| 2015-05-18 07:50:20 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15030731 / STRUCTURE ONLY PERMIT |
| | ADD: 333 FERN ST. |
| | CONT: KAST CONSTRUCTION |
| | CONTACT : |
| | TEL: (561)689-2910 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 1ST REVIEW |
| | DATE: MAY 18 /2015 |
| | ACTION: DENIED |
| | |
| | |
| | 1) FOR THE STRUCTURE ONLY PERMIT PLEASE NOTE THIS |
| | PERMIT IS AT THE CONTRACTORS OWN RISK!!!! |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 107.3.3 PHASED |
| | APPROVAL. THE BUILDING OFFICIAL IS AUTHORIZED TO ISSUE |
| | A PERMIT FOR THE CONSTRUCTION OF FOUNDATIONS OR ANY |
| | OTHER PART OF A BUILDING OR STRUCTURE BEFORE THE |
| | CONSTRUCTION DOCUMENTS FOR THE WHOLE BUILDING OR |
| | STRUCTURE HAVE BEEN SUBMITTED, PROVIDED THAT ADEQUATE |
| | INFORMATION AND DETAILED STATEMENTS HAVE BEEN FILED |
| | COMPLYING WITH PERTINENT REQUIREMENTS OF THIS CODE. THE |
| | HOLDER OF SUCH PERMIT FOR THE FOUNDATION OR OTHER PARTS |
| | OF A BUILDING OR STRUCTURE SHALL PROCEED AT THE |
| | HOLDER?S OWN RISK WITH THE BUILDING OPERATION AND |
| | WITHOUT ASSURANCE THAT A PERMIT FOR THE ENTIRE |
| | STRUCTURE WILL BE GRANTED. |
| | |
| | 2) THE PERMIT APPLICATION FOR THIS PERMIT UNDER THE |
| | HEADING SCOPE OF WORK HAS INCLUDED THE FOLLOWING: |
| | STRUCTURE ONLY TO INCLUDE FOUNDATIONS, STRUCTURAL |
| | CONCRETE AND EXTERIOR MASONRY. THE QUESTION TO BE |
| | ASKED, IS THE AUGURED CAST PILE INCLUDED IN THIS PERMIT |
| | & THE TERM EXTERIOR MASONRY OR ALL MASONRY WALLS |
| | INCLUDED UNDER THIS PERMIT. THE DESCRIPTION OF WORK |
| | DOES NOT INCLUDE ANY COMPONENTS AND CLADDING OR |
| | STUCCOING OF THE EXTERIOR OF THE BUILDING OR PARKING |
| | AREAS? 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 3) THERE ARE (2) OTHER AREAS THAT WILL NEED TO BE |
| | CLEARED UP AS TO IF A REVISION WILL BE REQUIRED. |
| | THE SOILS REPORT INDICATED THIS SITE HAD LOOSE TO VERY |
| | LOOSE SOILS AND VIBROFLOTATION WOULD POSSIBLY HARM |
| | STRUCTURES CLOSE BY. THE RECOMMENDATION WAS AUGURED |
| | CAST PILING FOR THE SITE AND THE UNDER PINNING OF THE |
| | STRUCTURE TO THE NORTH. |
| | 3A) THE UNDERPINNING OF THE STRUCTURE TO THE NORTH |
| | REQUIRES THE OWNERS APPROVAL AND SINCE IT HAS ITS OWN |
| | SEPARATE ADDRESS & PCN NUMBER AA SEPARATE PERMIT. |
| | |
| | 3B) THE 2ND ISSUE THAT WAS BROUGHT UP IN A MEETING |
| | 5/12/2015 WITH THE KAST PROJECT MANAGER FOR THE SITE |
| | MATT STILL WAS SHEET PILING THE PERIMETER OF THE SITE. |
| | THIS BROUGHT UP CONCERN SINCE THE SOILS REPORT |
| | RECOMMENDED AGAINST ANY ACTION THAT CAUSES EARTH |
| | VIBRATION SUCH AS VIBROFLOTATION OR SHEET PILE THAT ARE |
| | EITHER DRIVEN OR VIBRATED INTO THE SOILS. THE USE OF |
| | SHEET PILE ON THE PROPERTY LINE WILL ALSO CAUSE THE |
| | PILE CAP DESIGN TO BE ALTERED TO ACCOMMODATE THE SHEET |
| | PILE, THE PLANS SHOW A VERSION 2 ON THIS PLAN BUT NOT |
| | ON THE MAIN BUILDING PLANS. THE SOIL REPORT ALSO |
| | INCLUDED HOW TO SHORE UP THE UNITIES IN THE ALLEY. IN |
| | SPEAKING WITH JIM BOYCE WITH KALTER IT SEEMS THEY WILL |
| | NEED TO DECIDE HOW THEY WILL PROCEED WITH THIS PORTION |
| | OF THE PROJECT. |
| | |
| | 2010 FBC-B 3304.1.1 SLOPE LIMITS. SLOPES FOR PERMANENT |
| | FILL SHALL NOT BE STEEPER THAN ONE UNIT VERTICAL IN TWO |
| | UNITS HORIZONTAL (50-PERCENT SLOPE). CUT SLOPES FOR |
| | PERMANENT EXCAVATIONS SHALL NOT BE STEEPER THAN ONE |
| | UNIT VERTICAL IN TWO UNITS HORIZONTAL (50-PERCENT |
| | SLOPE). DEVIATION FROM THE FOREGOING LIMITATIONS FOR |
| | CUT SLOPES SHALL BE PERMITTED ONLY UPON THE |
| | PRESENTATION OF A SOIL INVESTIGATION REPORT ACCEPTABLE |
| | TO THE BUILDING OFFICIAL. |
| | |
| | 3304.1.2 SURCHARGE. NO FILL OR OTHER SURCHARGE LOADS |
| | SHALL BE PLACED ADJACENT TO ANY BUILDING OR STRUCTURE |
| | UNLESS SUCH BUILDING OR STRUCTURE IS CAPABLE OF |
| | WITHSTANDING THE ADDITIONAL LOADS CAUSED BY THE FILL OR |
| | SURCHARGE. EXISTING FOOTINGS OR FOUNDATIONS WHICH CAN |
| | BE AFFECTED BY ANY EXCAVATION SHALL BE UNDERPINNED |
| | ADEQUATELY OR OTHERWISE PROTECTED AGAINST SETTLEMENT |
| | AND SHALL BE PROTECTED AGAINST LATER MOVEMENT. |
| | |
| | 3307.1 PROTECTION REQUIRED. ADJOINING PUBLIC AND |
| | PRIVATE PROPERTY SHALL BE PROTECTED FROM DAMAGE DURING |
| | CONSTRUCTION, REMODELING AND DEMOLITION WORK. |
| | PROTECTION MUST BE PROVIDED FOR FOOTINGS, FOUNDATIONS, |
| | PARTY WALLS, CHIMNEYS, SKYLIGHTS AND ROOFS. PROVISIONS |
| | SHALL BE MADE TO CONTROL WATER RUNOFF AND EROSION |
| | DURING CONSTRUCTION OR DEMOLITION ACTIVITIES. THE |
| | PERSON MAKING OR CAUSING AN EXCAVATION TO BE MADE SHALL |
| | PROVIDE WRITTEN NOTICE TO THE OWNERS OF ADJOINING |
| | BUILDINGS ADVISING THEM THAT THE EXCAVATION IS TO BE |
| | MADE AND THAT THE ADJOINING BUILDINGS SHOULD BE |
| | PROTECTED. SAID NOTIFICATION SHALL BE DELIVERED NOT |
| | LESS THAN 10 DAYS PRIOR TO THE SCHEDULED STARTING DATE |
| | OF THE EXCAVATION. |
| | |
| | 3303.5 WATER ACCUMULATION. PROVISION SHALL BE MADE TO |
| | PREVENT THE ACCUMULATION OF WATER OR DAMAGE TO ANY |
| | FOUNDATIONS ON THE PREMISES OR THE ADJOINING PROPERTY. |
| | |
| | 4) NOTICE ONLY; THIS NOTICE IS PUT ON THIS PORTION OF |
| | THE PROJECT PLEASE CONTACT YOUR ZONING PLAN REVIEWER TO |
| | SEE IF IT APPLIES TO THE WHOLE BUILDING OR TO EACH |
| | PHASE OF THE STRUCTURE? THE CITY OF WEST PALM BEACH ART |
| | IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES TO |
| | ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH THE |
| | PERMIT APPLICATION WAS SUBMITTED AFTER 7/1/14, AND THE |
| | TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR |
| | GREATER THAN $500,000. PER CITY OF WEST PALM BEACH |
| | ORDINANCE NO. 4504-14, AND CITY OF WEST PALM BEACH CODE |
| | OF ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION |
| | 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS |
| | 1% OF THE TOTAL PROJECT CONSTRUCTION COST. |
| | |
| | PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE |
| | V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND |
| | NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO |
| | THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE |
| | PROJECTS. |
| | |
| | 5) PLEASE PROVIDE A SURVEY WITH THE PROPOSED OVERLAY OF |
| | THE BUILDING TO VERIFY THE ACTUAL DISTANCE FROM |
| | PROPERTY LINES. 2010 FBC-B TABLE 602. THE CURRENT |
| | SURVEY SUBMITTED INDICATES THIS PROPOSED STRUCTURE WILL |
| | BE LOCATED ON LOTS 11-15 OF BLOCK 10. A REPLAT WILL BE |
| | REQUIRED TO ELIMINATE THE BUILDING GOING PAST PROPERTY |
| | LINES. TABLE 602. |
| | |
| | 6) THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING. |
| | ?THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS |
| | GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH |
| | HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN |
| | THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. |
| | IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| | PERSONS. |
| | |
| | 6A) THRESHOLD INSPECTION PLAN FL S. S. 553.71(7). 2010 |
| | WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 109.3.6.1 THE ENFORCING |
| | AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL |
| | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A |
| | THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION |
| | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL |
| | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING |
| | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR |
| | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE |
| | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE |
| | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT |
| | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| | WITH THE PERMITTED DOCUMENTS. |
| | |
| | 6B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT REQUESTS FOR THRESHOLD |
| | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S |
| | 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS |
| | REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS |
| | ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH |
| | INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND |
| | REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE |
| | PLACE. CONTACT KEN CONRAD MANAGER OF THE SPECIAL |
| | INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER |
| | INFORMATION BEFORE THE PERMIT MAY BE ISSUED. |
| | FORMS WERE SENT TO: : [email protected] AT |
| | 05/09/2015 02:09 PM. |
| | |
| | 6C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B. |
| | AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH |
| | ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT |
| | OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE |
| | BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE |
| | PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE |
| | FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| | AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| | FLORIDA STATUTE. |
| | |
| | 6D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' |
| | OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE |
| | RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| | AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | CONTACT KEN CONRAD |
| | TEL: 561-805-6666 |
| | E-MAIL: [email protected] |
| | |
| | 6E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| | HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE |
| | SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD: |
| | [email protected] |
| | |
| | 6F) FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, THE |
| | PERMIT LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND |
| | BATCH STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO |
| | SETS OF PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR |
| | THE THRESHOLD INSPECTOR, THE OTHER FOR THE MEP |
| | INSPECTORS. |
| | |
| | 6G) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED |
| | TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR |
| | IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE |
| | INSPECTIONS. |
| | |
| | 6H) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES |
| | FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER |
| | HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE |
| | MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR |
| | WALLS AND CEILINGS. |
| | |
| | 7) THIS MAY OR MAY NOT APPLY TO THIS PERMIT DEPENDING |
| | IF COMPONENTS AND CLADDING ARE GOING TO BE INCLUDED. ) |
| | PAGES 163 S1.13 AND 164 S1.14. NOTE # 1 ON THESE SHEETS |
| | INDICATE THE PRESSURES WERE CALCULATED USING THE |
| | CALCULATED BY CODE ANALYTICAL METHODS. THIS TERM |
| | ANALYTICAL METHOD DOES NOT SHOW UP IN THE CODE WHEN A |
| | WORD SEARCH IS COMPLETED. IT WOULD APPEAR THAT A WIND |
| | TUNNEL TEST WAS COMPLETED AS ALLOWED BY FBC-B 1609.1.1 |
| | EXCEPTION 6. WIND TUNNEL TEST ARE TO BE IN ACCORDANCE |
| | WITH CHAPTER 31 OF ASCE 7. PLEASE PROVIDE THE SIGNED |
| | AND SEALED WIND TUNNEL TEST OR PROVIDE HOW THESE |
| | PRESSURES WERE DERIVED. |
| | |
| | 8) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 9) PLEASE SHOW COMPLIANCE WITH : |
| | |
| | 9A) FBC-B 3308.2 UTILITY FIXTURES.BUILDING MATERIALS, |
| | FENCES, SHEDS OR ANY OBSTRUCTION OF ANY KIND SHALL NOT |
| | BE PLACED SO AS TO OBSTRUCT FREE APPROACH TO ANY FIRE |
| | HYDRANT, FIRE DEPARTMENT CONNECTION, UTILITY POLE, |
| | MANHOLE, FIRE ALARM BOX OR CATCH BASIN, OR SO AS TO |
| | INTERFERE WITH THE PASSAGE OF WATER IN THE GUTTER. |
| | PROTECTION AGAINST DAMAGE SHALL BE PROVIDED TO SUCH |
| | UTILITY FIXTURES DURING THE PROGRESS OF THE WORK, BUT |
| | SIGHT OF THEM SHALL NOT BE OBSTRUCTED. |
| | |
| | 9B)FBC-B 3306.9 ADJACENT TO EXCAVATIONS. |
| | EVERY EXCAVATION ON A SITE LOCATED 5 FEET (1524 MM) OR |
| | LESS FROM THE STREET LOT LINE SHALL BE ENCLOSED WITH A |
| | BARRIER NOT LESS THAN 6 FEET (1829 MM) HIGH. WHERE |
| | LOCATED MORE THAN 5 FEET (1524 MM) FROM THE STREET LOT |
| | LINE, A BARRIER SHALL BE ERECTED WHEN REQUIRED BY THE |
| | BUILDING OFFICIAL. BARRIERS SHALL BE OF ADEQUATE |
| | STRENGTH TO RESIST WIND PRESSURE AS SPECIFIED IN |
| | CHAPTER 16. |
| | |
| | 9C) FBC-B 3306.1 PROTECTION REQUIRED. PEDESTRIANS SHALL |
| | BE PROTECTED DURING CONSTRUCTION, REMODELING AND |
| | DEMOLITION ACTIVITIES AS REQUIRED BY THIS CHAPTER AND |
| | TABLE 3306.1. SIGNS SHALL BE PROVIDED TO DIRECT |
| | PEDESTRIAN TRAFFIC. |
| | |
| | 9D) FBC-B 3306.5 BARRIERS. BARRIERS SHALL BE A MINIMUM |
| | OF 8 FEET (2438 MM) IN HEIGHT AND SHALL BE PLACED ON |
| | THE SIDE OF THE WALKWAY NEAREST THE CONSTRUCTION. |
| | BARRIERS SHALL EXTEND THE ENTIRE LENGTH OF THE |
| | CONSTRUCTION SITE. OPENINGS IN SUCH BARRIERS SHALL BE |
| | PROTECTED BY DOORS WHICH ARE NORMALLY KEPT CLOSE |
| | |
| | 9E)FBC-B [F] 3309.1 WHERE REQUIRED. ALL STRUCTURES |
| | UNDER CONSTRUCTION, ALTERATION OR DEMOLITION SHALL BE |
| | PROVIDED WITH NOT LESS THAN ONE APPROVED PORTABLE FIRE |
| | EXTINGUISHER IN ACCORDANCE WITH SECTION 906 AND SIZED |
| | FOR NOT LESS THAN ORDINARY HAZARD AS FOLLOWS: |
| | 1. AT EACH STAIRWAY ON ALL FLOOR LEVELS WHERE |
| | COMBUSTIBLE MATERIALS HAVE ACCUMULATED. |
| | 2. IN EVERY STORAGE AND CONSTRUCTION SHED. |
| | 3. ADDITIONAL PORTABLE FIRE EXTINGUISHERS SHALL BE |
| | PROVIDED WHERE SPECIAL HAZARDS EXIST, SUCH AS THE |
| | STORAGE AND USE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS. |
| | |
| | 9F) FBC-B 3309.2 FIRE HAZARDS. |
| | THE PROVISIONS OF THIS CODE AND THE FLORIDA FIRE |
| | PREVENTION CODE SHALL BE STRICTLY OBSERVED TO SAFEGUARD |
| | AGAINST ALL FIRE HAZARDS ATTENDANT UPON CONSTRUCTION |
| | OPERATIONS. |
| | |
| | 9G) [F] 3311.1 WHERE REQUIRED. IN BUILDINGS REQUIRED TO |
| | HAVE STANDPIPES BY SECTION 905.3.1, NOT LESS THAN ONE |
| | STANDPIPE SHALL BE PROVIDED FOR USE DURING |
| | CONSTRUCTION. SUCH STANDPIPES SHALL BE INSTALLED WHEN |
| | THE PROGRESS OF CONSTRUCTION IS NOT MORE THAN 40 FEET |
| | (12 192 MM) IN HEIGHT ABOVE THE LOWEST LEVEL OF FIRE |
| | DEPARTMENT VEHICLE ACCESS. SUCH STANDPIPE SHALL BE |
| | PROVIDED WITH FIRE DEPARTMENT HOSE CONNECTIONS AT |
| | ACCESSIBLE LOCATIONS ADJACENT TO USABLE STAIRS. SUCH |
| | STANDPIPES SHALL BE EXTENDED AS CONSTRUCTION PROGRESSES |
| | TO WITHIN ONE FLOOR OF THE HIGHEST POINT OF |
| | CONSTRUCTION HAVING SECURED DECKING OR FLOORING. |
| | |
| | 9H) [F] 3312.1 COMPLETION BEFORE OCCUPANCY. |
| | IN BUILDINGS WHERE AN AUTOMATIC SPRINKLER SYSTEM IS |
| | REQUIRED BY THIS CODE, IT SHALL BE UNLAWFUL TO OCCUPY |
| | ANY PORTION OF A BUILDING OR STRUCTURE UNTIL THE |
| | AUTOMATIC SPRINKLER SYSTEM INSTALLATION HAS BEEN TESTED |
| | AND APPROVED, EXCEPT AS PROVIDED IN SECTION 111.3. |
| | |
| | 9H) 109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION |
| | ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A |
| | MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF |
| | ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO |
| | AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY THE |
| | APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS |
| | AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS |
| | INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST, |
| | NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE |
| | STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION |
| | ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE |
| | WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY |
| | REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH |
| | ENGINEERING STANDARDS TO PRESERVE THE |
| | POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY, |
| | DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW |
| | RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS, |
| | PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING |
| | PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ |
| | FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A |
| | PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED |
| | DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS |
| | PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A |
| | CERTIFICATION FROM A LICENSED ENGINEER SHALL BE |
| | SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL |
| | OF THE FINAL INSPECTION. |
| | |
| | 9I) 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE |
| | UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED |
| | MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR |
| | OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS. |
| | AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE |
| | HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH |
| | CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE |
| | EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN |
| | SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH |
| | CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING |
| | DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY |
| | PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE |
| | CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24 |
| | HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE |
| | SUBJECT TO A FINE NOT TO EXCEED $500.00. IN ADDITION TO |
| | THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS |
| | SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO |
| | SECTION 113 OF THIS CHAPTER. |
| | |
| | 10) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |