| 2015-03-17 07:53:02 | |
| | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15030405 |
| | ADD: 4801 DREHER TRL N. |
| | CONT: HEDRICK BROTHERS |
| | TEL: (561)689-8880 |
| | E-MAIL:[email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. MARCH 18/ 2015 |
| | ACTION: DENIED |
| | |
| | IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015 |
| | ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED |
| | ELECTRONICALLY |
| | UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS |
| | SUBMISSION OPTIONS ARE AS FOLLOWS: |
| | 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL |
| | SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE |
| | THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| | 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL |
| | SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED |
| | NAMING CONVENTION FOR EACH DOCUMENT |
| | 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER |
| | DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE |
| | REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| | 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT |
| | TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS |
| | ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES |
| | AVAILABLE |
| | |
| | 1) SHEET A-1 THE EARLY LEARNING GALLERY SHOWS AN |
| | OCCUPANT LOAD OF 16. 773 SQ. FT./ 16= 45.8 SQ. FT. PER |
| | OCCUPANT. PLEASE PROVIDE HOW THIS CALCULATION WAS |
| | FIGURED. THE PLANS ARE FOR THE SCIENCE MUSEUM WHICH WE |
| | WOULD USE 15 SQ. FT. PER OCCUPANT FOR VIEWING AREAS |
| | WHERE THE PUBLIC WILL GATHER. |
| | 2010 FBC-B TABLE 1004.1.1. WHEN 773 SQ. FT. /15= 52 |
| | OCCUPANTS (FBC-B TABLE 1004.1.1.) THIS WILL REQUIRE (2) |
| | EXITS (TABLE 1015.1) AND 1/3RD THE DISTANCE APART FBC-B |
| | 1015.2.1 EXCEP # 2. |
| | |
| | PLEASE PROVIDE WHAT THE USAGE OF THIS ROOM WILL BE AND |
| | WHY THE REDUCED OCCUPANT LOAD ONLY REQUIRING 1 EXIT |
| | FROM THIS AREA. 107.2.1.3 ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | DEVELOPMENT SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | |
| | |