Plan Review Details - Permit 15030793
Plan Review Stops For Permit 15030793
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-06-17 Cont ID  
Sent By jgomez Date 2015-06-17 Time 12:39 Rev Time 0.00
Received By jgomez Date 2015-06-17 Time 12:38 Sent To  
Notes
2015-06-17 12:40:40RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS
 CODE: 2010 FBC.
  
 1- SHEET S-1:
 A) ALL WALL SECTIONS AND DETAILS ARE MISSING THE
 STRUCTURAL CONNECTORS. SPECIFY ALL STRUCTURAL
 CONNECTIONS FOR ALL WOOD STUDS, WOOD COLUMNS, FLOOR
 JOISTS TO NEW STEEL BEAM, ETC. . SEC. R301.1 AND R601.2
 OF 2010 FBC-RESIDENTIAL.
  
 2- SECTION 5/S-1:
 A) PROVIDE COMPLETE SPECIFICATIONS FOR THE TYPE OF
 STEEL BEAM. SQUARE BEAM? THICKNESS, ETC. SEC 107.2.1
 CITY AMENDMENTS.
  
 B) HOW MANY BOLTS ARE REQUIRED ON EACH STEEL ANGLE THAT
 IS SUPPORTING THE STEEL BEAM? SEC 107.2.1 CITY
 AMENDMENTS.
  
 C) STEEL ANGLE IS MISSING THE DIMENSION FOR ONE SIDE.
 SEC 107.2.1 CITY AMENDMENTS
  
 D) PROVIDE COMPLETE SPECIFICATIONS FOR THE TYPE OF
 FOUNDATION BEAM THAT WILL SUPPORT NEW STEEL BEAM. SEC
 107.2.1 CITY AMENDMENTS.
  
 3- SPECIFY TYPE AND SIZE OF EXISTING WINDOWS (SPECIALLY
 THE BEDROOM WINDOWS) AND TYPE AND SIZE OF PROPOSED
 WINDOWS TO VERIFY COMPLIANCE WITH SEC. 604 OF 2010
 FBC-EXISTING BUILDING.
  
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ENTRY DOOR. PROVIDE 2 COPIES FLORIDA PRODUCT
 APPROVAL FL15255.5. ONLY ONE SUBMITTED. ALSO, IDENTIFY
 WHICH DOOR IS GOING TO BE INSTALLED TO VERIFY THE
 DESIGN PRESSURES CALCULATED BY THE DESIGNER OF RECORD.
  
 B) INSWING SIDE DOOR AS SHOWN ON PLANS BY THE KITCHEN
 AREA. NONE SUBMITTED AT THIS TIME.
  
 C) FRENCH DOOR. PROVIDE 2 COPIES. ONLY ONE WAS
 SUBMITTED.
  
 D) WINDOW MULLIONS. PROVIDE 2 COPIES. ONLY ONE
 SUBMITTED. AND, CLEARLY SPECIFY MULLION SIZE TO VERIFY
 COMPLIANCE WITH THE CALCULATED DESIGN PRESSURES.
  
 E) SINGLE HUNG WINDOWS. PROVIDE 2 COPIES. ONLY ONE
 SUBMITTED.
  
 F) ALL STRUCTURAL CONNECTORS SPECIFIED ON WALL SECTIONS
 ON SHEET S-1. PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL
 NUMBER AND PAGE SHOWING THE SPECIFIED CONNECTOR. OR
 LIST THE FLORIDA PRODUCT APPROVAL NUMBER NEXT TO EACH
 SPECIFIED CONNECTOR.
  
 5- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
 NOTE: ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND
 APPROVED BY THE NEW DESIGNER OF RECORD NOT FERNANDO
 GOMEZ-PINA, P.E.
  
 6- ENERGY CALCULATIONS SUBMITTED;
 A) NEED INFORMATION FROM PERSON COMPLETING THE FORM.
 SEC 405.4 OF 2010 FBC-ENERGY CONSERVATION.
  
 B) NEED OWNER/AGENT SIGNATURE AND DATE AT BOTTOM OF
 FORM. SEC. 103.2.3.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 C) COMPLETE ALL THE INFORMATION ON TOP OF
 FORM,INCLUDING OWNER'S NAME AND BUILDER. SEC. 107.2.1
 CITY AMENDMENTS
  
 D) ITEM #1 IS INCORRECT. THIS IS NOT NEW CONSTRUCTION.
 SEC. 103.2.1.1.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 E) ITEM #8 IS INCORRECT. ACCORDING TO PLANS THERE IS
 NOT SLAB ON GRADE.
  
 F) ITEM # 9 IS INCORRECT. ACCORDING TO PLANS THERE ARE
 NOT CONCRETE BLOCK WALLS.
  
 G) ROOF MATERIAL SPECIFIED ON PAGE 2 OF 5 IS INCORRECT.
 THERE IS NOT BARREL TILE ON THIS HOUSE.
  
 H) DOOR TYPE ON PAGE 3 OF 5 IS INCORRECT. THERE ARE NOT
 WOOD DOORS. SEE PLANS AND PRODUCT APPROVALS SUBMITTED.
  
 NOTE: THIS IS A CONTRIBUTING HISTORIC HOUSE. ENERGY
 CALCULATIONS ARE NOT REQUIRED. BUT, IF THEY ARE
 SUBMITTED, THEY NEED TO BE CORRECT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-05-01 Cont ID  
Sent By jgomez Date 2015-04-30 Time 17:29 Rev Time 0.00
Received By jgomez Date 2015-04-30 Time 17:12 Sent To  
Notes
2015-04-30 17:56:27RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS
 CODE: 2010 FBC.
  
 THE REVIEW IS SUSPENDED AS THE SUBMITTAL DOCUMENTS WERE
 PREPARED, SIGNED AND SEALED BY FERNANDO R, GOMEZ-PINA.
 THE DRAWINGS WERE SIGNED AND SEALED ON 12/28/14. MR.
 GOMEZ-PINA VOLUNTARILY RELINQUISHED HIS ENGINEER
 LICENSE NUMBER 14710 ON 12/15/14 ACCORDING TO THE DBPR
 PUBLIC RECORDS.. ACCORDINGLY, THE DOCUMENTS ARE NOT IN
 COMPLIANCE WITH FLORIDA BUILDING CODE SECTION 107.1
 CITY AMENDMENTS. CHAPTER 471, FLORIDA STATUTES, AND
 61G15 FLORIDA ADMINISTRATIVE CODE. THE MATTER IS
 FORWARDED TO THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-05-26 Cont ID  
Sent By skennedy Date 2015-05-26 Time 11:05 Rev Time 0.00
Received By rlecky Date 2015-05-26 Time 10:23 Sent To  
Notes
2015-05-26 11:05:1315030793
 231 ARGYLE ROAD
 RESIDENTIAL REMODEL
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 IF THE BUILDING HAS GAS APPLIANCES, AN ATTACHED GARAGE
 OR A FIREPLACE, A CARBON MONOXIDE DETECTOR IS REQUIRED
 WITHIN TEN FEET OF EACH ROOM USED FOR SLEEPING. 2010
 FBC R314, 315
 ARC FAULT CIRCUIT PROTECTION IS REQUIRED FOR ALL BRANCH
 CIRCUITS SUPPLYING OUTLETS. NEC 210.12
 A GFCI PROTECTED RECEPTACLE IS REQUIRED AT THE FRONT
 ENTRANCE. NEC 210.8, 210.52(E) (1)
 INDICATE ON THE PLANS THE LOCATION OF ALL GFCI
 PROTECTED OUTLETS. NEC 210.8
 SHOW THE LOCATION OF THE ELECTRICAL SERVICE, PANELBOARD
 AND MAIN DISCONNECT ON THE BUILDING. VERIFY THE MAIN
 DISCONNECT IS LOCATED AT THE POINT OF SERVICE. VERIFY
 THE UNPROTECTED SERVICE CONDUCTORS ARE NOT LOCATED
 WITHIN THE BUILDING. NEC 230.70(A) (1)
 AN ELECTRICAL GROUNDING SYSTEM IS REQUIRED. NEC 250.24
 A BONDING STRIP IS REQUIRED AT THE ELECTRIC SERVICE
 GROUND. NEC 250.94
 PROVIDE A LOAD CALCULATION WHICH SUPPORTS THE SERVICE
 SIZE SELECTED. NEC 210.82
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-05-01 Cont ID  
Sent By skennedy Date 2015-05-01 Time 12:57 Rev Time 0.00
Received By skennedy Date 2015-05-01 Time 12:57 Sent To  
Notes
2015-05-01 12:59:09RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS
 CODE: 2010 FBC.
  
 THE REVIEW IS SUSPENDED AS THE SUBMITTAL DOCUMENTS WERE
 PREPARED, SIGNED AND SEALED BY FERNANDO R, GOMEZ-PINA.
 THE DRAWINGS WERE SIGNED AND SEALED ON 12/28/14. MR.
 GOMEZ-PINA VOLUNTARILY RELINQUISHED HIS ENGINEER
 LICENSE NUMBER 14710 ON 12/15/14 ACCORDING TO THE DBPR
 PUBLIC RECORDS.. ACCORDINGLY, THE DOCUMENTS ARE NOT IN
 COMPLIANCE WITH FLORIDA BUILDING CODE SECTION 107.1
 CITY AMENDMENTS. CHAPTER 471, FLORIDA STATUTES, AND
 61G15 FLORIDA ADMINISTRATIVE CODE. THE MATTER IS
 FORWARDED TO THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 STEVEN KENNEDY
 561 805 6710

Review Stop HIST HISTORICAL
Rev No 2 Status F Date 2015-06-01 Cont ID  
Sent By fmittner Date 2015-06-01 Time 15:37 Rev Time 0.00
Received By fmittner Date 2015-06-01 Time 15:37 Sent To  
Notes
2015-06-01 15:38:31NOTES FROM LAST REVIEW STILL NOT ADDRESSED:
  
 COA APPLICATION SHALL BE FILED FOR WINDOWS, DOORS,
 OPENING CHANGES NOT PERMITTED AS DEPICTED. IS CARPORT
 PROPOSED FOR REMOVAL? NOT SHOWN ON PLANS.THIS IS A
 SIGNIFICANT CONTRIBUTING PROPERTY. NEW WINDOWS MUST BE
 6/6 SINGLE HUNG WINDOWS WITH DIMENSIONAL MUNITNS, WHITE
 FRAMES, CLEAR GLASS. QUESTIONS CONTACT FRIEDERIKE
 MITTNER, CITY HISTORIC PRESERVATION PLANNER AT
 822-1457.

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2015-04-29 Cont ID  
Sent By fmittner Date 2015-04-29 Time 13:47 Rev Time 0.00
Received By fmittner Date 2015-04-29 Time 13:47 Sent To  
Notes
2015-04-29 13:50:26COA APPLICATION SHALL BE FILED FOR WINDOWS DOORS,
 OPENIGN CHANGES NOT PERMITTED AS DEPICTED. IS CARPORT
 PROPOSED FOR REMOVAL? NOT SHOWN ON PLANS.THIS IS A
 SIGNIFICANT CONTRIBUTING PROPERTY. NEW WINDOWS MUST BE
 6/6 SINGLE HUNG WINDOWS WITH DIMENSIONAL MUNITNS, WHITE
 FRAMES, CLEAR GLASS. QUESTIONS CONTACT FRIEDERIKE
 MITTNER, CITY HISTORIC PRESERVATION PLANNER AT
 822-1457.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-06-17 Cont ID  
Sent By jgomez Date 2015-06-17 Time 12:43 Rev Time 0.00
Received By jgomez Date 2015-05-06 Time 16:51 Sent To  
Notes
2015-05-06 16:50:49R18

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-05-01 Cont ID  
Sent By skennedy Date 2015-05-01 Time 12:59 Rev Time 0.00
Received By skennedy Date 2015-03-19 Time 07:48 Sent To  
Notes
2015-03-20 07:49:51****EXPEDITED****
 R23
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-06-12 Cont ID  
Sent By jgomez Date 2015-06-12 Time 10:32 Rev Time 0.00
Received By ccole Date 2015-06-11 Time 13:50 Sent To  
Notes
2015-06-12 10:45:302ND REVIEW: FBC 2010 MECHANICAL
  
 1) SHEET M-1: PROVIDE A DETAIL TO CLARIFY HOW THE 18
 X12 DUCT IS RUNNING FROM THE AHU DOWN TO THE FIRST
 FLOOR.
 2) M-1: SHOW THE DUCT RUN AND DUCT SIZE FROM THE MAIN
 DUCT TO THE BATHROOM ON THE SECOND FLOOR, AND INDICATE
 CFM SUPPLY AIR AT THE DIFFUSER.
 3) THE ENERGY CALCULATION FORM 405-10 MUST BE SIGNED
 AND DATED BY THE PREPARER AND BY THE OWNER.
 4) M-1: THE SEER OF THE PROPOSED UNIT IS NOT INDICATED
 IN THE AC SCHEDULE- IT IS LISTED AS 16 SEER IN THE
 ENERGY CALCS.
  
 CHRISTOPHER COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-05-01 Cont ID  
Sent By jgomez Date 2015-05-01 Time 11:24 Rev Time 0.00
Received By jgomez Date 2015-05-01 Time 11:24 Sent To  
Notes
2015-05-01 11:24:29RESIDENTIAL (R3) ALTERATION, MECHANICAL REVIEW COMMENTS
 CODE: 2010 FBC.
  
 RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS
 CODE: 2010 FBC.
  
 THE REVIEW IS SUSPENDED AS THE SUBMITTAL DOCUMENTS WERE
 PREPARED, SIGNED AND SEALED BY FERNANDO R, GOMEZ-PINA.
 THE DRAWINGS WERE SIGNED AND SEALED ON 12/28/14. MR.
 GOMEZ-PINA VOLUNTARILY RELINQUISHED HIS ENGINEER
 LICENSE NUMBER 14710 ON 12/15/14 ACCORDING TO THE DBPR
 PUBLIC RECORDS.. ACCORDINGLY, THE DOCUMENTS ARE NOT IN
 COMPLIANCE WITH FLORIDA BUILDING CODE SECTION 107.1
 CITY AMENDMENTS. CHAPTER 471, FLORIDA STATUTES, AND
 61G15 FLORIDA ADMINISTRATIVE CODE. THE MATTER IS
 FORWARDED TO THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-06-08 Cont ID  
Sent By tlarge Date 2015-06-08 Time 06:25 Rev Time 0.00
Received By tklarge Date 2015-06-08 Time 05:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-04-23 Cont ID  
Sent By tklarge Date 2015-04-23 Time 13:35 Rev Time 0.00
Received By tklarge Date 2015-04-12 Time 06:23 Sent To  
Notes
***NONE***