| | 1ST ELECTRICAL PLAN REVIEWON REVISION #15030533 |
| | ACTION: DENIED |
| | |
| | 1) FBC 107.2 CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHOULD BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE AND EXTENT OF WORK |
| | PROPOSED. CLARIFY THE NOTES ON THE "SPECIAL POLE |
| | LEGEND" THERE ARE NO CORRESPONDING NOTES ON THE PLAN |
| | INDICATING THE USE OF ANY OF THE SPECIAL NOTES. |
| | |
| | 2) PROVIDE A SITE PLAN INDICATING THE LOCATION OF EACH |
| | OF THE TYPES OF LOW VOLTAGE APPLICATIONS INCLUDING THE |
| | LOCATIONS OF ANY ASSOCIATED HARDWARE. SOME HAVE CAMERAS |
| | AND SOME HAVE CALL BOXES? PROVIDE INFORMATION AND |
| | LOCATIONS ON ANY ADDITIONAL TYPES OF SPECIALTY LOW |
| | VOLTAGE APPLICATIONS. |
| | |
| | 3) PROVIDE MANUFACTURER PRODUCT APPROVAL DOCUMENTATION |
| | FOR THE CAMERAS, CALL BOXES, ASSOCIATED HARDWARE, AND |
| | CABLES USED TO CONNECT THEM. |
| | |
| | 4) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY |
| | MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS |
| | ARE REQUIRED FOR CCTV, NETWORK, AND COMMUNICATION.(CALL |
| | BOXES). THE APPLICATION FOR THIS REVISION TO THE |
| | ORIGINAL SITE LIGHTING PERMIT STATES THAT THE LOW |
| | VOLTAGE WIRING FOR THE CAMERAS WILL BE INSTALLED BY |
| | OTHERS.PROVIDE APPLICATIONS WITH SHOP DRAWINGS PRODUCT |
| | APPROVALS ON ALL INSTALLED EQUIPMENT AND CABLES |
| | INVOLVED. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |