Plan Review Details - Permit 15030786
Plan Review Stops For Permit 15030786
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-05-08 Cont ID  
Sent By jwitmer Date 2015-05-08 Time 07:59 Rev Time 0.00
Received By jwitmer Date 2015-05-08 Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-05-01 Cont ID  
Sent By J,WITMER Date 2015-05-01 Time 07:27 Rev Time 0.00
Received By jwitmer Date 2015-05-01 Time 07:05 Sent To  
Notes
2015-05-01 07:26:04BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15030786
 ADD: 2808 N. AUSTRALIAN AVE.
 CONT: CLAY KOHLMEYER
 TEL: (561)694-1214
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE
  
 2ND REVIEW
 DATE: WED. MAY 01/ 2015
 ACTION: DENIED
  
 NOTICE: CHAPTER 553.80(2)(B) FLORIDA STATUTES STATES
 THAT A LOCAL GOVERNMENT SHALL IMPOSE A FEE OF FOUR
 TIMES THE FEE FOR PLAN REVIEW, IF PLANS ARE REJECTED
 (3) OR MORE TIMES FOR REPEATED FAILURE TO CORRECT A
 CODE VIOLATION.
  
  
 1) 2ND REQUEST THE RESPONSE LETTER INDICATES THE
 REMOVAL OF NON-BEARING WALLS, PLEASE SHOW A DEMOLITION
 PLAN SO THE SCOPE OF THE REMODEL CAN BE DETERMINED.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL THE SUBMITTED PLANS
 DO NOT SHOW THE EXISTING CONDITIONS, AREA TO BE
 REMODELED, THE PLANS SUBMITTED SHEET 1.0A DOESN'T
 REFLECT WHAT HAS CHANGED ,JUST THAT IT IS NEW.
 COMMENT FROM THE 1ST REVIEW.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES.
  
 2-3) COMPLIED.
  
 4) 2ND REQUEST. THE PROPOSED WORK SHOWN ON SHEET 1.0A
 ALSO SHOWS A WALK IN COOLER ON THE INTERIOR OF THE
 BUILDING WITH WHAT APPEARS IS A ADDITION TO THE COOLER
 TO THE EXTERIOR OF THE BUILDING.
  
 4A) 2ND REQUEST. THE RESPONSE LETTER INDICATES THE
 COOLER WILL NO LONGER BE OUTSIDE THE BUILDING BUT THE
 PLANS HAVE NOT BEEN UPDATED TO REFLECT THE DELETION OF
 THE EXTERIOR COOLER.
 1ST REVIEW COMMENT. THE PLANS DO NOT INDICATE WHEN THE
 ADDITION OF THE EXTERIOR COOLER IS ADDED HOW THE
 PENETRATION OF THE WALL IS MADE, ASSUMED MATERIAL TO BE
 CBS CONSTRUCTION, EITHER COLUMNS WOULD BE CUT OR
 MASONRY CELLS WITH STEEL. THE SUPPORTING BEAM WAS NOT
 DESIGNED TO BE A CLEAR SPAN LOAD BEARING BEAM NOR DOES
 THE PLANS SHOW THE SUPPORTING COLUMNS. 2010 FBC-B
 2107.1 GENERAL. THE DESIGN OF MASONRY STRUCTURES USING
 ALLOWABLE STRESS DESIGN SHALL COMPLY WITH THE
 REQUIREMENTS OF CHAPTERS 1 AND 2 OF TMS 402/ACI
 530/ASCE 5 EXCEPT AS MODIFIED BY SECTION 2107.2.
  
 4B) 2ND REQUEST. THE RESPONSE LETTER INDICATES THE
 COOLER WILL NO LONGER BE OUTSIDE THE BUILDING BUT THE
 PLANS HAVE NOT BEEN UPDATED TO REFLECT THE DELETION OF
 THE EXTERIOR COOLER.
 1ST REVIEW COMMENT. SHEET 1.0A INDICATES THE NEW
 EXTERIOR COOLER WILL BE CONSTRUCTED, THERE IS NO
 INFORMATION, IF THE SLAB IS EXISTING, THICKNESS, NOR IS
 THERE INFORMATION AS TO THE WIND SPEED THE NEW EXTERIOR
 COOLER IS TO BE CONSTRUCTED.
 WIND DESIGN CRITERIA
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
  
 4B)(1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 4B)(2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE
 7-10.
  
 4B)(3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 4B)(4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 4B)(5) COMPONENTS & CLADDING PRESSURES POSITIVE &
 NEGATIVE TABLE 1609.2(2) .
  
 5) 2ND REQUEST. THE RESPONSE LETTER INDICATES THE
 COOLER WILL NO LONGER BE OUTSIDE THE BUILDING BUT THE
 PLANS HAVE NOT BEEN UPDATED TO REFLECT THE DELETION OF
 THE EXTERIOR COOLER. SUBMIT PRODUCT APPROVALS: 2010
 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS: (31) (G) EXTERIOR COOLER, FREEZERS &
 PRE-ENGINEERED A/C STANDS
  
 6) 2ND REQUEST. THE RESPONSE LETTER INDICATES THE
 COOLER WILL NO LONGER BE OUTSIDE THE BUILDING BUT THE
 PLANS HAVE NOT BEEN UPDATED TO REFLECT THE DELETION OF
 THE EXTERIOR COOLER. 2010 FBC 107.3.4.1 PRODUCT
 APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE
 DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 7) 2ND REQUEST, NOT ADDRESSED. THE PLANS DO NOT
 INDICATE IF THERE IS ANOTHER AREA THAT HAS BECOME THE
 DINING ROOM, PLEASE SUBMIT A LIFE SAFETY PLANS OF THE
 WHOLE BUILDING. 2010 WEST PALM BEACH AMENDMENTS TO THE
 FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATION
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. THE
 EXAMINATION OF THE DOCUMENTS BY THE BUILDING OFFICIAL
 SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA AND
 DOCUMENTS: LIFE SAFETY PLAN.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-03-25 Cont ID  
Sent By jwitmer Date 2015-03-25 Time 07:16 Rev Time 0.00
Received By jwitmer Date 2015-03-25 Time 06:36 Sent To  
Notes
2015-03-25 07:18:35BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15030786
 ADD: 2808 N. AUSTRALIAN AVE.
 CONT: CLAY KOHLMEYER
 TEL: (561)694-1214
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE
  
 1ST REVIEW
 DATE: WED. MARCH 25/ 2015
 ACTION: DENIED
  
 1) THE SUBMITTED PLANS DO NOT SHOW THE EXISTING
 CONDITIONS, AREA TO BE REMODELED, THE PLANS SUBMITTED
 SHEET 1.0A DOESN'T REFLECT WHAT HAS CHANGED ,JUST THAT
 IT IS NEW.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES.
  
 2) SHEET 1.0A. WITHIN THE FLOOR PLAN WHERE THE THROUGH
 THE WALL HOOD EXHAUST VENT IS LOCATED, IT APPEARS THERE
 WAS A RAMP ON THE EXTERIOR OF THE BUILDING, PLEASE
 PROVIDE WHAT THIS AERA IS AND WAS THERE A DOOR WAY
 THERE.107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 3) SHEET 1.0A DOES NOT SHOW HOW THE EXHAUST FAN IS
 GOING TO BE CUT THROUGH THE WALL AND THERE IS NO DETAIL
 OF HOW THE HOLE IS TO BE CREATED AND MAINTAINED WEATHER
 TIGHT. 2010 FBC-B 1403.2 WEATHER PROTECTION. EXTERIOR
 WALLS SHALL PROVIDE THE BUILDING WITH A
 WEATHER-RESISTANT EXTERIOR WALL ENVELOPE.
  
 4) THE PROPOSED WORK SHOWN ON SHEET 1.0A ALSO SHOWS A
 WALK IN COOLER ON THE INTERIOR OF THE BUILDING WITH
 WHAT APPEARS IS A ADDITION TO THE COOLER TO THE
 EXTERIOR OF THE BUILDING.
  
 4A) THE PLANS DO NOT INDICATE WHEN THE ADDITION OF THE
 EXTERIOR COOLER IS ADDED HOW THE PENETRATION OF THE
 WALL IS MADE, ASSUMED MATERIAL TO BE CBS CONSTRUCTION,
 EITHER COLUMNS WOULD BE CUT OR MASONRY CELLS WITH
 STEEL. THE SUPPORTING BEAM WAS NOT DESIGNED TO BE A
 CLEAR SPAN LOAD BEARING BEAM NOR DOES THE PLANS SHOW
 THE SUPPORTING COLUMNS. 2010 FBC-B 2107.1 GENERAL. THE
 DESIGN OF MASONRY STRUCTURES USING ALLOWABLE STRESS
 DESIGN SHALL COMPLY WITH THE REQUIREMENTS OF CHAPTERS 1
 AND 2 OF TMS 402/ACI 530/ASCE 5 EXCEPT AS MODIFIED BY
 SECTION 2107.2.
  
 4B) SHEET 1.0A INDICATES THE NEW EXTERIOR COOLER WILL
 BE CONSTRUCTED, THERE IS NO INFORMATION, IF THE SLAB IS
 EXISTING, THICKNESS, NOR IS THERE INFORMATION AS TO THE
 WIND SPEED THE NEW EXTERIOR COOLER IS TO BE
 CONSTRUCTED.
 WIND DESIGN CRITERIA
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
  
 4B)(1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 4B)(2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE
 7-10.
  
 4B)(3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 4B)(4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 4B)(5) COMPONENTS & CLADDING PRESSURES POSITIVE &
 NEGATIVE TABLE 1609.2(2) .
  
 5) SUBMIT PRODUCT APPROVALS: 2010 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS: (31) (G) EXTERIOR COOLER, FREEZERS &
 PRE-ENGINEERED A/C STANDS
  
 6) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7) THE PLANS DO NOT INDICATE IF THERE IS ANOTHER AREA
 THAT HAS BECOME THE DINING ROOM, PLEASE SUBMIT A LIFE
 SAFETY PLANS OF THE WHOLE BUILDING.
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.3.5 MINIMUM PLAN
 REVIEW CRITERIA FOR BUILDINGS. THE EXAMINATION OF THE
 DOCUMENTS BY THE BUILDING OFFICIAL SHALL INCLUDE THE
 FOLLOWING MINIMUM CRITERIA AND DOCUMENTS: LIFE SAFETY
 PLAN.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-05-08 Cont ID  
Sent By D.HAYES Date 2015-05-08 Time 16:58 Rev Time 0.00
Received By skennedy Date 2015-05-08 Time 16:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-03-23 Cont ID  
Sent By dhayes Date 2015-03-23 Time 13:03 Rev Time 0.00
Received By dhayes Date 2015-03-23 Time 13:03 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-04-30 Cont ID  
Sent By P. LEDUC Date 2015-04-30 Time   Rev Time 0.00
Received By pleduc Date 2015-04-30 Time 10:02 Sent To  
Notes
2015-04-30 10:04:30THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 NO EXIT OR EMERGENCY LIGHTS WHERE SHOWN ON THE LIFE
 SAFETY OR ELECTRICAL PLAN. THE FIRE INSPECTOR SHALL
 FIELD VERIFY INSTALLATIONS ON THE FIRE INSPECTION.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-03-20 Cont ID  
Sent By pleduc Date 2015-03-20 Time   Rev Time 0.00
Received By pleduc Date 2015-03-20 Time 12:41 Sent To  
Notes
2015-03-20 12:55:26THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THE SUBMITTED PLAN INDICATES INCORRECT REFERENCES TO
 THE FLORIDA FIRE CODE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
  
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
  
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
  
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
  
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
  
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
  
 2) THE SUBMITTED PLAN DOES NOT CONTAIN A LIFE SAFETY
 PLAN. PLEASE SUBMIT A LIFE SAFETY PLAN INCLUDING, FIRE
 WALLS, OCCUPANY LOADS FOR EACH SPACE, EGRESS PATHS,
 COMMON PATHS OF TRAVEL, EMERGENCY LIGHTS, FIRE
 EXTINGUSHER LOCATIONS, EXITS AND EXIT WIDTHS, LOCATIONS
 OF A PUBLIC WAY, ETC
  
 3) ADDITIONAL COMMENTS MAY BE GENERATED BASED ON
 SUBMITTAL OF THE ABOVE INFORMATION.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date 2015-05-09 Cont ID  
Sent By jwitmer Date 2015-05-09 Time 08:14 Rev Time 0.00
Received By jwitmer Date 2015-04-27 Time   Sent To  
Notes
2015-04-28 10:22:48SENT TO B46.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-04-21 Cont ID  
Sent By hmoser Date 2015-04-21 Time 13:04 Rev Time 0.00
Received By hmoser Date 2015-03-19 Time 16:19 Sent To  
Notes
2015-03-19 16:19:53B36

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2015-03-25 Cont ID  
Sent By jwitmer Date 2015-03-25 Time 07:18 Rev Time 0.00
Received By jwitmer Date 2015-03-25 Time 07:18 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2015-05-09 Cont ID  
Sent By H.MOSER Date 2015-05-09 Time 08:14 Rev Time 0.00
Received By jwitmer Date 2015-05-09 Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-04-21 Cont ID  
Sent By hmoser Date 2015-04-21 Time 13:04 Rev Time 0.00
Received By hmoser Date 2015-04-21 Time 12:42 Sent To  
Notes
2015-04-21 13:04:02PLAN DENIED
 1) SHOW TYPE OF AIRCONDITIONING WORK TO BE CONTRACTED
 ON THE PLAN
 2) A COMPLETE SET OF PLANS FOR HEAT HOOD IS REQUIRED.
 SEPARATE
 APPLICATION, PLAN AND PERMIT IS REQUIRED FOR HOOD.
 PER SECTION 107 FBC 2010
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-05-04 Cont ID  
Sent By TKLARGE Date 2015-05-04 Time 11:49 Rev Time 0.00
Received By tklarge Date 2015-05-04 Time 09:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-04-12 Cont ID  
Sent By tklarge Date 2015-04-12 Time 06:18 Rev Time 0.00
Received By tklarge Date 2015-04-12 Time 05:06 Sent To  
Notes
2015-04-12 06:18:451) SUBMIT SANITARY / GREASE/ WATER RISER DIAGRAMS FOR
 ALL NEW WORK AND CHANGES TO THE EXISTING WATER AND
 SANITARY SYSTEM. SHOW ALL INDIRECT WASTES ON THE
 PLUMBING RISER , WPB AMEND. TO 2010 FBC SEC.
 107.3.5.1.3.
 2) SUBMIT A GAS RISER DIAGRAM FOR ALL NEW WORK OR
 CHANGES TO THE GAS SYSTEM. INDICATE PSI OF GAS, TYPE OF
 MATERIAL, TOATL DEVELOPED LENGTH TO MOST REMOTE OUTLET,
 ETC.WPB AMEND. TO 2010 FBC SEC. 107.3.5.1.3.
 3) SUBMIT 2 COPIES OF MANUF. SPECIFICATIONS FOR ALL GAS
 EQUIPMENT. ALL EQUIPMENT SHALL BE LISTED AND LABELED
 PER THE 2010 FUEL GAS CODE SEC. 301.3.
 4) SHT.1.1 (A) - THERE IS A LIST OF ALL THE KITCHEN
 EQUIPMENT IN A TABLE LABELED "ELECTRIC SCHEDULE."
 CLARIFY. IDENTIFY THE PIECES OF EQUIPMENT ON THIS
 SCHEDULE AS NEW OR EXISTING OR IDENTIFY THE EQUIPMENT
 AS SUCH ON THE FLOOR PLAN.WPB AMEND. TO 2010 FBC SEC.
 107.2.1.
 5) SUBMIT 2 COPIES OF MANUF. SPECIFICATIONS FOR THE
 GREASE INTERCEPTOR UNIT. WPB AMEND.TO 2010 FBC SEC.
 107.2.1.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2015-03-27 Cont ID  
Sent By ajones Date 2015-03-27 Time 10:29 Rev Time 0.00
Received By ajones Date 2015-03-27 Time 10:29 Sent To  
Notes
***NONE***