Plan Review Details - Permit 15030663
Plan Review Stops For Permit 15030663
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-07-17 Cont ID  
Sent By jwitmer Date 2015-07-17 Time 08:32 Rev Time 0.00
Received By jwitmer Date 2015-07-16 Time 07:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-04-02 Cont ID  
Sent By jwitmer Date 2015-04-02 Time   Rev Time 0.00
Received By jwitmer Date 2015-04-02 Time   Sent To  
Notes
2015-04-02 15:01:28BUILDING PLAN REVIEW
 W. P. B. PERMIT:
 ADD:
 CONT:
 TEL: (
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURSDAY APRIL 02/ 2015
 ACTION: DENIED
  
 1) SHEET C-5 DETAIL # 1 PERMANENT LADDER WILL NEED TO
 PROVIDE ADDITIONAL DETAILS AND OR INFORMATION ON THE
 FOLLOWING CODE ITEMS:
 2010 FBC-B 1509.6.3. LADDERS SHALL HAVE A TOE SPACING
 NOT LESS THAN 6 INCHES (152 MM) DEEP.
 1509.6.4. THERE SHALL BE A MINIMUM OF 18 INCHES (457
 MM) BETWEEN RAILS.
 1509.6.7. LADDERS SHALL BE PROTECTED AGAINST CORROSION
 BY APPROVED MEANS.
  
 2) ZONING APPEARS TO REQUIRE SCREENING OF THE NEW
 GENERATOR. PLEASE PROVIDE STRUCTURAL INFORMATION FOR
 SCREEN FRAMEWORK AND THE TYPE OF SCREENING MATERIAL TO
 BE INSTALLED. PLEASE PROVIDE ADDITIONAL INFORMATION AS
 TO TYPE OF STRUCTURE AND ATTACHMENT TO THE MAIN
 STRUCTURAL. 107.2.1.3 ADDITIONAL INFORMAATION IS
 REQUIRED.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-08-31 Cont ID  
Sent By ppetty Date 2015-08-31 Time 10:36 Rev Time 0.00
Received By ppetty Date 2015-08-31 Time 10:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-03-30 Cont ID  
Sent By tlarge Date 2015-03-30 Time 16:42 Rev Time 0.00
Received By dhayes Date 2015-03-30 Time 16:42 Sent To G
Notes
2015-03-30 16:48:38PROVIDE MANUFACTURER PRODUCT SPECIFICATION
 DOCUMENTATION ON ATS AND GENERATOR
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-08-06 Cont ID  
Sent By pleduc Date 2015-08-06 Time   Rev Time 0.00
Received By pleduc Date 2015-08-06 Time 13:26 Sent To  
Notes
2015-08-06 13:36:27THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THERE ARE INCORRECT REFERENCES TO THE FIRE CODE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2015-08-28 Cont ID  
Sent By tklarge Date 2015-08-28 Time 13:04 Rev Time 0.00
Received By tklarge Date 2015-08-28 Time 13:04 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2015-04-01 Cont ID  
Sent By tklarge Date 2015-04-01 Time 05:52 Rev Time 0.00
Received By tklarge Date 2015-03-31 Time 05:25 Sent To  
Notes
2015-03-31 06:58:251) INDICATE THE TYPE OF PIPE BEING INSTALLED. THE
 DESIGN PARAMETERS ON SHT. P1 REFER TO TABLE 402.4 (3)
 WHICH IS FOR SCH. 40 STEEL PIPE BUT THE PLAN SHOWS PE
 PIPE. CLARIFY.
 2) 2010 FUEL GAS CODE SEC.616.1 - GENERATOR SHALL MEET
 THE REQUIREMENTS OF UL 2200 AND INTSALLED IN ACCORDANCE
 W/ MANUF. INSTRUCTIONS AND NFPA 37. SUBMIT
 DOCUMENTATION SHOWING COMPLIANCE WITH THESE STANDARDS.
 THE PLANS ARE VAGUE AS TO COMPLIANCE W/UL2200.
 3)INDICATE ON THE PLANS IF THE EXISTING GAS METER IS
 GOING TO REMAIN OR BE REMOVED.
 4) SHT. P1 SHOWS PE PIPE TO THE GENERATOR. PE PIPE CAN
 ONLY BE USED OUTSIDE, UNDERGROUND PER THE 2010 FGC
 SEC.404.15.
 5) SHT. P1 NOTE #20 REFERS TO 2004 GAS CODE. CLARIFY.
 6) INDICATE THE BTU LOAD OF THE GENERATOR.
 7) SUBMIT MANUF. SPECS FOR THE REGULATOR. REGULATORS
 INSTALLED OUTDOORS SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-08-31 Cont ID  
Sent By lmarchan Date 2015-08-31 Time 10:53 Rev Time 0.00
Received By lmarchan Date 2015-06-30 Time   Sent To  
Notes
2015-08-28 10:32:01TLARGE DESK
2015-06-30 13:06:20B08

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-04-02 Cont ID  
Sent By   Date 2015-04-02 Time   Rev Time 0.00
Received By   Date 2015-04-02 Time   Sent To  
Notes
2015-03-27 11:10:12TO ELECTRIC.
2015-03-17 15:32:42ROUTED TO ZONING

Review Stop Z ZONING
Rev No 2 Status P Date 2015-07-17 Cont ID  
Sent By aaponte Date 2015-07-17 Time 15:06 Rev Time 0.00
Received By aaponte Date 2015-07-17 Time 15:06 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2015-03-27 Cont ID  
Sent By aaponte Date 2015-03-27 Time 10:43 Rev Time 0.00
Received By aaponte Date 2015-03-27 Time 10:39 Sent To  
Notes
2015-03-27 11:09:561. PLEASE PROVIDE INFORMATION TO CONFIRM THE NEW
 MECHANICAL EQUIPMENT IS SCREENED FROM VIEW. SCREENING
 SHALL BE AT LEAST THE SAME HEIGHT OF THE EQUIPMENT.
 2. PLEASE PROVIDE A SURVEY OF THE SITE INDICATING THE
 LOCATION OF THE GENERATOR.
 3. PLEASE INCLUDE PHOTOS.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439.