Plan Review Details - Permit 15030218
Plan Review Stops For Permit 15030218
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-03-19 Cont ID  
Sent By dhayes Date 2015-03-19 Time 14:20 Rev Time 0.00
Received By dhayes Date 2015-03-19 Time 13:34 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-03-07 Cont ID  
Sent By dhayes Date 2015-03-07 Time 10:17 Rev Time 0.00
Received By dhayes Date 2015-03-07 Time 10:17 Sent To  
Notes
2015-03-07 10:31:123/7/2015
 PROJECT: AUDIO/VIDEO
 PERMIT#: 15030218
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 PROVIDE REVISED PLANS AND SPECIFICATION TO ADDRESS THE
 COMMENTS LISTED BELOW:
  
 1) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. WPB AMENDMENTS
 107.2.1.
 FL STATE STATEUTE SAYS: ALL FINAL DRAWINGS,
 SPECIFICATIONS, PLANS, REPORTS, OR DOCUMENTS PREPARED
 OR ISSUED BY THE LICENSEE AND BEING FILED FOR PUBLIC
 RECORD AND ALL FINAL DOCUMENTS PROVIDED TO THE OWNER OR
 THE OWNER?S REPRESENTATIVE SHALL BE SIGNED BY THE
 LICENSEE, DATED, AND SEALED WITH SAID SEAL.
 FL SS 471.025 668.001-668.006.
 THE PLANS PROVIDED HAVE BEEN PREPARED ON A PLAN WITH AN
 ARCHITECT'S TITLE BLOCK BUT WITHOUT THE SIGNATURE OR
 SEAL OF THE ARCHITECT. PROVIDE THE NAME AND SIGNATURE
 OF THE DESIGNER ON THE PLANS. IF THE PLAN HAS A TITLE
 BLOCK BELONGING TO AN ARCHITECT OR ENGINEER IT SHALL BE
 THE ARCHITECT OR ENGINEER THAT IS RESPONSIBLE FOR
 SIGNING AND SEALING THE PLAN.
  
 2) PROVIDE MANUFACTURER PRODUCT APPROVALS FOR
 AUDIO/VIDEO EQUIPMENT.
  
 3) PROVIDE A CABLE TYPE SYMBOLS LEGEND AND PRODUCT
 APPROVALS FOR EACH CABLE TYPE INDICATED IN THE LEGEND.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-03-19 Cont ID  
Sent By dhayes Date 2015-03-19 Time 14:20 Rev Time 0.00
Received By dhayes Date 2015-03-18 Time 14:02 Sent To  
Notes
2015-03-18 14:02:57SENT TO D HAYES

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-03-07 Cont ID  
Sent By dhayes Date 2015-03-07 Time 10:17 Rev Time 0.00
Received By dhayes Date 2015-03-05 Time 14:38 Sent To  
Notes
2015-03-05 14:38:57TO ELEC < $5K


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved