Plan Review Details - Permit 15030253
| Plan Review Stops For Permit 15030253 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2015-03-24 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2015-03-24 |
Time |
17:21 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2015-03-24 |
Time |
17:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2015-03-23 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2015-03-23 |
Time |
07:24 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2015-03-23 |
Time |
07:18 |
Sent To |
|
|
| Notes |
| 2015-03-23 07:50:21 | RE-ROOF BUILDING REVIEW COMMENTS | | | CODE: 2010 FBC. | | | | | | 1- BORAL ROOFING UNDERLAYMENT FL14317-R5: IF USING A | | | DIRECT-BOND TO DECK UNDERLAYMENT, THEN SEE DESIGN | | | PRESSURES ON LIMITATIONS 5.5. SELECTED UNDERLAYMENT | | | NEEDS TO MEET THE DESIGN PRESSURES OF ALL ROOF ZONES | | | INCLUDING PERIMETER AND CORNER AREAS. IF SELECTED | | | UNDERLAYMENT DOESN'T MEET THE DESIGN PRESSURES OF ALL | | | ROOF ZONES, THEN IT CAN'T BE USED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2015-03-09 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2015-03-09 |
Time |
13:57 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2015-03-09 |
Time |
13:33 |
Sent To |
|
|
| Notes |
| 2015-03-09 14:09:42 | RE-ROOF BUILDING REVIEW COMMENTS | | | CODE: 2010 FBC. | | | | | | 1- MODIFIED BITUMEN ROOF SYSTEM FL10497-R2 SUBMITTED: | | | THE DESIGN PRESSURES OF SELECTED ROOF ASSEMBLY W-12 ARE | | | -60 PSF. NEED TO PROVIDE SIGNED AND SEALED RAS 117 | | | CALCULATIONS AS REQUIRED BY NOTE #8 (PAGE 2 OF 16) TO | | | MEET THE DESIGN PRESSURES REQUIRED BY SEC. 1609 OF 2010 | | | FBC. | | | | | | 2- BORAL ROOFING UNDERLAYMENT FL14317-R5: IF USING A | | | DIRECT-BOND TO DECK UNDERLAYMENT, THEN SEE DESIGN | | | PRESSURES ON LIMITATIONS 5.5. SELECTED UNDERLAYMENT | | | NEEDS TO MEET THE DESIGN PRESSURES OF ALL ROOF ZONES | | | INCLUDING PERIMETER AND CORNER AREAS. IF SELECTED | | | UNDERLAYMENT DOESN'T MEET THE DESIGN PRESSURES OF ALL | | | ROOF ZONES, THEN IT CAN'T BE USED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | [email protected] |
|
|
| Review Stop |
HIST |
HISTORICAL |
| Rev No |
1 |
Status |
P |
Date |
2015-03-06 |
|
|
Cont ID |
|
| Sent By |
fmittner |
Date |
2015-03-06 |
Time |
11:16 |
Rev Time |
0.00 |
| Received By |
fmittner |
Date |
2015-03-06 |
Time |
11:16 |
Sent To |
|
|
| Notes |
|
|
|