Review Stop G GAS REVIEW
Rev No 2 Status P Date 2015-03-13 Cont ID  
Sent By tklarge Date 2015-03-13 Time 13:09 Rev Time 0.00
Received By tklarge Date 2015-03-13 Time 13:09 Sent To  
Notes
2015-03-13 13:11:05REVISION REQUIRED TO REROUTE PE PIPE FROM UNDER SLAB AT
 ROOFED PATIO AREA.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2015-03-11 Cont ID  
Sent By tklarge Date 2015-03-11 Time 06:36 Rev Time 0.00
Received By tklarge Date 2015-03-11 Time 04:04 Sent To  
Notes
2015-03-11 06:09:071) SHT. P-1 NOTES A TOTAL BTU LOAD OF 1,039,000 BUT MY
 CALCULATIONS COME TO 1,264,00 INCLUDING THE EXISTING
 GENERATOR. TABLE 402.4 (20) SHOWS THE MAXIMUM BTU LOAD
 ON 3/4" PE PIPE AT 2 PSI AT 200 FT. IS 736,000 ( THERE
 IS NO ROW FOR 185 FT.). THE SIZE OF THE PE LINE FROM
 THE POINT OF CONNECTION AT THE METER UP TO THE TEE FOR
 THE GAS RANGE SHALL BE 1" ( THE 60 FT. SECTION)
 2) THE 1/2" GALVANIZED DROP TO THE RANGE SHALL BE 3/4"
 PER TABLE 402.4 (2) OF 2010 FUEL GAS CODE. THE MAXIMUM
 BTU LOAD ON 1/2" SCH. 40 PIPE @ 60 FT. IS 65,000 BTU'S.
 3) SIZE THE LINE FROM THE POOL HEATER REGULATOR TO THE
 NEW POOL HEATER. IF IT IS SCH. 40 METAL IT SHALL BE 1"
 PER TABLE 402.4 (2) OF THE FUEL GAS CODE.
 4) SHOW THE LINE SIZES AND PIPE MATERIAL FROM THE
 MEDIUM PRESSURE REGULATORS TO THE APPLIANCES WHERE
 NEEDED.
 5) NOTE # 12 ON SHT. P-1 NOTES THAT PE PIPE WILL BE
 INSTALLED OUTSIDE UNDERGROUND ONLY BUT THE PLAN CLEARLY
 SHOWS THE PIPE GOING UNDER THE SLAB TO THE NEW GAS
 GRILL. CLARIFY.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-03-13 Cont ID  
Sent By tklarge Date 2015-03-13 Time 13:09 Rev Time 0.00
Received By tklarge Date 2015-03-13 Time 13:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-03-11 Cont ID  
Sent By tklarge Date 2015-03-11 Time 06:36 Rev Time  
Received By tklarge Date 2015-03-09 Time   Sent To  
Notes
2015-03-10 06:22:30SENT TO PLUMBING BOX<$5K.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved