Plan Review Details - Permit 15030360
Plan Review Stops For Permit 15030360
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-06-27 Cont ID  
Sent By jwitmer Date 2015-06-27 Time 10:28 Rev Time 0.00
Received By jwitmer Date 2015-06-27 Time 10:28 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-06-23 Cont ID  
Sent By jwitmer Date 2015-06-23 Time 12:27 Rev Time 0.00
Received By jwitmer Date 2015-06-23 Time 09:31 Sent To  
Notes
2015-06-23 13:33:05BUILDING PLAN REVIEW
 W. P. B. REVISION: 15030360
 W. P. B. PERMIT: 13110271
 ADD: 1750 OKEECHOBEE RD.
 CONT: THORTON & THORTON
 TEL: (321)229-3406
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. JUNE 23/ 2015
 ACTION: DENIED
  
 1) BECAUSE OF THE WELDING ON THIS PROJECT AND THE
 HORIZONTAL CONCRETE HOLLOW PLANK EYEBROW COMPONENT THE
 CITY MAY REQUIRE A RESIDENT INSPECTOR ON THIS SITE. FOR
 THE SHORING OF THE HOLLOW PLANK EYEBROW AS WELL. PLEASE
 CONTACT KEN CONRAD MANAGER OF THE RESIDENT INSPECTOR
 PROGRAM AT 561-805-6715.
  
 NOTE ARCHITECTURAL AND STRUCTURAL SHEETS STAMPED FOR
 CODE COMPLIANCE.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  
  
2015-05-07 14:23:58C11

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-03-17 Cont ID  
Sent By jwitmer Date 2015-03-17 Time 11:53 Rev Time 0.00
Received By jwitmer Date 2015-03-17 Time 08:33 Sent To  
Notes
2015-03-17 11:43:43BUILDING PLAN REVIEW
 W. P. B. REVISION: 15030360
 W. P. B. PERMIT: 13110271
 ADD: 1750 OKEECHOBEE RD.
 CONT: THORTON & THORTON
 TEL: (321)229-3406
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE
  
 1ST REVIEW
 DATE: TUES. MARCH 17/ 2015
 ACTION: DENIED
  
 1) II-A1-0 PROJECT DATA LIST THIS BUILDING AS A TYPE
 IA-UNPROTECTED- SPRINKLERED. PLEASE NOTE FOR A TYPE IA
 BUILDING THERE ARE PROTECTED MEMBERS SEE FBC-B TABLE
 601 FOR STRUCTURAL MEMBERS THAT REQUIRE FIRE RESISTANCE
 RATING.
  
 2A) SHEET II-A5-0 DETAIL # 1 EAST ELEVATION SHOWS NEW
 ENTRY DOORS AND SIDE LITES, PLEASE PROVIDE PRODUCT
 APPROVALS FOR THIS OPENING.
 SHOP DRAWING STAMP OF APPROVAL
 106.3* PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC...
  
  
 2B) SHEET II-A2-1 DEMO SHEET INDICATES ON THE NORTH
 ELEVATION A DOUBLE DOORWAY BEING CLOSED, PLEASE PROVIDE
 DETAILS. SHEET II-A2-0 NORTH ELEVATION SHOWS A NEW
 3'-0" EXIT DOORWAY THIS DOOR WILL REQUIRE PRODUCT
 APPROVAL ALSO AS WELL AS A SECTION THROUGH THE NEW
 DOORWAY FOR THE NEW COLUMNS AND LINTEL THAT WILL BE
 REQUIRED .
  
 SHOP DRAWING STAMP OF APPROVAL
 106.3* PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE
 REGULATED BY DCA RULE 9N-3 SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC...
  
 3) SHEET II-A4-0 AND DETAI # 3& 4 BOTH SHOW A NEW
 HOLLOW PANK EYEBROW SYSTEM. SHEET I-S2.0 DETAIL # 1 & 3
 SHOWS THE NEW COLUMN DETAILS AND THE TIE INTO THE
 CONCRETE HOLLOW PLANK FLOOR SYSTEM. THE PLANS STATE THE
 TIE IN TO BE DESIGNED BY THE HOLLOW PLANK MANUFATURER.
 THE CONCRETE HOLLOW PLANK
 MANUFACTURER WILL NEED TO PROVIDE THE ENGINEERED DESIGN
 CRITERIA THAT THIS UNIT IS BEING DESIGNED FOR THIS
 APPLICATIION AND WIND SPEED.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS
 SHALL BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL.
  
 4) SHEET II-A4.0 & II-A5.0 BOTH SHOW THE ADDITION OF A
 ROOFED OVER PATIO. SHEET II-S2.0 ALSO SHOWS THE USE OF,
 WOOD BEARING BEAMS, WOOD TRUSSES, WOOD SHEATHING, WOOD
 COLUMNS AND WOOD LEDGERS TO CREATE THE NEW CANOPY.
 PLEASE REVIEW 2010 FBC-B 603.1 COMBUSTIBLE MATERIAL IN
 TYPE I
 AND II CONSTRUCTION: 1. FIRE-RETARDANT-TREATED WOOD
 SHALL BE PERMITTED IN:
  
 1.1. NONBEARING PARTITIONS WHERE THE REQUIRED
 FIRE-RESISTANCE RATING IS 2 HOURS OR LESS.
  
 1.2. NONBEARING EXTERIOR WALLS WHERE NO FIRE RATING IS
 REQUIRED.
  
 1.3. ROOF CONSTRUCTION, INCLUDING GIRDERS, TRUSSES,
 FRAMING AND DECKING.
  
 EXCEPTION: IN BUILDINGS OF TYPE IA CONSTRUCTION
 EXCEEDING TWO STORIES ABOVE GRADE PLANE,
 FIRE-RETARDANT-TREATED WOOD IS NOT PERMITTED IN ROOF
 CONSTRUCTION WHEN THE VERTICAL DISTANCE FROM THE UPPER
 FLOOR TO THE ROOF IS LESS THAN 20 FEET.
  
 5) THE ROOFING MATIALS FOR BOTH THE HORIZONTAL CONCRETE
 HOLLOW CORE EYEBROW AND THE STANDING SEAM METAL ROOFING
 WILL ALSO REQUIRE PRODUCT APPROVALS.
  
 107.2.1.2 FOR ROOF ASSEMBLIES REQUIRED BY THE CODE, THE
 CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE AND
 DELINEATE THE TYPE OF ROOFING SYSTEM, MATERIALS,
 FASTENING REQUIREMENTS, FLASHING REQUIREMENTS AND WIND
 RESISTANCE RATING THAT ARE REQUIRED TO BE INSTALLED.
 PRODUCT EVALUATION AND INSTALLATION SHALL INDICATE
 COMPLIANCE WITH THE WIND CRITERIA REQUIRED FOR THE
 SPECIFIC SITE OR A STATEMENT BY AN ARCHITECT OR
 ENGINEER FOR THE SPECIFIC SITE MUST BE SUBMITTED WITH
 THE CONSTRUCTION DOCUMENTS.
  
 6) SHEET II-A4-0 DETAIL # 3 SHOWS A NEW EXTERIOR WALL
 BEHEATH THE CONCRETE HOLLOW PLANKS EYEBROW. SHEET
 II-A5-0 DETAILS SHOW ANOTHER SECTION OF THIS SAME WALL.
 NOTE THERE ARE NO SECTIONS THROUGH THE ARCHITECTURAL
 NOR STRUCTURAL SHEETS GIVING ANY STRUCTURAL
 INFORMATION. ARE THE METAL STUDS, STRUCTURAL OR
 ARCHITECURAL, GAUGE, ANCHORING TOP AND BOTTOM PLATES,
 ALLOWABLE COMBUSTIBLES TYPE I CONSTRUCTION. FASTENERS,
 TYPE, SIZE AND FREQUENCY FOR THE SUBSHEATHING AND
 FINISH.
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 7) SHEET II-A5-0 DETAIL # 2 INDICATES A HANDRAIL ALONG
 THE NEW RAMP BUT THE HANDRAIL AS DRAWN CONTINUES DOWN
 THE SAME SLOPE AS THE RAMP FOR AN ADDITIONAL 8'-0". NO
 MENTION OF A HANDRAIL ON THE WALL SIDE OF THE RAMP.
 PLEASE REVIEW FBC-B 1010.8 .
  
 8) SHEET II-S2.0 SHOWS A WIND LOAD SCHEDULE FOR ROOFING
 ZONES 1,2 & 3. THE SCHEDULE DOES NOT INDICATE IF THIS
 IS FOR A FLAT ROOF OR IF IT IS FOR THE SLOPED ROOF 2/12
 PITCH. IF THIS FOR A FLAT ROOF THE PRESSURES SHOULD BE
 TAKEN AT 10 SQ. FT. THE PRESSURES SHOULD BE HIGHER THAN
 SHOWN. THERE SHOULD ALSO BE A SCHEDULE FOR A 2/12
 SLOPED ROOF FOR THE METAL ROOFING. FBC-B 1609.1.2.3.1.
  
 9) SHEET II-S1.0 DETAIL 5 SHOWS A DISCREPANCY IN WHERE
 THE WELD LOCATION IS LOCATED. THE PLANS DOES NOT SHOW
 THE WELD LOCATION FROM THE BASE PLATE TO COLUMN.
 107.2.1.3 DISCRPANCY, ADDITIONAL INFORMATION IS
 REQUIRED.
  
 10) BECAUSE OF THE WELDING ON THIS PROJECT AND THE
 HORIZONTAL CONCRETE HOLLOW PLANK EYEBROW COMPONENT THE
 CITY MAY REQUIRE A RESIDENT INSPECTOR ON THIS SITE. FOR
 THE SHORING OF THE HOLLOW PLANK EYEBROW AS WELL. PLEASE
 CONTACT KEN CONRAD MANAGER OF THE RESIDENT INSPECTOR
 PROGRAM AT 561-805-6715.
  
 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2015-06-29 Cont ID  
Sent By dhayes Date 2015-06-29 Time 14:50 Rev Time 0.00
Received By dhayes Date 2015-06-29 Time 14:50 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2015-06-15 Cont ID  
Sent By dhayes Date 2015-06-15 Time 11:16 Rev Time 0.00
Received By dhayes Date 2015-06-15 Time 07:42 Sent To  
Notes
2015-06-15 10:19:066/15/2015
 PROJECT: FERGUSON SHOWROOM
 PERMIT#: 13110271
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 3RD ELECTRICAL PLAN REVIEW REVISION# 15030360
 ACTION: DENIED
  
 1) FBC, WPB AMENDMENTS 107.2.1
 THE REVISED PLANS ARE NOT ALL SIGNED OR SEALED. SHEET
 II-E-4-0 IS NOT SIGNED OR SEALED. PROVIDE A NEW SIGNED
 SEALED SHEET FOR REPLACEMENT. ALL INFORMATION,
 DRAWINGS, SPECIFICATIONS AND ACCOMPANYING DATA SHALL
 BEAR THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE
 FOR THE DESIGN.
 A) 471.025 668.001-668.006.
 ALL FINAL DRAWINGS, SPECIFICATIONS, PLANS, REPORTS, OR
 DOCUMENTS PREPARED OR ISSUED BY THE LICENSEE AND BEING
 FILED FOR PUBLIC RECORD AND ALL FINAL DOCUMENTS
 PROVIDED TO THE OWNER OR THE OWNER?S REPRESENTATIVE
 SHALL BE SIGNED BY THE LICENSEE, DATED, AND SEALED WITH
 SAID SEAL.
  
 2) 2011 EDITION OF THE NEC 220.43(B)EX: IF THE TRACK
 LIGHTING IS SUPPLIED THROUGH A DEVICE THAT LIMITS THE
 CURRENT TO THE TRACK, THE LOAD SHALL BE PERMITTED TO BE
 CALCULATED BASED ON THE RATING OF THE DEVICE USED TO
 LIMIT THE CURRENT. THE STATE OF FLORIDA AND THE CITY OF
 WEST PALM BEACH CURRENTLY RECOGNIZE ONLY THE 2008
 EDITION OF THE NEC. THERE IS NO SUCH EXCEPTION IN THE
 THE 2008 NEC. THE ENGINEER HAS FORMALLY REQUESTED VIA
 LETTER ATTACHED TO USE THE EXCEPTION IN THE 2011 NEC TO
 ALLOW THE USE OF A CURRENT LIMITING DEVICE FOR ALL
 TRACK LIGHTING ON THIS PROJECT. WE HAVE AGREED TO
 APPROVE THE USE OF THIS DEVICE UNDER THE 2011 NEC
 220.43(B) EXCEPTION IN THIS INSTANCE.
  
 3) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR ALL LOW VOLTAGE SPECIALTY PERMITS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-05-07 Cont ID  
Sent By dhayes Date 2015-05-07 Time 14:31 Rev Time 0.00
Received By dhayes Date 2015-05-07 Time 14:24 Sent To  
Notes
2015-05-07 14:33:345/7/2015
 PROJECT: FERGUSON SHOWROOM
 PERMIT#: 13110271
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW REVISION# 15030360
 ACTION: DENIED
  
 REVISE YOUR PLANS IN RESPONSE TO THE FOLLOWING REVIEW
 COMMENTS:
  
 1) FBC, WPB AMENDMENTS 107.2.1
 THE REVISED PLANS ARE NOT SIGNED OR SEALED. ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
 A) 471.025 668.001-668.006.
 ALL FINAL DRAWINGS, SPECIFICATIONS, PLANS, REPORTS, OR
 DOCUMENTS PREPARED OR ISSUED BY THE LICENSEE AND BEING
 FILED FOR PUBLIC RECORD AND ALL FINAL DOCUMENTS
 PROVIDED TO THE OWNER OR THE OWNER?S REPRESENTATIVE
 SHALL BE SIGNED BY THE LICENSEE, DATED, AND SEALED WITH
 SAID SEAL.
  
 2) NEC 220.43(B)
 REVISE THE BRANCH CIRCUIT LOAD FOR THE TRACK LIGHTING
 THROUGHOUT. A SINGLE 20AMP BRANCH CIRCUIT CAN CARRY A
 MAXIMUM OF 25 LINIAL FT. THERE ARE SECTIONS OF TRACK
 CONNECTED TO A SINGLE 120V 20AMP BRANCH CIRCUIT IN
 EXCESS OF 80 LINIAL FT. SEE NEC 220.43(B)
 THE EXCEPTION REFERRED TO IN THE ENGINEER'S RESPOSE TO
 THE PREVIOUS COMMENTS IS BASED ON THE 2011 EDITION OF
 THE NATIONAL ELECTRICAL CODE. THE STATE OF FLORIDA AND
 THE CITY OF WEST PALM BEACH CURRENTLY RECOGNIZE ONLY
 THE 2008 EDITION. THERE IS NO SUCH EXCEPTION IN THE THE
 2008 EDITION OF THE NEC. PLEASE REVISE THE PLAN
 ACCORDINGLY.
  
 3)NEC 700.12
 REVISE THE BRANCH CIRCUITRY FEEDING EMERGENCY AND EXIT
 LIGHTING THROUGHOUT. THE BRANCH CIRCUIT FEEDING
 EMERGENCY AND EXIT LIGHTING SHALL BE THE SAME BRANCH
 CIRCUIT AS THAT SERVING THE NORMAL LIGHTING IN THE AREA
 AND CONNECTED AHEAD OF ANY LOCAL SWITCHES.
  
 SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR LOW VOLTAGE SPECIALTY PERMITS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-04-29 Cont ID  
Sent By dhayes Date 2015-04-29 Time 12:46 Rev Time 0.00
Received By dhayes Date 2015-04-29 Time 07:35 Sent To  
Notes
2015-04-29 12:46:394/29/2015
 PROJECT: FERGUSON SHOWROOM
 PERMIT#: 13110271
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW OF REVISION TRACKING NUMBER
 15030360
 ACTION: DENIED
  
 E1-2
 PROVIDE CIRCUIT NUMBERS FOR JUNCTION BOXES NOTED FOR
 "HEATERS"
 PROVIDE CIRCUITS AND CONTROLS FOR FANS INDICATED BY THE
 "F" SYMBOL AND NOTE "5" TO BE INSTALLED IN SEVERAL
 LOCATIONS ALL THROUGHOUT AREA TO BE RENNOVATED.
  
 E-1-3
 FBC-ENERGY
 FBC-E 505.2 LIGHTING CONTROLS (MANDATORY).
 1) PROVIDE A MEANS OF LIGHTING CONTROL IN COMPLIANCE
 WITH THE FBC-ENERGY 505.2. LIGHTING SYSTEMS SHALL BE
 PROVIDED WITH CONTROLS AS REQUIRED IN SECTIONS 505.2.1,
 505.2.2, 505.2.3 AND 505.2.4.
 FBC-E 502.3.8 RECESSED LIGHTING.
 2) ALL RECESSED LUMINAIRES SHALL BE IC-RATED. ALL
 RECESSED LUMINAIRES SHALL BE SEALED WITH A GASKET OR
 CAULK BETWEEN THE HOUSING AND INTERIOR WALL OR CEILING
 COVERING.
  
 E2-0
 NEC 700.12
 1) THE FIRE PLANS EXAMINER HAS ADDED EMERGENCY AND EXIT
 LIGHTING TO THE LIGHTING PLAN. SEE NEC 700.12 THE
 BRANCH CIRCUIT FEEDING EMERGENCY AND EXIT LIGHTING
 SHALL BE THE SAME BRANCH CIRCUIT AS THAT SERVING THE
 NORMAL LIGHTING IN THE AREA AND CONNECTED AHEAD OF ANY
 LOCAL SWITCHES.
 NEC 220.43(B)
 2) REVISE THE BRANCH CIRCUIT LOAD FOR THE TRACK
 LIGHTING THROUGHOUT. A SINGLE 20AMP BRANCH CIRCUIT CAN
 CARRY A MAXIMUM OF 25 LINIAL FT. THERE ARE SECTIONS OF
 TRACK CONNECTED TO A SINGLE 120V 20AMP BRANCH CIRCUIT
 IN EXCESS OF 80 LINIAL FT. SEE NEC 220.43(B)
  
 E2-1
 ELECTRICAL DETAIL 1A
 PROVIDE CIRCUITS AND CONTROLS FOR FANS INDICATED BY THE
 "F" SYMBOLS AND NOTES TO BE INSTALLED IN SEVERAL
 LOCATIONS ALL THROUGHOUT AREA TO BE RENNOVATED.
  
 E4-0
 WPB AMENDMENTS TO FBC 107.3.5.1.2
 1) THE RISER DIGRAM INDICATES THE INSTALLATION OF FIVE
 (5) NEW ELECTRICAL PANELS. PROVIDE A SUMMARY LOAD
 CALCULATION THAT INDICATES THE ADDITION OF THE LOAD OF
 ALL FIVE(5) OF THE NEW PANELS.
 2) PROVIDE A PANEL DIRECTORY AND LOAD CALCULATION FOR
 PANEL MDP-B. NEC 408.4
 3) PROVIDE THE SERVICE ENTRANCE AND GROUNDING ELECTRODE
 SIZE AND TYPES.
 4) PROVIDE THE SIZE OF THE FEEDERS TO MDP -A AND MDP-B
 5) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR
 THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.16.
  
 SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR LOW VOLTAGE SPECIALTY PERMITS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-06-30 Cont ID  
Sent By pleduc Date 2015-06-30 Time   Rev Time 0.00
Received By pleduc Date 2015-06-30 Time 13:57 Sent To PC
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-03-12 Cont ID  
Sent By pleduc Date 2015-03-12 Time   Rev Time 0.00
Received By pleduc Date 2015-03-12 Time 12:22 Sent To  
Notes
2015-03-12 13:14:01THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 SHEET A2-0 & E2-0 - NEED TO ADD 5 EXIT SIGNS IN THE
 PATH OF EGRESS AS INDICATED ON THE LIFE SAFETY PLAN.
  
 SHEET A2-0 - NEED TO INSTALL FIRE EXTINGUISHERS EVERY
 75' WALKING DISTANCE.
  
 SHEET 5-0 - NEED TO ENSURE TO INSTALL FIRE SPRINKLERS
 UNDER THE NEWLY CREATED ROOF/PORCH ARE AS IT IS AN
 EXTENSION OF AND ATTACHED TO THE FULLY SPRINKLERED
 BUILDING.
  
 PER FLORIDA STATUTUE 69A-60.0081, NOTICE SIGNAGE IS
 REQUIRED FOR STRUCTURES WITH LIGHT-FRAME TRUSS-TYPE
 CONSTRUCTION. ANY COMMERCIAL, INDUSTRIAL, OR ANY
 MULTIUNIT RESIDENTIAL STRUCTURE OF THREE UNITS OR MORE
 WHICH USES HORIZONTAL OR VERTICAL LIGHT-FRAME
 TRUSS-TYPE CONSTRUCTION IN ANY PORTION SHALL BE MARKED
 WITH A MALTESE CROSS SIGN MEASURING 8 INCHES
 HORIZONTALLY AND 8 INCHES VERTICALLY, OF A BRIGHT RED
 REFLECTIVE COLOR. THE APPROVED SYMBOL SHALL BE PLACED
 WITHIN 24 INCHES TO THE LEFT OF THE MAIN ENTRY DOOR.
 1. STRUCTURES WITH LIGHT-FRAME TRUSS ROOFS SHALL BE
 MARKED WITH THE LETTER "R".
 2. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR SYSTEMS
 SHALL BE MARKED WITH THE LETTER "F".
 3. STRUCTURES WITH LIGHT-FRAME TRUSS FLOOR AND ROOF
 SYSTEMS SHALL BE MARKED WITH THE LETTERS "R/F".
  
  
  

Review Stop G GAS REVIEW
Rev No 3 Status P Date 2015-06-30 Cont ID  
Sent By tklarge Date 2015-06-30 Time 07:01 Rev Time 0.00
Received By tklarge Date 2015-06-30 Time 06:12 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2015-06-14 Cont ID  
Sent By tklarge Date 2015-06-14 Time 05:21 Rev Time 0.00
Received By tklarge Date 2015-06-13 Time 09:32 Sent To  
Notes
2015-06-13 10:07:381) THE GAS PLAN IS NOT SIGNED AND SEALED AS REQUIRED BY
 F.S. 471 & F.A.C RULE 61G15-23.002. SEE SHT.P1-2.
 2) SHT.II-P1-2 - SIZE EACH SECTION OF PIPE ON THE
 RISER.2010 FBC-FUEL GAS SEC.402.4.1 & 402.4.2.
 3) THE MANUFACURER'S SPECIFICATION SHEETS THAT WERE
 SUBMITTED FOR THE GAS EQUIPMENT ARE INADEQUATE. THE
 SPECIFICATIONS DO NOT SHOW THAT THE EQUIPMENT IS LISTED
 AND LABELED PER THE 2010 FBC-FUEL GAS, SEC.301.3,
 301.5. REFER TO THE DEFINITION OF "LISTED" AND "LABELED
 " IN FBC-FUEL GAS, SEC.202.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2015-04-16 Cont ID  
Sent By tklarge Date 2015-04-16 Time 10:05 Rev Time 0.00
Received By tklarge Date 2015-04-16 Time 10:03 Sent To  
Notes
2015-04-16 10:10:221) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE GAS
 EQUIPMENT IN ACCORDANCE WITH THE 2010 FUEL GAS CODE
 SEC. 304. SUBMIT VENTING DETAILS PER THE 2010 FUEL GAS
 CODE SECS.502 & 503.
 2) SUBMIT MANUF. SPEC SHEETS FOR ALL GAS APPLIANCES.
 APPLIANCES SHALL BE LISTED AND LABELED PER THE 2010
 FUEL GAS CODE SEC. 301.3.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-06-27 Cont ID  
Sent By jwitmer Date 2015-06-27 Time 10:52 Rev Time 0.00
Received By jwitmer Date 2015-05-06 Time 14:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-04-29 Cont ID  
Sent By dhayes Date 2015-04-29 Time 12:47 Rev Time 0.00
Received By dhayes Date 2015-03-10 Time 17:01 Sent To  
Notes
2015-03-10 17:02:03REVISION SENT TO C11 BIN FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2015-07-01 Cont ID  
Sent By mmanhong Date 2015-07-01 Time 15:42 Rev Time 0.00
Received By mmanhong Date 2015-07-01 Time 15:42 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2015-06-23 Cont ID  
Sent By jwitmer Date 2015-06-23 Time 12:25 Rev Time 0.00
Received By jwitmer Date 2015-06-23 Time 12:25 Sent To  
Notes
2015-06-23 12:26:00BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-03-17 Cont ID  
Sent By   Date 2015-03-17 Time   Rev Time 0.00
Received By   Date 2015-03-17 Time   Sent To  
Notes
2015-06-23 12:26:55BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop L LANDSCAPING
Rev No 4 Status N Date 2015-06-26 Cont ID  
Sent By rcaranci Date 2015-06-26 Time 08:01 Rev Time 0.00
Received By rcaranci Date 2015-06-26 Time 08:01 Sent To  
Notes
2015-06-26 08:02:18SEPARATE LANDSCAPE PERMIT REQUIRED

Review Stop L LANDSCAPING
Rev No 3 Status F Date 2015-06-19 Cont ID  
Sent By rcaranci Date 2015-06-19 Time 11:32 Rev Time 0.00
Received By rcaranci Date 2015-06-19 Time 11:32 Sent To  
Notes
2015-06-19 11:34:28REVISION INCLUDES EXTERIOR CHANGES REQUIRING SEPARATE
 APPROVALS AND PERMITS. SEPARATE LANDSCAPE PERMIT IS
 REQUIRED.

Review Stop L LANDSCAPING
Rev No 2 Status F Date 2015-04-13 Cont ID  
Sent By rcaranci Date 2015-04-13 Time 16:56 Rev Time 0.00
Received By rcaranci Date 2015-04-13 Time 16:56 Sent To  
Notes
2015-04-13 17:00:31SITE PLAN SUBMITTED DOES NOT MATCH THE LANDSCAPE PLAN
 SUBMITTED WITH THE REVISION. THE OUTSIDE IMPROVEMENTS
 AND LANDSCAPING APPEAR TO ELIMINATE PARKING SPACES.
 PLEASE SUBMIT SITE PLAN SHOWING THE RECONFIGURATION OF
 THE SPACES.

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2015-04-08 Cont ID  
Sent By rcarnci Date 2015-04-08 Time 11:39 Rev Time 0.00
Received By rcaranci Date 2015-04-08 Time 09:18 Sent To  
Notes
2015-04-08 11:44:27LANDSCAPE PLAN INCLUDED IS ONLY A PARTIAL PLAN. FURTHER
 ZONING REVIEW NEEDED IF ADDITION OF STRUCTURE TRIGGERS
 UPDATING OF SITE LANDSCAPE IMPROVEMENTS. NEED SURVEY
 AND SITE PLAN SUBMITTED.
 RAY CARANCI, LANDSCAPE PLANNER
 561-822-1462

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2015-04-02 Cont ID  
Sent By hmoser Date 2015-04-02 Time 08:42 Rev Time 0.00
Received By hmoser Date 2015-04-01 Time 14:53 Sent To  
Notes
2015-04-02 08:40:32PASS PROVISO
 1) REFER TO SECTION 604.8 LINING INSTALLATION
 2REFER TO SECTION M 1503.1 BACH DRAFT DAMPER
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-04-16 Cont ID  
Sent By tklarge Date 2015-04-16 Time 10:01 Rev Time 0.00
Received By tklarge Date 2015-04-16 Time 08:52 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2015-06-26 Cont ID  
Sent By rcaranci Date 2015-06-26 Time 08:02 Rev Time 0.00
Received By rcaranci Date 2015-06-26 Time 08:02 Sent To  
Notes
2015-06-26 08:03:56PROVISO :SEPARATE PERMIT REQUIRED FOR PARKING LOT
 CHANGES IN PAVEMENT AND STRIPING. SEPARATE PERMIT FOR
 LANDSCAPING.
2015-06-22 16:49:59EXTERIOR CHANGES TO PARKING LOT AND LANDSCAPING.
 DISPLAY PORCH WITH ROOF BEING ADDED.

Review Stop Z ZONING
Rev No 1 Status P Date 2015-04-06 Cont ID  
Sent By ajones Date 2015-04-06 Time 14:41 Rev Time 0.00
Received By ajones Date 2015-04-06 Time 14:41 Sent To  
Notes
***NONE***