| 2015-03-20 06:45:47 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2010 |
| | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL |
| | |
| | |
| | 1. COMPLETE THE SAMPLE INSTALLATION SCHEDULE OR PROVIDE |
| | ALL INFORMATION TO SHOW CODE COMPLIANCE IN ANOTHER |
| | FORMAT, FBC*106, FBC R301, FBC1609. TWO SETS REQUIRED. |
| | THIS FORM IS AVAILABLE IN THE LOBBY OR ON THE INTERNET |
| | AT |
| | |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/SCHEDULE_FOR_INSTALLATION.PDF |
| | |
| | INSTALLATION SCHEDULE TIPS - READ THE FOLLOWING ONLY IF |
| | YOU ARE UNFAMILIAR WITH THIS FORM AND NEED ASSISTANCE: |
| | |
| | THE FOLLOWING IS A GUIDE TO ASSIST WITH COMPLETION OF |
| | THE COLUMNS IN THE INSTALLATION SCHEDULE MOST OFTEN |
| | FAILED IN PLAN REVIEW. IT IS RECOMMENDED THAT THE |
| | CONTRACTOR CIRCLE THE PERTINENT INFORMATION IN THE |
| | PRODUCT APPROVAL. IF PROPOSED INSTALLATION IS CLEAR, AN |
| | EFFORT WILL BE MADE TO REDLINE THE INSTALLATION |
| | SCHEDULE IF NECESSARY. |
| | |
| | SHUTTER CONNECTION MOUNTING TYPE: THIS IS NOT THE |
| | FASTENER PROPOSED. THE INFORMATION IN THIS COLUMN |
| | SHOULD CORRELATE WITH THE ANCHOR CHARTS. MOST PRODUCT |
| | APPROVALS HAVE ANCHOR CHARTS WHICH SPECIFY THE ANCHOR |
| | SPACING. FIRST, LOCATE THE ANCHOR CHARTS IN THE PRODUCT |
| | APPROVAL. NOTE THE NAMING CONVENTION. THE MOST COMMON |
| | NAMING CONVENTIONS ARE THE FOLLOWING: |
| | |
| | C1, C2, C3, C4, C5 |
| | 1 (TOP), 1 (BOTTOM); 2 (TOP), 2 (BOTTOM), ETC. |
| | |
| | WITH THE NAMING CONVENTION IN MIND, LOCATE THE |
| | INSTALLATION MOUNTING DETAILS IN THE PRODUCT APPROVAL. |
| | DETERMINE WHICH INSTALLATION METHOD YOU PROPOSE. THE |
| | SHUTTER CONNECTION MOUNTING TYPE WILL BE INDICATED |
| | WITHIN THE DETAIL. |
| | |
| | SHUTTER SPAN: FOR ACCORDION SHUTTERS, THIS DIMENSION IS |
| | THE BLADE LENGTH. FOR PANELS AND MOST OTHER TYPES OF |
| | IMPACT PROTECTION, THIS IS THE DIMENSION FROM ANCHOR TO |
| | ANCHOR. |
| | |
| | SHUTTER INSTALLED VERTICAL/HORIZONTAL: ACCORDIONS ARE |
| | INSTALLED VERTICALLY; PANELS CAN BE INSTALLED EITHER |
| | VERTICALLY OR HORIZONTALLY. THIS COLUMN CORRELATES WITH |
| | THE CONFIGURATION OF THE ANCHORS (ANCHORS AT TOP AND |
| | BOTTOM = VERTICAL, ANCHORS AT SIDES OF OPENING = |
| | HORIZONTAL). |
| | |
| | SUBSTRATE: FOR MOST VERTICAL INSTALLATIONS, CBS |
| | STRUCTURE, THE TOP IS USUALLY CONCRETE, BOTTOM IS |
| | USUALLY BLOCK (MASONRY) UNLESS THE PRODUCT APPROVAL |
| | INCLUDES A CHART FOR GROUT FILLED BLOCK. FOR HORIZONTAL |
| | INSTALLATIONS, UNLESS THE STRUCTURE HAS CONCRETE WALLS |
| | RATHER THAN CBS, THE SUBSTRATE IS MASONRY OR GROUT |
| | FILLED BLOCK (IF THAT SUBSTRATE IS INCLUDED IN THE |
| | PRODUCT APPROVAL). ONLY A FORMED AND POURED CONCRETE |
| | SUBSTRATE IS CONSIDERED CONCRETE FOR THIS PURPOSE. |
| | |
| | ANCHOR SPACING: THIS IS DETERMINED BY LOCATING THE |
| | PROPOSED DESIGN PRESSURE, SHUTTER CONNECTION MOUNTING |
| | TYPE, SUBSTRATE AND ANCHOR TYPE IN THE PRODUCT APPROVAL |
| | ANCHOR CHARTS. THE MOST COMMON ERROR IS THE USE OF THE |
| | CONCRETE CHART. IN SOME PRODUCT APPROVALS, SOME |
| | MOUNTING TYPES ARE LIMITED TO CONCRETE AND WOOD |
| | SUBSTRATES ONLY. READ THE INFORMATION AT THE TOP OF THE |
| | CHART CAREFULLY. |
| | |
| | WHY IS THIS REQUIRED? |
| | |
| | THIS FORM (OR ALL OF THE INFORMATION CONTAINED ON THE |
| | FORM PROVIDED IN ANOTHER FORMAT) IS USED IN PLAN REVIEW |
| | TO DETERMINE THAT THE PROPOSED INSTALLATION IS |
| | CONSISTENT WITH THE REQUIREMENTS IN THE PRODUCT |
| | APPROVAL. IN THE FIELD, IT ASSISTS THE INSPECTOR TO |
| | PERFORM THE INSPECTION QUICKLY AND ACCURATELY. |
| | |