| 2015-04-07 17:09:57 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | 1. FOOTINGS TO BE MINIMUM 12" BELOW THE UNDISTURBED |
| | GROUND SURFACE, FBC 1809.4. |
| | |
| | 2. THE INDEX SHEET FOR THE CALCULATIONS ARE TO BE IN |
| | THE FOLLOWING FORMAT PER FAC61G15-23.002(2)(B): |
| | |
| | WHEN AN ENGINEER MUST SEAL, SIGN AND DATE ENGINEERING |
| | SPECIFICATIONS OR CALCULATIONS UNDER THE PROVISIONS OF |
| | SECTION 471.025, F.S., AND SUBSECTION (1) OF THIS RULE, |
| | AN INDEX SHEET FOR ENGINEERING SPECIFICATIONS AND |
| | CALCULATIONS MAY BE USED. THE INDEX SHEET MUST BE |
| | SIGNED, SEALED AND DATED BY THOSE PROFESSIONAL |
| | ENGINEERS IN RESPONSIBLE CHARGE OF THE PRODUCTION AND |
| | PREPARATION OF EACH SECTION OF THE ENGINEERING |
| | SPECIFICATIONS OR CALCULATIONS, WITH SUFFICIENT |
| | INFORMATION ON INDEX SHEET SO THAT THE USER WILL BE |
| | AWARE OF EACH PORTION OF THE SPECIFICATIONS OR |
| | CALCULATIONS FOR WHICH EACH PROFESSIONAL ENGINEER IS |
| | RESPONSIBLE. IN ADDITION, THE INDEX SHEET SHALL INCLUDE |
| | AT A MINIMUM: |
| | 1. THE NAME, ADDRESS AND LICENSE NUMBER OF EACH |
| | ENGINEER IN RESPONSIBLE CHARGE OF THE PRODUCTION OF ANY |
| | PORTION OF THE CALCULATIONS OR SPECIFICATIONS. |
| | 2. IDENTIFICATION OF THE PROJECT, BY ADDRESS OR BY LOT |
| | NUMBER, BLOCK NUMBER, SECTION OR SUBDIVISION AND CITY |
| | OR COUNTY. |
| | 3. IDENTIFICATION OF THE APPLICABLE BUILDING CODE AND |
| | CHAPTER(S) THAT THE DESIGN IS INTENDED TO MEET. |
| | 4. IDENTIFICATION OF ANY COMPUTER PROGRAM USED FOR |
| | ENGINEERING THE SPECIFICATIONS OR CALCULATIONS. |
| | |
| | 3. THE PROPOSED IMPROVEMENT IS TO RESIST FLOOD LOADS AS |
| | THIS IS LOCATED IN A SPECIAL HAZARD FLOOD ZONE, |
| | FBC1612.2. REVISE DESIGN CRITERIA. |
| | |
| | |
| | |
| | |