Plan Review Details - Permit 15030301
Plan Review Stops For Permit 15030301
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2015-08-21 Cont ID  
Sent By jwitmer Date 2015-08-21 Time 07:30 Rev Time 0.00
Received By jwitmer Date 2015-08-21 Time 07:00 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-07-22 Cont ID  
Sent By jwitmer Date 2015-07-22 Time 08:52 Rev Time 0.00
Received By jwitmer Date 2015-07-22 Time 07:31 Sent To  
Notes
2015-07-22 08:51:56BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15030301
 ADD: 3805 S OLIVE AVE.
 CONT: DELTA MG
 TEL: ( 561)239-4947
 E-MAIL:[email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: WED. JULY 22/ 2015
 ACTION: BUILDING PROVISO
  
 1) THE SUBMITTED REPORT FOR WHISPER MAT FLOOR
 UNDERLAYMENT WITH A IIC RATING OF 49 TESTED TO ASTM E
 492 TO MEET THE REQUIRED IIC RATING OF 50 A DOUBLE
 LAYER OF 3 1/2 INCHES OF INSULATION TO BE INSTALLED
 BETWEEN JOIST. THIS WAS DISCUSSED WITH ASSISTANT B. O.
 DOUG HARVEY AND OK'ED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-04-27 Cont ID  
Sent By jwitmer Date 2015-04-27 Time 15:52 Rev Time 0.00
Received By jwitmer Date 2015-04-27 Time 15:52 Sent To  
Notes
2015-04-27 15:52:26BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15030301
 ADD: 3805 S OLIVE AVE.
 CONT: DELTA MG
 TEL: ( 561)239-4947
 E-MAIL:[email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. APRIL 27/ 2015
 ACTION: DENIED
  
 1-3) COMPLIED>
  
 4) 2ND REQUEST. SEMI- COMPLIED. THE (3) REPORTS
 SUBMITTED FOR WHISPER MAT:
  
 4A) COMPLIED. SURFACE BURNING CHARACTERISTICS OF
 BURNING MATERIALS ASTM E 84 : FLAME SPREAD 0 & SMOKE
 DEVELOPED INDEX 0.
  
 4B) SEMI-COMPLIED. THE SOUND TRANSMISSION LOSS TEST,
 ASTM E-90, WITH A STC= 57 DB. THE SYSTEM THAT WAS
 TESTED PAGE 2 OF 4 LIST THE COMPONENTS THAT MAKE UP THE
 TESTED ASSEMBLY, 1/4 IN. GLAZED TILE, 1/4 IN. POLYMER
 MODIFIED THIN SET, 2.5 MM (0.1 IN.), 5/8 IN. B. C.
 PLYWOOD, 3/4 IN. T & G OSB SUB-FLOOR, 3 1/2 IN. X 18
 IN. X 12 FT. OPEN WEB TRUSSES, RESILIENT FURRING
 CHANNEL, 3 1/2 IN. OF FIBERGLASS INSULATION BATTS & 1
 LAYER OF 5/8 IN. TYPE C WALLBOARD.
 SITE CONDITIONS WRITTEN ON THE FACE OF THE TEST REPORT
 2X12 TRUSSES, (FLOOR JOIST/ I LOIST?) 5/8 PLYWOOD PLUS
 1/2 IN. DUROCK. THE TESTED ASSMBLY HAS A 5/8 IN. B. C.
 FINISH PLYWOOD + 3/4 IN. OSB OPEN WEB JOIST, RESILIENT
 CHANNEL FURRING. PLEASE PROVIDE RANIONAL ANALYSIS AND
 PREFORM A ENGINEERED JUDGEMENT AS WHAT IT WILL TAKE TO
 MEET THE EQUIVALENCY OF THE TESTING. WE UNDERSTAND THAT
 YOU WILL NOT FIND A TESTED REPORT WITH THE SAME
 COMONENTS AS THE TEST SPECIMEN FOR THE WOOD PRODUCTS
 AND WITH DURAROCK AS A COMPONENT, PLEASE BE SPECIFIC AS
 TO HOW EACH OF THE MEMBERS ARE TO BE EITHER FASTENED
 AND OR ADHERRED TO EACH OTHER.
  
 4C) THE SUBMITTED REPORT FOR WHISPER MAT FLOOR
 UNDERLAYMENT WITH A IIC RATING OF 49 TESTED TO ASTM E
 492 DOES NOT MEET THE REQUIRED IIC RATING OF 50.
 AS STATED ABOVE THE TESTED ASSEMBLY IN THIS CASE DID
 NOT MEET THE REQUIREMENTS OF THE CODE WITH THE SAME
 CONFIGURATION. PLEASE PROVIDE RANIONAL ANALYSIS AND
 PREFORM A ENGINEERED JUDGEMENT AS WHAT IT WILL TAKE TO
 MEET THE REQUIREMENT OF ASTM E-492 WITH A IIC OF 50 DB
 MINIMUM. WE UNDERSTAND THAT YOU WILL NOT FIND A TESTED
 REPORT WITH THE SAME COMONENTS AS THE TEST SPECIMEN FOR
 THE WOOD PRODUCTS AND WITH DURAROCK AS A COMPONENT,
 PLEASE BE SPECIFIC AS TO HOW EACH OF THE MEMBERS ARE TO
 BE EITHER FASTENED AND OR ADHERRED TO EACH OTHER.
 -------------------------------------------------------
 -------------------------------------------------------
 -------------------------------------------------------
 -------------------------------
 4) 1ST REVIEW COMMENTS. 2010 1207.3 STRUCTURE BORN
 SOUND REPORT FOR PROFLEX . PLEASE PROVIDE THE SLAB
 THICKNESS. THIS REPORT DECLARES A IIC RATING OF 68DB
 WHEN APPLIED TO A 8 INCH SLAB AND A 5/8 IN DROP CEILING
 WITH 3 1/2 INCHES OF FIBERGLASS INSULATION (0.16PSF).
 PLEASE IDENTIFY THE ACTUAL FLOOR/ CEILING ASSEMBLY TO
 SEE IF THIS REPORT IS THE RIGHT CONFIGURATION, NOTE
 DROPED CEILINGS WOULD NEED TO BE THROUGH THE WHOLE UNIT
 WITH A 10 INCH PLENUM. 1207.3 STRUCTURE-BORNE SOUND.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561) 805-6715
 FAX: (561)805-6676
 E-MAIL: [email protected]
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-03-13 Cont ID  
Sent By jwitmer Date 2015-03-13 Time 07:45 Rev Time 0.00
Received By jwitmer Date 2015-03-13 Time 06:41 Sent To  
Notes
2015-03-13 07:50:23BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15030301
 ADD: 3805 S OLIVE AVE.
 CONT: DELTA MG
 TEL: ( 561)239-4947
 E-MAIL:[email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. APRIL 27/ 2015
 ACTION: DENIED
  
 1-3) COMPLIED>
  
 4) 2ND REQUEST. SEMI- COMPLIED. THE (3) REPORTS
 SUBMITTED FOR WHISPER MAT:
  
 4A) COMPLIED. SURFACE BURNING CHARACTERISTICS OF
 BURNING MATERIALS ASTM E 84 : FLAME SPREAD 0 & SMOKE
 DEVELOPED INDEX 0.
  
 4B) SEMI-COMPLIED. THE SOUND TRANSMISSION LOSS TEST,
 ASTM E-90, WITH A STC= 57 DB. THE SYSTEM THAT WAS
 TESTED PAGE 2 OF 4 LIST THE COMPONENTS THAT MAKE UP THE
 TESTED ASSEMBLY, 1/4 IN. GLAZED TILE, 1/4 IN. POLYMER
 MODIFIED THIN SET, 2.5 MM (0.1 IN.), 5/8 IN. B. C.
 PLYWOOD, 3/4 IN. T & G OSB SUB-FLOOR, 3 1/2 IN. X 18
 IN. X 12 FT. OPEN WEB TRUSSES, RESILIENT FURRING
 CHANNEL, 3 1/2 IN. OF FIBERGLASS INSULATION BATTS & 1
 LAYER OF 5/8 IN. TYPE C WALLBOARD.
 SITE CONDITIONS WRITTEN ON THE FACE OF THE TEST REPORT
 2X12 TRUSSES, (FLOOR JOIST/ I LOIST?) 5/8 PLYWOOD PLUS
 1/2 IN. DUROCK. THE TESTED ASSMBLY HAS A 5/8 IN. B. C.
 FINISH PLYWOOD + 3/4 IN. OSB OPEN WEB JOIST, RESILIENT
 CHANNEL FURRING. PLEASE PROVIDE RANIONAL ANALYSIS AND
 PREFORM A ENGINEERED JUDGEMENT AS WHAT IT WILL TAKE TO
 MEET THE EQUIVALENCY OF THE TESTING. WE UNDERSTAND THAT
 YOU WILL NOT FIND A TESTED REPORT WITH THE SAME
 COMONENTS AS THE TEST SPECIMEN FOR THE WOOD PRODUCTS
 AND WITH DURAROCK AS A COMPONENT, PLEASE BE SPECIFIC AS
 TO HOW EACH OF THE MEMBERS ARE TO BE EITHER FASTENED
 AND OR ADHERRED TO EACH OTHER.
  
 4C) THE SUBMITTED REPORT FOR WHISPER MAT FLOOR
 UNDERLAYMENT WITH A IIC RATING OF 49 TESTED TO ASTM E
 492 DOES NOT MEET THE REQUIRED IIC RATING OF 50.
 AS STATED ABOVE THE TESTED ASSEMBLY IN THIS CASE DID
 NOT MEET THE REQUIREMENTS OF THE CODE WITH THE SAME
 CONFIGURATION. PLEASE PROVIDE RANIONAL ANALYSIS AND
 PREFORM A ENGINEERED JUDGEMENT AS WHAT IT WILL TAKE TO
 MEET THE REQUIREMENT OF ASTM E-492 WITH A IIC OF 50 DB
 MINIMUM. WE UNDERSTAND THAT YOU WILL NOT FIND A TESTED
 REPORT WITH THE SAME COMONENTS AS THE TEST SPECIMEN FOR
 THE WOOD PRODUCTS AND WITH DURAROCK AS A COMPONENT,
 PLEASE BE SPECIFIC AS TO HOW EACH OF THE MEMBERS ARE TO
 BE EITHER FASTENED AND OR ADHERRED TO EACH OTHER.
 -------------------------------------------------------
 -------------------------------------------------------
 -------------------------------------------------------
 -------------------------------
 4) 1ST REVIEW COMMENTS. 2010 1207.3 STRUCTURE BORN
 SOUND REPORT FOR PROFLEX . PLEASE PROVIDE THE SLAB
 THICKNESS. THIS REPORT DECLARES A IIC RATING OF 68DB
 WHEN APPLIED TO A 8 INCH SLAB AND A 5/8 IN DROP CEILING
 WITH 3 1/2 INCHES OF FIBERGLASS INSULATION (0.16PSF).
 PLEASE IDENTIFY THE ACTUAL FLOOR/ CEILING ASSEMBLY TO
 SEE IF THIS REPORT IS THE RIGHT CONFIGURATION, NOTE
 DROPED CEILINGS WOULD NEED TO BE THROUGH THE WHOLE UNIT
 WITH A 10 INCH PLENUM. 1207.3 STRUCTURE-BORNE SOUND.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561) 805-6715
 FAX: (561)805-6676
 E-MAIL: [email protected]
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-09-17 Cont ID  
Sent By albarran Date 2015-09-17 Time 18:46 Rev Time 0.00
Received By albarran Date 2015-09-17 Time 17:59 Sent To I
Notes
2015-09-17 19:22:50SO AS NOT TO HOLD THE PERMIT FROM BEING ISSUED, THIS
 APPLICATION IS BEING APPROVED WITH THE FOLLOWING
 PROVISOS:
 1. IF THE CORNER AREA BEHIND THE KITCHEN SINK IS 12
 INCHES OR GREATER AS SPECIFIED IN NEC 210.52(C), IT
 SHALL HAVE AN OUTLET.
 2. EACH CONDENSING UNIT SHALL HAVE WITHIN 25' A SERVICE
 OUTLET AS REQUIRED BY NEC 210.63. THIS OUTLET SHALL BE
 SERVED FROM THE RESPECTIVE UNIT'S ELECTRIC SERVICE.
 I CAN SUGGEST GE MODEL # TFN60RGFRCP, 60 AMP 240-VOLT
 NON-FUSE AC DISCONNECT WITH GFCI RECEPTACLE OR
 EQUIVALENT.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-08-20 Cont ID  
Sent By albarran Date 2015-08-20 Time 19:03 Rev Time 0.00
Received By albarran Date 2015-08-20 Time 18:38 Sent To B
Notes
2015-08-20 19:16:33PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
  
 1. ACCORDING TO A LETTER FROM MR. DANILO ALCANTARA,
 EACH SUB WILL SUBMIT THEIR OWN DRAWING AND THEREFORE
 APPLY FOR THEIR OWN PERMIT. THE FOLLOWING REVIEW IS FOR
 THE DRAWING PRESENTLY SUBMITTED, THOUGH IF THIS
 STATEMENT IS TRUE, THE RESULTS OF THIS REVIEW WILL
 DIFFER. PLEASE ADVISE IF THE PREVIOUSLY SUBMITTED
 LETTER ATTESTING TO THIS REMAINS IN EFFECT.
 2. THE WORD "ROMEX" AS USED IN THIS NOTE IS TO IDENTIFY
 A TYPE OF CABLE. ROMEX IS A BRAND NAME AND NOT A TYPE
 OF CABLE, REFER TO CABLE TYPES "NM", "NMC" OR "NMS".
 3. THE TITLE BLOCK INDICATES THAT THIS IS A 4 PLEX
 REMODEL. THE SUBMITTED DRAWING IS INCOMPLETE. IT
 REFLECTS ONLY TWO UNITS.
 4. YOU SHALL SUBMIT A SITE SPECIFIC RISER DIAGRAM
 5. YOU SHALL PROVIDE SITE SPECIFIC LOAD CALCS FOR EACH
 UNIT AND THEN THE FOR THE SINGLE SERVICE FOR THE
 MULTI-UNIT DWELLING.
 6. AS CIRCUIT DIRECTORY AS DESCRIBED IN NEC 408.4 SHALL
 BE SUBMITTED FOR EACH UNIT.
 7. EVERY CEILING LUMINAIRE OUTLET SHALL BE LISTED TO
 SUPPORT A MINIMUM OF 50 LBS. AS INDICATED IN NEC 314.27
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-04-09 Cont ID  
Sent By rlecky Date 2015-04-09 Time 11:59 Rev Time 0.00
Received By rlecky Date 2015-04-09 Time 11:56 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2015-06-08 Cont ID  
Sent By fmittner Date 2015-06-08 Time 12:30 Rev Time 0.00
Received By fmittner Date 2015-06-08 Time 12:30 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2015-03-19 Cont ID  
Sent By fmittner Date 2015-03-19 Time 14:10 Rev Time 0.00
Received By fmittner Date 2015-03-19 Time 14:10 Sent To  
Notes
2015-03-19 14:12:59SINGLE HUNG WINDOWS NOT APPROPRIATE ON MID-CENTURY
 STYLE. FHM SPOKE TO CONTARCTOR AND RECOMMENDED
 CASEMENT. NEED FRAME AND GLAZING COLOR CONFIRMED.
 QUESTIONS CONTACT FRIEDERIKE MITTNER, CITY HISOTRIC
 PRESERVATION PLANNER AT 822-1457.

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2015-09-17 Cont ID  
Sent By albarran Date 2015-09-17 Time 19:23 Rev Time 0.00
Received By albarran Date 2015-09-17 Time 16:00 Sent To  
Notes
2015-09-17 19:25:449/17/15 - PASSED ELECTRICAL REVIEW W/PROVISOS.
 CONTRACTOR NOTIFIED VIA EMAIL. SENT TO SMALL READY BIN
 "D". MA
2015-09-17 16:00:24RESUB ROUTED TO MALBARRAN

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-08-21 Cont ID  
Sent By jwitmer Date 2015-08-21 Time 07:40 Rev Time 0.00
Received By jwitmer Date 2015-08-18 Time 16:03 Sent To  
Notes
2015-08-18 16:03:41RESUB ROUTED TO CCOLE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-07-22 Cont ID  
Sent By jwitmer Date 2015-07-22 Time 08:52 Rev Time 0.00
Received By jwitmer Date 2015-07-20 Time 13:32 Sent To  
Notes
2015-07-20 13:33:38CCOLE DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-08-18 Cont ID  
Sent By lmarchan Date 2015-07-22 Time 16:03 Rev Time 0.00
Received By lmarchan Date 2015-04-24 Time   Sent To  
Notes
2015-04-25 09:29:10B32

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-04-11 Cont ID  
Sent By hmoser Date 2015-04-11 Time 11:03 Rev Time  
Received By hmoser Date 2015-03-09 Time   Sent To  
Notes
2015-03-09 17:12:11SENT TO B-15.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2015-08-19 Cont ID  
Sent By ccole Date 2015-08-19 Time 07:28 Rev Time 0.00
Received By ccole Date 2015-08-19 Time 06:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2015-07-20 Cont ID  
Sent By ccole Date 2015-07-20 Time 14:44 Rev Time 0.00
Received By ccole Date 2015-07-20 Time 14:44 Sent To  
Notes
2015-07-20 14:48:512ND REVIEW: FBC 2010 MECHANICAL
  
 1) SHOW THE BRANCH DUCT SIZES ON THE PLAN.
 2) THE 16X6" TRANSFER GRILL IS UNDERSIZED FOR 287
 CFM'S- SEE SECTION 601.4 FBC-10 MECHANICAL.
 3) PROVIDE TIE DOWN ENGINEERING FOR ANCHORING THE
 CONDENSERS TO THE PADS- SECTION 301.12.
 4) SHOW THE LOCATIONS OF ALL FOUR CONDENSERS ON THE
 PLANS- ONLY ONE OF THE FOUR IS SHOWN.
 5) THE PLAN INDICATES A 3/8" CONDENSATE PIPE, MINIMUM
 3/4" IS REQUIRED- SECTION 307.
  
  
  
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-05-29 Cont ID  
Sent By ccole Date 2015-05-29 Time 12:55 Rev Time 0.00
Received By ccole Date 2015-05-29 Time 12:55 Sent To  
Notes
2015-05-29 13:00:053RD MECHANICAL REVIEW.
  
 1) AS PREVIOUSLY REQUESTED, PLEASE SUBMIT AC PLANS AND
 SPECIFICATIONS, AND A MECHANICAL SUB-PERMIT. THIS IS
 PER THE PLAN NOTES INDICATING NEW AC AND A DROP CEILING
 IN THE HALL FOR DUCTWORK.
  
 CHRISTOPHER COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-04-11 Cont ID  
Sent By hmoser Date 2015-04-11 Time 11:03 Rev Time 0.00
Received By hmoser Date 2015-04-11 Time 10:54 Sent To  
Notes
2015-04-11 11:03:41NOTE SAY REFER TO AIR CONDITIONING
 PLAN. NO AIR CONDITIONING PLAN
 SUBMITTED AT THIS TIME
 REVIEW BY HM.
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-04-04 Cont ID  
Sent By tklarge Date 2015-04-04 Time 07:35 Rev Time 0.00
Received By tklarge Date 2015-04-04 Time 07:09 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-03-19 Cont ID  
Sent By fmittner Date 2015-03-19 Time 14:13 Rev Time 0.00
Received By fmittner Date 2015-03-19 Time 14:13 Sent To  
Notes
2015-03-10 13:59:223/10/15