Plan Review Details - Permit 15030705
Plan Review Stops For Permit 15030705
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-05-04 Cont ID  
Sent By rmcdouga Date 2015-05-04 Time 18:52 Rev Time 0.00
Received By rmcdouga Date 2015-05-04 Time 18:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-03-31 Cont ID  
Sent By rmcdouga Date 2015-03-31 Time 11:49 Rev Time 0.00
Received By rmcdouga Date 2015-03-31 Time 11:49 Sent To  
Notes
2015-03-31 11:43:16PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PLANS ARE REQUIRED TO HAVE THE ENGINEER'S
 HANDWRITTEN SIGNATURE. DIGITAL SIGNATURES ARE ONLY
 VALID FOR ELECTRONICALLY TRANSMITTED PLANS AND OTHER
 DOCUMENTS. FS 471, FAC 61G15-23.002 & FAC 61G15-23.003
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-05-04 Cont ID  
Sent By rmcdouga Date 2015-05-04 Time 18:44 Rev Time 0.00
Received By rmcdouga Date 2015-05-04 Time 18:36 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-03-31 Cont ID  
Sent By rmcdouga Date 2015-03-31 Time 11:50 Rev Time 0.00
Received By rmcdouga Date 2015-03-31 Time 11:50 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2015-03-31 Cont ID  
Sent By rmcdouga Date 2015-03-31 Time 11:50 Rev Time 0.00
Received By rmcdouga Date 2015-03-31 Time 11:50 Sent To  
Notes
2015-03-31 11:51:23NO GAS IS SHOWN ON THE PLANS AND NO GAS PERMIT WAS
 APPLIED FOR.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By tlarge Date 2015-05-04 Time   Rev Time 0.00
Received By dhayes Date 2015-04-22 Time 16:22 Sent To P
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-03-31 Cont ID  
Sent By tklarge Date 2015-03-31 Time 13:32 Rev Time 0.00
Received By tklarge Date 2015-03-18 Time 10:41 Sent To  
Notes
2015-03-23 10:41:53SENT TO ZONING SHELF FOR REVIEW. JG.

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-04-28 Cont ID  
Sent By tklarge Date 2015-04-28 Time 10:01 Rev Time 0.00
Received By tklarge Date 2015-04-28 Time 10:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-03-31 Cont ID  
Sent By tklarge Date 2015-03-31 Time 13:32 Rev Time 0.00
Received By tklarge Date 2015-03-31 Time 13:32 Sent To  
Notes
2015-03-31 13:29:30THE PLANS ARE REQUIRED TO HAVE THE ENGINEER'S WET
 SIGNATURE.DIGITAL SIGNATURES ARE ONLY VALID FOR
 ELECTRONICALLY SUBMITTED PLANS AND OTHER DOCUMENTS. FL.
 STATUTE 471, FAC RULE 61G15-23.002 & FAC RULE
 61G15-23.003.

Review Stop Z ZONING
Rev No 1 Status P Date 2015-03-31 Cont ID  
Sent By sgraham Date 2015-03-31 Time 09:46 Rev Time 0.00
Received By sgraham Date 2015-03-31 Time 09:46 Sent To  
Notes
***NONE***