| 2015-03-30 12:19:33 | 3/30/2015 |
| | PROJECT: IBIS CLUBHOUSE SITE AND LANDSCAPE LIGHTING |
| | PERMIT#: 15030800 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) 505.2.4 EXTERIOR LIGHTING CONTROLS. |
| | LIGHTING FOR ALL EXTERIOR APPLICATIONS NOT EXEMPTED IN |
| | SECTION 505.1 SHALL HAVE AUTOMATIC CONTROLS CAPABLE OF |
| | TURNING OFF EXTERIOR LIGHTING WHEN SUFFICIENT DAYLIGHT |
| | IS AVAILABLE OR WHEN THE LIGHTING IS NOT REQUIRED |
| | DURING NIGHTTIME HOURS. LIGHTING NOT DESIGNATED FOR |
| | DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY EITHER A |
| | COMBINATION OF A PHOTOSENSOR AND A TIME SWITCH, OR AN |
| | ASTRONOMICAL TIME SWITCH. INDICATE COMPLIANCE WITH THE |
| | FLORIDA ENERGY CODE, 505.2 ON THE PLANS. |
| | |
| | 2) 2010 FBC-BUILDING SECTION 1609 |
| | PROVIDE WIND LOAD CALCULATIONSIN COMPLIANCE WITH THE |
| | FBC 1609, (PRIOR TO RELEASE OF PERMIT), FOR ALL LIGHT |
| | POLE LIGHTS. INCLUDE THE INSTALLATION OF THE LUMINAIRE |
| | ON THE POLE IN THE CALCULATION. |
| | |
| | 3) PROVIDE PANEL SCHEDULES, AND LOAD CALCULATIONS AS |
| | WELL AS THE METHODS AND MATERIALS PROPOSED FOR THE |
| | INSTALLATION OF NEW CIRCUITRY. |
| | |
| | 4) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF |
| | THE PERSON RESPONSIBLE FOR THE DESIGN. FL SS 471, |
| | 668.001-668.006 FBC, WPB AMENDMENTS 107.2.. THE PLANS |
| | HAVE NOT BEEN SIGNED BY THE ENGINEER. PROVIDE TWO SETS |
| | OF SIGNED, SEALED PLANS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |
| | |
| | |
| | |