Plan Review Details - Permit 15030665
Plan Review Stops For Permit 15030665
Review Stop G GAS REVIEW
Rev No 1 Status F Date 2015-03-21 Cont ID  
Sent By tklarge Date 2015-03-21 Time 07:09 Rev Time 0.00
Received By tklarge Date 2015-03-21 Time 06:40 Sent To  
Notes
2015-03-21 07:27:071) INDICATE ON THE PLAN IF THE EXISTING GAS METER WILL
 REMAIN OR BE REMOVED. THE PLAN IS NOT CLEAR. WPB AMEND.
 TO 2010 FBC SEC.107.2.1
 2) THE PLAN SHOWS PE PIPE TO BE INSTALLED. PLASTIC PIPE
 SHALL BE INSTALLED OUTDOORS UNDERGROUND ONLY PER 2010
 FUEL GAS CODE SEC.404.15.1.THE PLAN APPEARS TO SHOW THE
 PIPE ABOVEGROUND.
 3) INDICATE THE APPLICABLE GAS SIZING TABLE BEING USED
 TO SIZE THE GAS LINE.THE PLANE REFERS TO TABLE 402.4
 (3) WHICH IS FOR METALLIC PIPE BUT THE PLAN SHOWS PE
 PIPE.
 4) 2010 FUEL GAS CODE SEC. 616.1 - PERMANENTLY
 INSTALLED EQUIPMENT POWERED BY INTERNAL COMBUSTION
 ENGINES AND TURBINES SHALL BE INSTALLED IN ACCORDANCE
 WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS AND
 NFPA 37. STATIONARY ENGINE GENERATOR ASSEMBLIES SHALL
 MEET THE REQUIREMENTS OF UL 2200.
 5) SUBMIT MANUFACTURER'S SPECIFICATION / INSTALLATION
 SHEETS FOR REVIEW. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  