| Plan Review Stops For Permit 15030464 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2015-07-21 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-07-21 |
Time |
18:11 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-07-21 |
Time |
18:11 |
Sent To |
|
|
| Notes |
| 2015-07-21 18:13:45 | SEE PERMIT #15030458 FOR PLANS AND CONSTRUCTION | | | DOCUMENTS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2015-06-29 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-06-29 |
Time |
13:30 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-06-29 |
Time |
13:48 |
Sent To |
|
|
| Notes |
| 2015-06-29 13:31:45 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | THE BUILDING PLAN INDICATES THAT LOT 14 IS AN AVANTI | | | MODEL AND THE ENERGY CALULATION IS FOR THE AVANTI | | | MODEL. THE APPLICATION AND PROJECT DOCS DESCRIPTION HAS | | | CASSANDRA MODEL. IT APPEARS THAT THE APPLICATION SHOULD | | | BE CHANGED TO THE AVANTI MODEL. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2015-04-28 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-04-28 |
Time |
17:49 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-04-28 |
Time |
17:49 |
Sent To |
|
|
| Notes |
| 2015-04-30 12:54:47 | THE BUILDING PLAN INDICATES THAT LOT 14 IS AN AVANTI | | | MODEL AND THE ENERGY CALULATION IS FOR THE AVANTI | | | MODEL. THE APPLICATION THE APPLICATION HAS CASSANDRA | | | MODEL. IT APPEARS THAT THE APPLICATION SHOULD BE | | | CHANGED TO THE AVANTI MODEL. | | 2015-04-28 17:52:08 | SEE COMMENTS FOR PERMIT # 15030458. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2015-07-21 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-07-21 |
Time |
18:12 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-07-21 |
Time |
18:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
N |
Date |
2015-07-06 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2015-07-06 |
Time |
18:13 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2015-07-06 |
Time |
18:12 |
Sent To |
|
|
| Notes |
| 2015-07-06 18:14:09 | 7/06/15 - FOR ELECTRICAL REVIEW RESULTS AND DATA, SEE | | | PERMIT 15030458. MA |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2015-04-28 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-04-28 |
Time |
17:49 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-04-28 |
Time |
17:49 |
Sent To |
|
|
| Notes |
| 2015-04-28 17:52:19 | SEE COMMENTS FOR PERMIT # 15030458. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2015-07-21 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-07-21 |
Time |
18:13 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-07-14 |
Time |
07:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2015-07-09 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-07-09 |
Time |
18:15 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-06-08 |
Time |
08:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2015-04-30 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-04-30 |
Time |
14:57 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-04-17 |
Time |
09:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2015-07-09 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-07-09 |
Time |
18:15 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-07-09 |
Time |
18:15 |
Sent To |
|
|
| Notes |
| 2015-07-09 18:16:21 | MU 2015 - 16755 |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2015-04-28 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-04-28 |
Time |
17:49 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-04-28 |
Time |
17:49 |
Sent To |
|
|
| Notes |
| 2015-04-28 17:52:57 | SEE COMMENTS FOR PERMIT # 15030458. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2015-07-21 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-07-21 |
Time |
18:14 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-07-21 |
Time |
18:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2015-07-09 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-07-09 |
Time |
18:15 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-07-09 |
Time |
18:15 |
Sent To |
|
|
| Notes |
| 2015-07-09 18:15:33 | SEE REVIEW COMMENTS FOR PERMIT #15030458. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2015-04-30 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-04-30 |
Time |
14:57 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-04-28 |
Time |
17:42 |
Sent To |
|
|
| Notes |
| 2015-04-30 14:57:00 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC 2010 | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY MECHANICAL | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE APPLICATION SPECIFIES THAT THIS IS THE CASSANDRA | | | MODEL AND THAT IT IS LOCATED ON LOT 14. THE BUILDING | | | PLANS INDICATE THAT LOT 14 IS AN END UNIT AND IS AN | | | AVANTI MODEL. THE ENERGY CALCULATIONS SUBMITTED ARE FOR | | | THE AVANTI MODEL. PLEASE CORRECT. FBC 107.2.1 | | | | | | 2) THE ENERGY FORM IS MISSING THE FOLLOWING | | | INFORMATION: OWNER, BUILDER NAME, PERMIT OFFICE ( CITY | | | OF WEST PALM BEACH ), JURISDICTION ( 604700 ). FBC | | | 107.2.1.4 | | | | | | 3) THE ENERGY CALCULATIONS APPEAR TO HAVE USED AN | | | INCORRECT ORIENTATION FOR THE AVANTI MODEL ON LOT 14. | | | THE 3080 ENTRY DOOR ON THE SIDE FACES SOUTH NOT EAST. | | | THE WINDOWS ARE LOCATED ON THE EAST, WEST AND SOUTH | | | SIDES OF THIS END UNIT. THE 64 SQFT SLIDING GLASS DOOR | | | FACES WEST NOT NORTH. FBC 107.2.1 | | | | | | 4) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE | | | FRONT DOOR IS FOR A GLAZED SINGLE FRENCH DOOR WHERE THE | | | GLASS AREA IS EQUAL OR GREATER THAN ONE THIRD OF THE | | | DOOR AREA. THIS DOOR IS REQUIRED TO BE INCLUDED IN THE | | | GLAZING CALCULATION AS A TOTAL FENESTRATION. FBC ENERGY | | | SECTION 405.5.3 | | | | | | 5) THE END UNITS TYPICALLY REQUIRE LARGER HEATING AND | | | COOLING LOADS THAN THE UNITS IN BETWEEN. THEY HAVE AN | | | EXTRA EXTERIOR WALL WITH WINDOWS. REVIEW THE | | | CALCULATIONS TO DETERMINE WHY ALL OF THE UNITS HAVE THE | | | SAME LOADS. FBC 107.2.1 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2015-06-25 |
|
|
Cont ID |
|
| Sent By |
tklarge |
Date |
2015-06-25 |
Time |
05:33 |
Rev Time |
0.00 |
| Received By |
tklarge |
Date |
2015-06-25 |
Time |
05:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2015-04-28 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2015-04-28 |
Time |
17:49 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2015-04-28 |
Time |
17:49 |
Sent To |
|
|
| Notes |
| 2015-04-28 17:52:36 | SEE COMMENTS FOR PERMIT # 15030458. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2015-06-15 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2015-06-15 |
Time |
15:10 |
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2015-06-15 |
Time |
15:10 |
Sent To |
|
|
| Notes |
| 2015-06-15 15:11:16 | ZONING APPROVED WITH THE FOLLOWING PROVISO: | | | | | | 1.) DRIVEWAY SHALL BE SETBACK AT LEAST 3 FT. FROM THE | | | INTERIOR SIDE PROPERTY LINE. | | | | | | * SEPARATE PERMIT REQUIRED FOR LANDSCAPING. | | | | | | CALL LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2015-04-29 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2015-04-29 |
Time |
12:02 |
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2015-04-29 |
Time |
12:02 |
Sent To |
|
|
| Notes |
| 2015-04-29 12:03:14 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) THE APPROVED PLAT FOR THE DEVELOPMENT SHALL BE | | | REVIEWED BY ENGINEERING SERVICES AND RECORDED IN THE | | | PUBLIC RECORDS OF PALM BEACH COUNTY PRIOR TO THE | | | APPROVAL OF THIS PERMIT. | | | | | | 2.) PROVIDE SETBACK DIMENSIONS FOR ALL STRUCTURAL | | | ELEMENTS, INCLUDING BUT NOT LIMITED TO THE A/C UNIT, | | | DRIVEWAY/STEPS, ETC. | | | | | | 3.) AREA CALCULATIONS FOR UNIT REQUIRED IN PLANS. | | | | | | 4.) SEPARATE REVIEW AND PERMIT APPLICATION REQUIRED FOR | | | LANDSCAPING, DRIVEWAYS AND STEPS. | | | | | | PLEASE NOTE THAT ANY CHANGES ON THE RESUBMITTED PLANS | | | MAY RESULT IN ADDITIONAL COMMENTS. CONTACT LINDA LOUIE | | | @ (561) 822-1458 IF YOU HAVE QUESTIONS. | | | | | | ART IN PUBLIC PLACES REQUIREMENT: | | | | | | PURSUANT TO THE ART IN PUBLIC PLACES ORDINANCE NO. | | | 4504-14, AN ART ASSESSMENT FOR THE PROJECT IS REQUIRED. | | | THE APPLICANT SHALL COMPLETE ONE OF THE FOLLOWING | | | WITHIN NINETY (90) DAYS OF THE ISSUANCE OF THE FIRST | | | BUILDING PERMIT: | | | | | | OPTION 1: SUBMIT DOCUMENTATION EVIDENCING THE ESCROW OF | | | FUNDS FOR A WORK OF ART OR HISTORIC OR CULTURAL | | | ELEMENTS VALUED IN AN AMOUNT OF ONE PERCENT OF THE | | | TOTAL VERTICAL CONSTRUCTION COSTS IN COMPLIANCE WITH | | | ORDINANCE NO. 4504-14 AND SUBMIT AN APPLICATION FOR | | | APPROVAL OF THE WORK OF ART OR HISTORIC OR CULTURAL | | | ELEMENTS. | | | | | | OPTION 2: CONTRIBUTE AN AMOUNT EQUAL TO ONE PERCENT OF | | | THE TOTAL VERTICAL CONSTRUCTION COSTS FOR DEPOSIT TO | | | THE ART IN PUBLIC PLACES FUND. | | | | | | *** UNLESS AN ALTERNATIVE DEADLINE IS ESTABLISHED IN A | | | DEVELOPMENT ORDER, OR A TIME EXTENSION IS GRANTED BY | | | THE DIRECTOR OF DEVELOPMENT SERVICES, NO CERTIFICATE OF | | | OCCUPANCY FOR THE PROJECT SHALL BE ISSUED UNTIL THE | | | ARTWORK IS INSTALLED, THE FINAL REVISED CONSTRUCTION | | | COST AFFIDAVIT AND ACCOUNTING OF THE ESCROWED ART FUNDS | | | HAS BEEN PROVIDED; AND/OR THE FULL ART ASSESSMENT HAS | | | BEEN PAID TO THE CITY. *** | | | | | | |
|
|