| 2015-03-31 09:22:08 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15030795 |
| | ADD: 5390 GEORGIA AVE. |
| | CONT: TIM GIVENS BUILDING |
| | TEL: (561)533-5825 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. MARCH 30/2015 |
| | ACTION: DENIED |
| | |
| | IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015 |
| | ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED |
| | ELECTRONICALLY |
| | UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS |
| | SUBMISSION OPTIONS ARE AS FOLLOWS: |
| | 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL |
| | SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE |
| | THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| | 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL |
| | SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED |
| | NAMING CONVENTION FOR EACH DOCUMENT |
| | 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER |
| | DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE |
| | REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| | 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT |
| | TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS |
| | ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES |
| | AVAILABLE |
| | |
| | 1) COVERSHEET A-000 THE BUILDING AREA CALCULATIONS |
| | APPEAR NOT TO INCLUDE UNDER ROOF PARKING AND DUMPSTER |
| | ENCLOSURE. ALL AREA UNDER ROOF OR FOOTPRINT OF BUILDING |
| | IS TO BE CONSIDERED IN THE BUILDING SQUARE FOOT AREA. |
| | 2010 FBC-B DEFINITIONS AREA, BUILDING. |
| | |
| | 2) THE PERMIT VALUE OF $150,000.00 IS LOW. THE |
| | CALCULATED VALUE OF THE PROPOSED PROJECT IS |
| | $214,564.00. |
| | PERMIT FEES/ PLAN REVIEW: |
| | THE PERMIT APPLIED VALUE IS STATED AS $4,055,000 THE |
| | CALCULATED VALUE IS $4,131,694.00 IN VALUE. W P B |
| | ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT FEES. ON |
| | BUILDINGS, STRUCTURES, ELECTRICAL, GAS, MECHANICAL AND |
| | PLUMBING SYSTEMS OR ALTERATIONS REQUIRING A PERMIT, A |
| | FEE FOR EACH PERMIT SHALL BE PAID AS REQUIRED, IN |
| | ACCORDANCE WITH THE SCHEDULE ESTABLISHED BY THE |
| | APPLICABLE GOVERNING AUTHORITY. |
| | |
| | 108.3* BUILDING PERMIT VALUATION. |
| | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE |
| | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, |
| | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS |
| | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE |
| | PERMIT SHALL BE DENIED. FOR PERMITTING PURPOSES, |
| | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND |
| | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE |
| | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR |
| | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR |
| | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING |
| | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES |
| | (MARSHALL-SWIFT, MEANS, ETC.) WITH REGIONAL ADJUSTMENTS |
| | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE |
| | CONGRESS. |
| | |
| | 3) THE SUBMITTED SOILS REPORTS ARE COPIES NOT ORIGINAL |
| | SIGNED AND SEALED DOCUMENTS. PLANS, SPECIFICATIONS, |
| | REPORTS OR OTHER DOCUMENTS PREPARED BY THE DESIGN |
| | PROFESSIONAL AND BEING FILED FOR PUBLIC RECORD SHALL |
| | HAVE THE SIGNATURE AND SEAL OF THE DESIGN PROFESSIONAL |
| | AFFIXED TO THE DOCUMENT. FL ADMIN CODE 61G15-23.002 |
| | ENGINEERS |
| | |
| | 4) MISSING FROM THE SET OF PLANS IS A LIFE SAFETY PLAN. |
| | THIS PLAN WILL NEED TO SHOW COMPLIANCE WITH: |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, |
| | 107.3.5.1.1 MINIMUM PLAN REVIEW CRITERIA FOCOMMERCIAL |
| | BUILDINGS |
| | LIFE SAFETY PLAN SHOW FURNATURE AND EQUIPMENT |
| | OCCUPANCY LOAD |
| | GROSS |
| | NET |
| | MEANS OF EGRESS |
| | EXIT ACCESS |
| | EXIT |
| | EXIT DISCHARGE |
| | STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION |
| | DOORS |
| | EMERGENCY LIGHTING AND EXIT SIGNS |
| | SPECIFIC OCCUPANCY REQUIREMENTS: |
| | |
| | 2) SPECIFIC OCCUPANCY REQUIREMENTS: NOTE IF THE |
| | CARPENTRY STUDIO AND OR CARPENTER WORK SHOP SHOW |
| | COMPLIANCE WITH: |
| | |
| | 2A) FBC-M 903.2.4.1 WOODWORKING OPERATIONS. AN |
| | AUTOMATIC SPRINKLER SYSTEM SHALL BE PROVIDED THROUGHOUT |
| | ALL GROUP F-1 OCCUPANCY FIRE AREAS THAT CONTAIN |
| | WOODWORKING OPERATIONS IN EXCESS OF 2,500 SQUARE FEET |
| | (232 M2) IN AREA WHICH GENERATE FINELY DIVIDED |
| | COMBUSTIBLE WASTE OR USE FINELY DIVIDED COMBUSTIBLE |
| | MATERIALS. |
| | |
| | 2B) FBC-M 503.2 FANS. PARTS OF FANS IN CONTACT WITH |
| | EXPLOSIVE OR FLAMMABLE VAPORS, FUMES OR DUSTS SHALL BE |
| | OF NONFERROUS OR NONSPARKING MATERIALS, OR THEIR CASING |
| | SHALL BE LINED OR CONSTRUCTED OF SUCH MATERIAL. WHEN |
| | THE SIZE AND HARDNESS OF MATERIALS PASSING THROUGH A |
| | FAN ARE CAPABLE OF PRODUCING A SPARK, BOTH THE FAN AND |
| | THE CASING SHALL BE OF NONSPARKING MATERIALS. WHEN FANS |
| | ARE REQUIRED TO BE SPARK RESISTANT, THEIR BEARINGS |
| | SHALL NOT BE WITHIN THE AIRSTREAM, AND ALL PARTS OF THE |
| | FAN SHALL BE GROUNDED. FANS IN SYSTEMS-HANDLING |
| | MATERIALS THAT ARE CAPABLE OF CLOGGING THE BLADES, AND |
| | FANS IN BUFFING OR WOODWORKING EXHAUST SYSTEMS, SHALL |
| | BE OF THE RADIAL-BLADE OR TUBE-AXIAL TYPE. |
| | |
| | 2C) FBC-M [F] 510.2.1 LUMBER YARDS AND WOODWORKING |
| | FACILITIES. |
| | EQUIPMENT OR MACHINERY LOCATED INSIDE BUILDINGS AT |
| | LUMBER YARDS AND WOODWORKING FACILITIES WHICH GENERATES |
| | OR EMITS COMBUSTIBLE DUST SHALL BE PROVIDED WITH AN |
| | APPROVED DUST-COLLECTION AND EXHAUST SYSTEM INSTALLED |
| | IN CONFORMANCE WITH THIS SECTION AND THE FLORIDA FIRE |
| | PREVENTION CODE. EQUIPMENT AND SYSTEMS THAT ARE USED TO |
| | COLLECT, PROCESS OR CONVEY COMBUSTIBLE DUSTS SHALL BE |
| | PROVIDED WITH AN APPROVED EXPLOSION-CONTROL SYSTEM. |
| | |
| | 2D) FBC-M 511.4 WOOD PROCESSING AND WOODWORKING |
| | FACILITIES. |
| | WOOD PROCESSING FACILITIES THAT PRODUCE OR UTILIZE |
| | FINELY DIVIDED WOOD PARTICLES OR WOOD FIBERS SHALL |
| | CONFORM WITH NFPA 664. |
| | EXCEPTION: FACILITIES WITH AN AREA OF 2,000 SQUARE FEET |
| | (185.8 M2) OR LESS AND HAVE A DUST COLLECTION FLOW RATE |
| | OF 1500 CUBIC FEET PER MINUTE (0.708 M3/SEC) OR LESS. |
| | |
| | 3) SHEET A100 THE RESTROOM DOES NOT COMPLY WITH THE |
| | 2010 FL ACCESSIBILITY CODE 604.3.2. |
| | |
| | 4) SHEET A100 THE CONFERENCE ROOM SHOWS A WET BAR |
| | PLEASE SHOW COMPLIANCE WITH 2010 FL ACC. CODE 606.1-5. |
| | |
| | 5) SHEET A100 THE RECEPTION DESK DOES NOT INDICATE |
| | COMPLIANCE WITH 2010 FBC- ACCESS. 04.4 SALES AND |
| | SERVICE COUNTERS. |
| | SALES COUNTERS AND SERVICE COUNTERS SHALL COMPLY WITH |
| | 904.4.1 OR 904.4.2. |
| | |
| | 6) SHEET A400 THE DOORS IDENTIFIED AS 2 & 3 IN THE DOOR |
| | SCHEDULE AS A 2 FT. 8 INCH DOORS. 2010 FL ACC. CODE THE |
| | DOORS WILL NEED TO COMPLY WITH 404.2.3 CLEAR WIDTH. |
| | DOOR OPENINGS SHALL PROVIDE A CLEAR WIDTH OF 32 INCHES |
| | (815 MM) MINIMUM. CLEAR OPENINGS OF DOORWAYS WITH |
| | SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE OF |
| | THE DOOR AND THE STOP, WITH THE DOOR OPEN 90 DEGREES. |
| | |
| | 7) THE DOOR THAT LEADS TO THE RESTROOM DOES NOT COMPLY |
| | WITH 2010 FL ACCESS. CODE 404.2.4 MANEUVERING |
| | CLEARANCES REQUIRING 18 INCHES ON THE LATCH SIDE OF THE |
| | DOOR. THERE IS A DOOR IDENTIFICATION TAG # 6 BUT THERE |
| | ARE 2 DOORS IN THIS LOCATION WHICH IS IT FOR, OR FOR |
| | BOTH? |
| | |
| | 8A) SHEET S-3.0 THE ROOF WIND DESIGN IS OFF, THE |
| | POSITIVE PRESSURES ARE HIGHER THAN THE NEGATIVE |
| | PRESSURES, THE OTHER ISSUE, ZONES 2 & 3 HAVE THE SAME |
| | PRESSURE, THE ROOF WIND DESIGN CHART DOES NOT INDICATE |
| | IF THESE VALUES ARE IN VULT OR VASD OR WHAT SQ. FT OF |
| | TRIBUTARY AREA THIS CHART IS FOR. 2010 FBC-B 1609.1.1 |
| | DETERMINATION OF WIND DESIGN- CHAPTER 6 OF ASCE 7-10. |
| | |
| | 8B) SHEET S4.0 THE WINDOW AND DOOR PRESSURES ARE |
| | PROVIDED. THE NORTH ELEVATION THE CORNER ZONE # 5 THE |
| | WINDOW PRESSURES ARE LOW. THE SOUTH ELEVATION OF THE |
| | NORTH WING THE PRESSURES ARE LOW IN ZONES 5 THE UPPER |
| | AND LOWER WINDOWS, IN ZONE 4 THE UPPER AND LOWER WINDOW |
| | PRESSURES ARE ALSO LOW. 2010 FBC-B 1609.1.1 |
| | DETERMINATION OF WIND DESIGN- CHAPTER 6 OF ASCE 7-10. |
| | |
| | 8C) PRESSURES FOR THE OFFICE DOOR ARE NOT PROVIDED. |
| | 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| | CHAPTER 6 OF ASCE 7-10. |
| | |
| | 8D) THE SOUTH WING NORTH ELEVATION THE PRESSURES ARE |
| | LOW FOR BOTH WINDOW ZONES 4 & 5. 2010 FBC-B 1609.1.1 |
| | DETERMINATION OF WIND DESIGN- CHAPTER 6 OF ASCE 7-10. |
| | THE GAGE DOOR PRESSURES ARE NOT PROVIDED. |
| | |
| | 8E) DOOR 8 ON THE SOUTH WING PRESSURES ARE NOT |
| | PROVIDED. |
| | |
| | 9) THE WINDOW, MULLION AND DOOR PRODUCT APPROVALS |
| | SUBMITTED DO NOT INDICATE THE SIZE OF THE UNIT, TYPE OF |
| | GLAZING TO BE INSTALLED, MULLION SIZE AND OR IF |
| | RE-INFORCED ANCHOR TYPE OR SIZE. PLEASE IDENTIFY THESE |
| | COMPONENTS SO A PLAN REVIEW OF THSE ITEMS CAN TAKE |
| | PLACE. |
| | |
| | 10) CLOPAY GARAGE DOORS DOES NOT HAVE THE COVER SHEETS |
| | FOR EITHER A FLORIDA APPROVAL OR A MIAMI-DADE NOA. |
| | |
| | 11) NO ROOFING SUBMITTALS HAVE BEEN PROVIDED. |
| | |
| | 12) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 13) THIS PROJECT WILL REQUIRE A RESIDENT INSPECTOR |
| | BECAUSE OF THE STEEL THAT WILL BE WELDED ON SITE AND |
| | THE CONCRETE HOLLOW PLANK SYSTEM. 2010 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION, 110.3.9 OTHER INSPECTIONS SERVICES. THE |
| | BUILDING OFFICIAL MAY MAKE, OR CAUSE TO BE MADE BY |
| | OTHERS, THE INSPECTIONS REQUIRED BY SECTION 109. HE/SHE |
| | MAY ACCEPT REPORTS OF INSPECTORS OF RECOGNIZED |
| | INSPECTION SERVICES, PROVIDED THAT AFTER INVESTIGATION |
| | HE/SHE IS SATISFIED AS TO THEIR QUALIFICATIONS AND |
| | RELIABILITY. A CERTIFICATE CALLED FOR BY ANY PROVISION |
| | OF THE TECHNICAL CODES SHALL NOT BE BASED ON SUCH |
| | REPORTS UNLESS THE SAME ARE IN WRITING AND CERTIFIED BY |
| | A RESPONSIBLE OFFICER OF SUCH SERVICE. THE BUILDING |
| | OFFICIAL MAY REQUIRE THE OWNER TO EMPLOY AN INSPECTION |
| | SERVICE IN THE FOLLOWING INSTANCES: |
| | |
| | 1. FOR BUILDINGS OR ADDITIONS OF TYPE I OR II |
| | CONSTRUCTION |
| | 2. FOR ALL MAJOR STRUCTURAL ALTERATIONS |
| | 3. WHERE THE CONCRETE DESIGN IS BASED ON COMPRESSIVE |
| | STRENGTH (F ?C) IN EXCESS OF 3000 |
| | POUNDS PER SQUARE INCH |
| | 4. FOR PILE DRIVING |
| | 5. FOR BUILDINGS WITH AREA GREATER THAN 20,000 SQUARE |
| | FOOT |
| | 6. FOR BUILDINGS MORE THAN 2 STORIES IN HEIGHT |
| | 7. FOR BUILDINGS AND STRUCTURES OF UNUSUAL DESIGN OR |
| | METHODS OF CONSTRUCTION |
| | |
| | 13A) FOR THE RESIDENT INSPECTOR PLEASE PROVIDE A |
| | RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. |
| | THE RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| | AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | CONTACT KEN CONRAD |
| | TEL: 561-805-6666 |
| | E-MAIL: [email protected] |
| | |
| | 13B) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| | HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE |
| | SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD: |
| | [email protected] |
| | |
| | 13C) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE |
| | REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, THE |
| | PERMIT LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND |
| | BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO |
| | SETS OF PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR |
| | THE RESIDENT INSPECTOR, THE OTHER FOR THE MEP |
| | INSPECTORS. |
| | |
| | 13D) PLEASE CALL THE CITY OF WEST PALM BEACH?S |
| | AUTOMATED TELEPHONE INSPECTIONS LINE (561) 805-6700) |
| | FOR IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE |
| | INSPECTIONS. |
| | |
| | NOTE: RESIDENT INSPECTOR FORMS ARE BEING SENT TO: |
| | [email protected] |
| | |
| | 14) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 15) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | DEVELOPMENT SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF |
| | FLORIDA SAVING LIVES AND PROPERTY SINCE 1953 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |