25 07:32:26 | BUILDING PLAN REVIEW | | | W. P. B. PERMIT: 15030804 | | | ADD: 1270 PALM BEACH LAKES | | | CONT: EVANS PETROLEUM | | | TEL: ( 305)796-9695 | | | E-MAIL: | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015 | | | ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED | | | ELECTRONICALLY | | | UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS | | | SUBMISSION OPTIONS ARE AS FOLLOWS: | | | 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL | | | SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE | | | THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT | | | 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL | | | SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED | | | NAMING CONVENTION FOR EACH DOCUMENT | | | 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER | | | DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE | | | REQUIRED NAMING CONVENTION FOR EACH DOCUMENT | | | 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT | | | TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS | | | ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES | | | AVAILABLE | | | | | | 1ST REVIEW | | | DATE: WED. MARCH 25/ 2015 | | | ACTION: DENIED | | | | | | 1) SHEET C-1.0 SHOWS THE ACCESSIBLE PARKING SPACE AND | | | ACCESS AISLE NEXT TO THE PARKING SPACE AND IN FRONT A | | | RAISED SIDEWALK WITH NO CURB CUT. SHEET C-2.0 DOES SHOW | | | DETAILS FOR CURB CUTS BUT NONE IS SHOWN ON SHEET C-1.0, | | | SHOW COMPLIANCE WITH 2010 FBC-ACCESSIBILITY CODE 406 | | | CURB RAMPS. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
F |
Date |
2015-07-14 |
|
|
Cont ID |
|
| Sent By |
cranford |
Date |
2015-07-14 |
Time |
14:22 |
Rev Time |
0.00 |
| Received By |
cranford |
Date |
2015-07-13 |
Time |
10:02 |
Sent To |
|
|
| Notes |
| 2015-07-14 14:22:46 | PUBLIC WORKS DEPT. | | | | | | 1. THE SUBMITTED PLANS DO NOT MATCH THOSE INCLUDED | | | UNDER ENGINEERING DEVELOPMENT APPROVAL E11110018. | | | PLEASE SUBMIT REVISED DRAWINGS TO THE PUBLIC WORKS | | | DEPARTMENT FOR REVIEW. | | | | | | ENGINEERING DEVELOPMENT APPROVAL FROM THE CITY?S PUBLIC | | | WORKS DEPARTMENT IS REQUIRED FOR ALL PROJECTS INVOLVING | | | OR AFFECTING THE CITY?S STREET RIGHT-OF-WAYS, | | | EASEMENTS, POTABLE WATER SYSTEM, SANITARY SEWER SYSTEM, | | | STORMWATER SYSTEM, SOLID WASTE COLLECTION, OR | | | PEDESTRIAN AND VEHICULAR TRAFFIC. THIS INCLUDES ANY | | | WORK THAT INCREASES IMPERVIOUS AREAS; CHANGES THE | | | DIRECTION, VELOCITY, OR TIMING OF STORMWATER DISCHARGE; | | | OR CREATES A CONDITION OF ENVIRONMENTAL CONCERN. THE | | | ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS CAN | | | BE DOWNLOADED AT | | | HTTP://WPB.ORG/ENGINEERING/FORMS-AND-PUBLICATIONS/ | | | | | | 2. IT DOES NOT APPEAR THAT THE CITY'S SANITATION TRUCKS | | | WILL BE ABLE TO ACCESS THE DUMPSTER LOCATION SHOWN ON | | | THE REVISED PLANS. PLEASE PROVIDE AN AUTOTURN ANALYSIS | | | DEMONSTRATING THE SOLID WASTE COLLECTION VEHICLE CAN | | | ACCESS THE PROPOSED DUMPSTER AND COMPACTOR LOCATIONS. | | | THE TRASH DUMPSTER/COMPACTORS MUST LOCATED IN AREAS | | | EASILY SERVICED BY THE CITY SANITATION EQUIPMENT AND | | | MANPOWER PER SECTION 74-35(A)(5) OF THE CODE OF | | | ORDINANCES. | | | | | | 3. PLEASE REVISE PLANS TO INCLUDE THE CITY OF WEST PALM | | | BEACH GARBAGE RECEPTACLE DETAIL. THE SHOWN DETAIL DOES | | | NOT MEET THE MINIMUM DIMENSIONAL REQUIREMENTS OF CODE | | | OF ORDINANCES, SECTION 94-444(B), ALSO SEE FIGURE XIV-3 | | | OF THE SAME SECTION. CITY STANDARD DETAIL GC-8 MAY BE | | | DOWNLOADED AT HTTP://WPB.ORG/ENGINEERING/ENGINEERING-SE | | | RVICES/ENGINEERING-STANDARDS/ | | | | | | 4. THE SUBMITTED PLANS SHOW CONSTRUCTION ACTIVITES ON | | | PROPERTY NOT OWNED BY THE APPLICANT. PLEASE PROVIDE | | | WRITTEN AUTHORIZATION FROM PALM BEACH COUNTY FOR THE | | | CONSTRUCTION PROPOSED WITHIN THE RIGHT-OF-WAY. | | | | | | 5. THE SUBMITTED PLANS TO NOT APPEAR TO MATCH THE | | | APPROVED SITE PLAN. PER SECTION 94-35(G) OF THE CODE OF | | | ORDINANCES, COMPLIANCE WITH SITE PLAN APPROVAL IS | | | REQUIRED PRIOR TO ISSUANCE OF A BUILDING PERMIT, ALL | | | CONSTRUCTION, ANY USE OF LAND OR WATER, OR ANY CHANGE | | | IN USE. | | | | | | KELLY CRANFORD, P.E. | | | LAND DEVELOPMENT ENGINEER | | | PUBLIC WORKS DEPARTMENT | | | CITY OF WEST PALM BEACH |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
F |
Date |
2015-05-08 |
|
|
Cont ID |
|
| Sent By |
cranford |
Date |
2015-05-08 |
Time |
09:46 |
Rev Time |
0.00 |
| Received By |
cranford |
Date |
2015-05-08 |
Time |
09:23 |
Sent To |
P |
|
| Notes |
| 2015-05-08 09:43:39 | 1. DEMONSTRATE THAT THE PROPOSED DUMPSTER ENCLOSURE | | | LOCATION IS ACCESSIBLE TO THE SOLID WASTE TRUCKS (35 FT | | | LONG, 15 FT HIGH) PER SECTION 74-35(A)(5) OF THE CODE | | | OF ORDINANCES. | | | | | | 2. VERIFY THAT THE PROPOSED SIZE AND QUANTITY OF TRASH | | | BINS IS APPROPRIATE FOR THE WASTE YARDAGE ANTICIPATED | | | TO BE GENERATED BY THE COMPLEX. | | | | | | 3. THE SUBMITTED PLANS DO NOT MATCH THOSE INCLUDED | | | UNDER ENGINEERING DEVELOPMENT APPROVAL E11110018. | | | PLEASE SUBMIT REVISED DRAWINGS TO THE PUBLIC WORKS | | | DEPARTMENT FOR REVIEW. | | | | | | 4. PLEASE REVISE PLANS TO INCLUDE THE CITY OF WEST PALM | | | BEACH GARBAGE RECEPTACLE DETAIL. THE SHOWN DETAIL DOES | | | NOT MEET THE MINIMUM DIMENSIONAL REQUIREMENTS OF CODE | | | OF ORDINANCES, SECTION 94-444(B), ALSO SEE FIGURE XIV-3 | | | OF THE SAME SECTION. CITY STANDARD DETAIL GC-8 MAY BE | | | DOWNLOADED AT HTTP://WPB.ORG/ENGINEERING/ENGINEERING-SE | | | RVICES/ENGINEERING-STANDARDS/ | | | | | | 5. THE SUBMITTED PLANS SHOW CONSTRUCTION ACTIVITES ON | | | PROPERTY NOT OWNED BY THE APPLICANT. PLEASE PROVIDE | | | WRITTEN AUTHORIZATION FROM PALM BEACH COUNTY FOR THE | | | CONSTRUCTION PROPOSED WITHIN THE RIGHT-OF-WAY. | | | | | | 6. THE SUBMITTED PLANS TO NOT APPEAR TO MATCH THE | | | APPROVED SITE PLAN. PER SECTION 94-35(G) OF THE CODE OF | | | ORDINANCES, COMPLIANCE WITH SITE PLAN APPROVAL IS | | | REQUIRED PRIOR TO ISSUANCE OF A BUILDING PERMIT, ALL | | | CONSTRUCTION, ANY USE OF LAND OR WATER, OR ANY CHANGE | | | IN USE. | | | | | | KELLY CRANFORD, P.E. | | | LAND DEVELOPMENT ENGINEER | | | PUBLIC WORKS DEPARTMENT | | | CITY OF WEST PALM BEACH | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2015-04-14 |
|
|
Cont ID |
|
| Sent By |
cranford |
Date |
2015-04-14 |
Time |
10:20 |
Rev Time |
0.00 |
| Received By |
cranford |
Date |
2015-04-14 |
Time |
09:21 |
Sent To |
FIRE |
|
| Notes |
| 2015-04-14 10:13:26 | PUBLIC WORKS DEPT. | | | | | | 1. THE SUBMITTED DESIGN PLANS WERE NOT SIGNED OR SEALED | | | BY A LICENSED PROFESSIONAL (ARCHITECT, CIVIL ENGINEER, | | | AND/OR LANDSCAPE ARCHITECT). PLEASE SUBMIT SIGNED AND | | | SEALED PLANS. (FAC 61G15-23.002, FS 481.221 AND | | | 481.321) | | | | | | 2. THE SUBMITTED PLANS DATED MARCH 17, 2015, DO NOT | | | MATCH THOSE INCLUDED UNDER ENGINEERING DEVELOPMENT | | | APPROVAL E11110018. PLEASE SUBMIT REVISED DRAWINGS TO | | | THE PUBLIC WORKS DEPARTMENT FOR REVIEW. | | | | | | ENGINEERING DEVELOPMENT APPROVAL FROM THE CITY?S PUBLIC | | | WORKS DEPARTMENT IS REQUIRED FOR ALL PROJECTS INVOLVING | | | OR AFFECTING THE CITY?S STREET RIGHT-OF-WAYS, | | | EASEMENTS, POTABLE WATER SYSTEM, SANITARY SEWER SYSTEM, | | | STORMWATER SYSTEM, SOLID WASTE COLLECTION, OR | | | PEDESTRIAN AND VEHICULAR TRAFFIC. THIS INCLUDES ANY | | | WORK THAT INCREASES IMPERVIOUS AREAS; CHANGES THE | | | DIRECTION, VELOCITY, OR TIMING OF STORMWATER DISCHARGE; | | | OR CREATES A CONDITION OF ENVIRONMENTAL CONCERN. THE | | | ENGINEERING DEVELOPMENT APPROVAL APPLICATION FORMS CAN | | | BE DOWNLOADED AT | | | HTTP://WPB.ORG/ENGINEERING/FORMS-AND-PUBLICATIONS/ | | | | | | 3. IT DOES NOT APPEAR THAT THE CITY'S SANITATION TRUCKS | | | WILL BE ABLE TO ACCESS THE DUMPSTER LOCATION SHOWN ON | | | THE REVISED PLANS. PLEASE PROVIDE AN AUTOTURN ANALYSIS | | | DEMONSTRATING THE SOLID WASTE COLLECTION VEHICLE CAN | | | ACCESS THE PROPOSED DUMPSTER AND COMPACTOR LOCATIONS. | | | THE TRASH DUMPSTER/COMPACTORS MUST LOCATED IN AREAS | | | EASILY SERVICED BY THE CITY SANITATION EQUIPMENT AND | | | MANPOWER PER SECTION 74-35(A)(5) OF THE CODE OF | | | ORDINANCES. | | | | | | 4. PLEASE REVISE PLANS TO INCLUDE THE CITY OF WEST PALM | | | BEACH GARBAGE RECEPTACLE DETAIL. THE SHOWN DETAIL DOES | | | NOT MEET THE MINIMUM DIMENSIONAL REQUIREMENTS OF CODE | | | OF ORDINANCES, SECTION 94-444(B), ALSO SEE FIGURE XIV-3 | | | OF THE SAME SECTION. CITY STANDARD DETAIL GC-8 MAY BE | | | DOWNLOADED AT HTTP://WPB.ORG/ENGINEERING/ENGINEERING-SE | | | RVICES/ENGINEERING-STANDARDS/ | | | | | | 5. THE SUBMITTED PLANS SHOW CONSTRUCTION ACTIVITES ON | | | PROPERTY NOT OWNED BY THE APPLICANT. PLEASE PROVIDE | | | WRITTEN AUTHORIZATION FROM PALM BEACH COUNTY FOR THE | | | CONSTRUCTION PROPOSED WITHIN THE RIGHT-OF-WAY. | | | | | | 6. THE SUBMITTED PLANS TO NOT APPEAR TO MATCH THE | | | APPROVED SITE PLAN. PER SECTION 94-35(G) OF THE CODE OF | | | ORDINANCES, COMPLIANCE WITH SITE PLAN APPROVAL IS | | | REQUIRED PRIOR TO ISSUANCE OF A BUILDING PERMIT, ALL | | | CONSTRUCTION, ANY USE OF LAND OR WATER, OR ANY CHANGE | | | IN USE. | | | | | | KELLY CRANFORD, P.E. | | | LAND DEVELOPMENT ENGINEER | | | PUBLIC WORKS DEPARTMENT | | | CITY OF WEST PALM BEACH | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2015-07-09 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2015-07-09 |
Time |
11:47 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2015-07-09 |
Time |
11:47 |
Sent To |
|
|
| Notes |
| 2015-07-09 11:47:11 | PERMIT # 15030804 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | APPROVED WITH THE FOLLOWING COMMENTS: | | | | | | 1) PLEASE ADDRESS ANY AND ALL COMMENTS FROM OTHER | | | DEPARTMENT REVIEWS. | | | | | | 2) PROJECT SHALL BE IN FULL COMPLIANCE WITH THE 5TH | | | EDITION OF THE FLORIDA FIRE PREVENTION CODE, INCLUDING | | | THE 2012 EDITION OF NFPA 1 AND NFPA 101. | | | | | | 3) PROJECT SHALL BE IN FULL COMPLIANCE WITH THE | | | REQUIREMENTS OF NFPA 30A: CODE FOR MOTOR FUEL | | | DISPENSING FACILITIES AND REPAIR GARAGES. | | | | | | | | | SUE ELLEN CALDERON | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 644-7326 | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2015-04-27 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2015-04-27 |
Time |
13:43 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2015-04-27 |
Time |
13:43 |
Sent To |
|
|
| Notes |
| 2015-04-27 13:45:39 | PERMIT #15030804 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | FAILED: | | | SEE COMMENTS FROM 4/15/15. | | | | | | | | | SUE ELLEN CALDERON | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 644-7326 | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2015-04-15 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2015-04-15 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2015-04-15 |
Time |
10:53 |
Sent To |
PC |
|
| Notes |
| 2015-04-15 11:02:50 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) PLEASE ADDRESS COMMENTS OF OTHER DEPARTMENTS. | | | | | | 2) PLEASE PROVIDE AND NOTE AND ENSURE ALL CONSTRUCTION | | | SHALL MEET THE REQUIREMENTS OF THE 5TH EDITION OF | | | FLORIDA FIRE PREVENTION CODE INCLUDING THE 2012 EDITION | | | OF NFPA 1 AND NFPA 101 AND ALL OTHER APPLICABLE CODES | | | OR STANDARDS. | | | | | | 3) PROVIDE A NOTE AND ENSURE ALL WORK RELATED TO THE | | | FUEL PUMPS SHALL COMPLY WITH THE REQUIREMENTS OF NFPA 1 | | | AND 30A CODE FOR MOTOR FUEL DISPENSING FACILITIES AND | | | REPAIR GARAGES. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2015-07-27 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2015-07-27 |
Time |
15:30 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2015-07-02 |
Time |
10:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2015-05-09 |
|
|
Cont ID |
|
| Sent By |
|
Date |
2015-05-09 |
Time |
|
Rev Time |
0.00 |
| Received By |
shill |
Date |
2015-04-16 |
Time |
14:05 |
Sent To |
|
|
| Notes |
| 2015-04-16 14:07:47 | ****EXPEDITED**** | | | C02 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2015-04-15 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2015-04-15 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2015-03-20 |
Time |
12:19 |
Sent To |
|
|
| Notes |
| 2015-03-20 14:37:10 | REVISION SENT TO C8 SHELF FOR REVIEW. JG. |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
2 |
Status |
N |
Date |
2015-06-12 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
2015-06-12 |
Time |
13:59 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
2015-06-12 |
Time |
13:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
P |
Date |
2015-04-10 |
|
|
Cont ID |
|
| Sent By |
rcaranci |
Date |
2015-04-10 |
Time |
08:43 |
Rev Time |
0.00 |
| Received By |
rcaranci |
Date |
2015-04-10 |
Time |
08:42 |
Sent To |
|
|
| Notes |
| 2015-04-10 08:44:13 | SEPARATE LANDSCAPE PERMIT ISSUED 15010460 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2015-05-09 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-05-09 |
Time |
05:48 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-05-09 |
Time |
05:36 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2015-04-06 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-04-06 |
Time |
07:22 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-04-06 |
Time |
05:40 |
Sent To |
|
|
| Notes |
| 2015-04-06 07:33:18 | 1) PLANS SHALL BE SIGNED AND SEALED BY THE DESIGN | | | PROFESSIONAL OF RECORD PER THE FL. ADMIN. CODE SEC. | | | 61G15-23.002. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2015-07-24 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2015-07-24 |
Time |
11:06 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2015-07-24 |
Time |
11:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2015-04-29 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2015-04-29 |
Time |
14:40 |
Rev Time |
0.00 |
| Received By |
sgraham |
Date |
2015-04-29 |
Time |
14:40 |
Sent To |
|
|
| Notes |
| 2015-04-29 14:41:50 | 4/29/15 ZONING FAILED AV | | | | | | NEED RIGHT-AWAY PERMIT FROM PALM BEACH COUNTY AS PER A. | | | VANN. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2015-04-09 |
|
|
Cont ID |
|
| Sent By |
ajvann |
Date |
2015-04-09 |
Time |
14:04 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2015-04-09 |
Time |
14:04 |
Sent To |
|
|
| Notes |
|
|