Plan Review Details - Permit 15030550
Plan Review Stops For Permit 15030550
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2015-04-30 Cont ID  
Sent By shill Date 2015-04-30 Time 15:22 Rev Time 0.00
Received By shill Date 2015-04-30 Time 15:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-04-16 Cont ID  
Sent By shill Date 2015-04-16 Time 11:03 Rev Time 0.00
Received By shill Date 2015-04-16 Time 10:45 Sent To  
Notes
2015-04-16 11:03:31****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
 [email protected]
  
 FBC FLORIDA BUILDING CODE 2010
  
 3RD REVIEW, REPORTS FOR 6" CONCRETE SLAB, ACOUSTICORK
 6MM, 14MM (.56") WOOD FLOOR SUBMITTED; NOT CONSISTENT
 WITH THIS APPLICATION. STC=52, IIC=50.
 2ND REVIEW, COMMENTS NOT ADDRESSED. APPLICANT SUBMITTED
 A BASIC FLOOR PLAN AND ACOUSTICORK SPEC SHEETS.
 1ST REVIEW, ACOUSTICORK BROCHURE SUBMITTED AND R60
 CIRCLED - BROCHURE STATES THAT A SUSPENDED CEILING IS
 REQUIRED (THEREFORE CANNOT BE USED FOR THIS PROJECT)
  
  
 COMMENTS FROM PREVIOUS LISTS:
  
 1. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 IF A SUSPENDED CEILING WAS USED AS A PART OF THE TEST,
 PROVIDE INFORMATION AS TO HOW IT HAS BEEN DETERMINED
 THAT THIS CONDITION CURRENTLY EXISTS AND HOW IT CAN BE
 GUARANTEED THAT THE CONDITIONS IN THE UNIT BELOW WILL
 NOT BE ALTERED.
  
 PLEASE PROVIDE A COPY OF THE TEST REPORT.
  
 REVIEW #3, TEST IS FOR A .56" (14MM) WOOD FLOOR OVER
 6MM ACOUSTICORK, 6" CONCRETE SLAB. THIS APPLICATION IS
 FOR A LAMINATE FLOOR. IT IS NOT CLEAR WHICH OF THE
 ACOUSTICORK PRODUCTS IS PROPOSED.
  
 2. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. IF A SUSPENDED CEILING WAS USED AS A PART
 OF THE TEST, PROVIDE INFORMATION AS TO HOW IT HAS BEEN
 DETERMINED THAT THIS CONDITION CURRENTLY EXISTS AND HOW
 IT CAN BE GUARANTEED THAT THE CONDITIONS IN THE UNIT
 BELOW WILL NOT BE ALTERED.
  
 PLEASE PROVIDE A COPY OF THE TEST REPORT.
  
 REVIEW #3, TEST IS FOR A .56" (14MM) WOOD FLOOR OVER
 6MM ACOUSTICORK, 6" CONCRETE SLAB. THIS APPLICATION IS
 FOR A LAMINATE FLOOR. IT IS NOT CLEAR WHICH OF THE
 ACOUSTICORK PRODUCTS IS PROPOSED.
  
 3. OK
  
 4. APPLICATION LICENSE NUMBER IS "B14.1392020"; THIS
 DOES NOT APPEAR TO BE A CONTRACTOR LICENSE NUMBER. PALM
 BEACH COUNTY RECORDS DO NOT SHOW A LICENSE FOR DONALD
 BRODSKY (INDIVIDUAL WHO SIGNED AS CONTRACTOR). PALM
 BEACH COUNTY RECORDS SHW GEORGE VAN HAEZEBROUCK AS
 QUALIFIER FOR "HOUSE OF FLOORS". IF THIS IS THE
 APPLICANT, A NEW APPLICATION SIGNED BY THE QUALIFIER
 WILL BE REQUIRED AS THE CITY OF WEST PALM BEACH DOES
 NOT ACCEPT PERMIT APPLICATIONS SIGNED BY AUTHORIZED
 AGENTS.
  
 3RD REVIEW, NOT ADDRESSED.
  
 5. THE OWNER'S SIGNATURE IS BLANK, ALTHOUGH IT IS
 NOTARIZED. PLEASE REFER THE NOTARY TO FS 117.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-04-07 Cont ID  
Sent By shill Date 2015-04-07 Time 14:12 Rev Time 0.00
Received By shill Date 2015-04-07 Time 14:12 Sent To  
Notes
2015-04-07 14:14:57****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
 [email protected]
  
 FBC FLORIDA BUILDING CODE 2010
  
 2ND REVIEW, COMMENTS NOT ADDRESSED. APPLICANT SUBMITTED
 A BASIC FLOOR PLAN AND ACOUSTICORK SPEC SHEETS.
  
 COMMENTS FROM PREVIOUS LIST:
  
 1. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 IF A SUSPENDED CEILING WAS USED AS A PART OF THE TEST,
 PROVIDE INFORMATION AS TO HOW IT HAS BEEN DETERMINED
 THAT THIS CONDITION CURRENTLY EXISTS AND HOW IT CAN BE
 GUARANTEED THAT THE CONDITIONS IN THE UNIT BELOW WILL
 NOT BE ALTERED.
  
 PLEASE PROVIDE A COPY OF THE TEST REPORT.
  
 2. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. IF A SUSPENDED CEILING WAS USED AS A PART
 OF THE TEST, PROVIDE INFORMATION AS TO HOW IT HAS BEEN
 DETERMINED THAT THIS CONDITION CURRENTLY EXISTS AND HOW
 IT CAN BE GUARANTEED THAT THE CONDITIONS IN THE UNIT
 BELOW WILL NOT BE ALTERED.
  
 PLEASE PROVIDE A COPY OF THE TEST REPORT.
  
 3. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM
 E 84 OR UL 723.
  
 4. APPLICATION LICENSE NUMBER IS "B14.1392020"; THIS
 DOES NOT APPEAR TO BE A CONTRACTOR LICENSE NUMBER. PALM
 BEACH COUNTY RECORDS DO NOT SHOW A LICENSE FOR DONALD
 BRODSKY (INDIVIDUAL WHO SIGNED AS CONTRACTOR). PALM
 BEACH COUNTY RECORDS SHW GEORGE VAN HAEZEBROUCK AS
 QUALIFIER FOR "HOUSE OF FLOORS". IF THIS IS THE
 APPLICANT, A NEW APPLICATION SIGNED BY THE QUALIFIER
 WILL BE REQUIRED AS THE CITY OF WEST PALM BEACH DOES
 NOT ACCEPT PERMIT APPLICATIONS SIGNED BY AUTHORIZED
 AGENTS.
  
 5. THE OWNER'S SIGNATURE IS BLANK, ALTHOUGH IT IS
 NOTARIZED. PLEASE REFER THE NOTARY TO FS 117.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-03-16 Cont ID  
Sent By shill Date 2015-03-16 Time 11:55 Rev Time 0.00
Received By shill Date 2015-03-16 Time 11:55 Sent To  
Notes
2015-03-16 11:55:37****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
 [email protected]
  
 FBC FLORIDA BUILDING CODE 2010
  
 TWO COMPLETE COLLATED SETS OF ALL DOCUMENTS REQUIRED
  
 1. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 IF A SUSPENDED CEILING WAS USED AS A PART OF THE TEST,
 PROVIDE INFORMATION AS TO HOW IT HAS BEEN DETERMINED
 THAT THIS CONDITION CURRENTLY EXISTS AND HOW IT CAN BE
 GUARANTEED THAT THE CONDITIONS IN THE UNIT BELOW WILL
 NOT BE ALTERED.
  
 PLEASE PROVIDE A COPY OF THE TEST REPORT.
  
 2. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. IF A SUSPENDED CEILING WAS USED AS A PART
 OF THE TEST, PROVIDE INFORMATION AS TO HOW IT HAS BEEN
 DETERMINED THAT THIS CONDITION CURRENTLY EXISTS AND HOW
 IT CAN BE GUARANTEED THAT THE CONDITIONS IN THE UNIT
 BELOW WILL NOT BE ALTERED.
  
 PLEASE PROVIDE A COPY OF THE TEST REPORT.
  
 3. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM
 E 84 OR UL 723.
  
 4. APPLICATION LICENSE NUMBER IS "B14.1392020"; THIS
 DOES NOT APPEAR TO BE A CONTRACTOR LICENSE NUMBER. PALM
 BEACH COUNTY RECORDS DO NOT SHOW A LICENSE FOR DONALD
 BRODSKY (INDIVIDUAL WHO SIGNED AS CONTRACTOR). PALM
 BEACH COUNTY RECORDS SHW GEORGE VAN HAEZEBROUCK AS
 QUALIFIER FOR "HOUSE OF FLOORS". IF THIS IS THE
 APPLICANT, A NEW APPLICATION SIGNED BY THE QUALIFIER
 WILL BE REQUIRED AS THE CITY OF WEST PALM BEACH DOES
 NOT ACCEPT PERMIT APPLICATIONS SIGNED BY AUTHORIZED
 AGENTS.
  
 5. THE OWNER'S SIGNATURE IS BLANK, ALTHOUGH IT IS
 NOTARIZED. PLEASE REFER THE NOTARY TO FS 117.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-04-16 Cont ID  
Sent By shill Date 2015-04-16 Time 11:03 Rev Time 0.00
Received By shill Date 2015-04-15 Time 08:20 Sent To B
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-04-07 Cont ID  
Sent By shill Date 2015-04-07 Time 14:15 Rev Time 0.00
Received By shill Date 2015-03-24 Time 13:37 Sent To  
Notes
2015-03-24 13:38:01RE-SUBMITTAL SENT TO SAMANTHA HILL FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-03-16 Cont ID  
Sent By shill Date 2015-03-16 Time 11:55 Rev Time 0.00
Received By shill Date 2015-03-13 Time 17:37 Sent To  
Notes
2015-03-13 17:37:47SENT TO BUILDING UNDER $5000