Plan Review Details - Permit 15030270
Plan Review Stops For Permit 15030270
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-03-12 Cont ID  
Sent By tklarge Date 2015-03-12 Time 11:50 Rev Time 0.00
Received By tklarge Date 2015-03-09 Time   Sent To  
Notes
2015-03-09 17:23:51SENT TO T. K.LARGE.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-03-07 Cont ID  
Sent By tklarge Date 2015-03-07 Time 10:45 Rev Time 0.00
Received By tklarge Date 2015-03-07 Time 10:40 Sent To  
Notes
2015-03-06 16:56:59PLUMBING LESS THAN 5K

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-03-12 Cont ID  
Sent By tklarge Date 2015-03-12 Time 11:50 Rev Time 0.00
Received By tklarge Date 2015-03-10 Time 04:45 Sent To  
Notes
2015-03-12 11:54:59SEPARATE PERMIT REQUIRED FOR LANDSCAPING.

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-03-07 Cont ID  
Sent By tklarge Date 2015-03-07 Time 10:40 Rev Time 0.00
Received By tklarge Date 2015-03-07 Time 10:40 Sent To  
Notes
2015-03-07 10:45:101)SUBMIT A PLAN THAT SHOWS THE LOCATION AND TYPE OF THE
 BACKFLOW PREVENTION DEVICE. THE DEVICE SHALL BE LOCATED
 AT THE METER AND SHALL BE CERTIFIED BY THE CITY OF WPB
 UTILITIES.
 2) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS FOR THE BACKFLOW PREVENTER. WPB AMEND.
 TO 2010 FBC SEC. 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
  