Plan Review Details - Permit 15030098
Plan Review Stops For Permit 15030098
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-04-07 Cont ID  
Sent By rlecky Date 2015-04-07 Time 11:10 Rev Time 0.00
Received By rlecky Date 2015-04-07 Time 11:05 Sent To FIRE
Notes
2015-04-07 11:12:08SEE ATTACHED DOCUMENTS FOR ELECTRICAL.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-04-02 Cont ID  
Sent By rlecky Date 2015-04-02 Time 14:14 Rev Time 0.00
Received By rlecky Date 2015-04-02 Time 14:00 Sent To  
Notes
2015-04-02 14:27:09 
 15030098
 401 OGSTON STREET
 GENERATOR FOR TOWER #3
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 A DISCONNECTING MEANS IS REQUIRED AT THE GENERATOR. NEC
 445.18
  
 THE AMPACITY OF THE CONDUCTORS TO THE THE FIRST
 DISTRIBUTION DEVICE WITH OVERCURRENT PROTECTION SHALL
 NOT BE LESS THAT 115% OF THE NAMEPLATE CURRENT RATING
 OF THE GENERATOR. NEC 445.13
  
 INDICATE THE SIZE OF THE CONDUIT AND WIRING METHOD
 PROPOSED FROM THE GENERATOR TO THE MODULAR BUILDING.
 NEC 215.5
  
 PROVIDE A GROUNDING SYSTEM FOR THE GENERATOR. NEC
 250.20, 250.30
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS REVIEW
 561-373-3701
 [email protected]
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-04-07 Cont ID  
Sent By pleduc Date 2015-04-07 Time   Rev Time 0.00
Received By pleduc Date 2015-04-07 Time 14:51 Sent To  
Notes
2015-04-07 15:07:19THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 PROVIDE FOR KNOX BOX KEY ACCESS.
  
 PROVIDE A 10LB ABC FIRE EXTINGUISHER AND CLASS C FOR
 ELECTRICAL EQUIPMENT SEPARATELY IF DESIRED.
  

Review Stop Z ZONING
Rev No 2 Status P Date 2015-04-23 Cont ID  
Sent By ajones Date 2015-04-23 Time 13:53 Rev Time 0.00
Received By ajones Date 2015-04-23 Time 13:53 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2015-04-02 Cont ID  
Sent By jroach Date 2015-04-02 Time 09:54 Rev Time 0.00
Received By jroach Date 2015-04-02 Time 09:54 Sent To  
Notes
2015-04-02 09:54:35ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 04.02.2015
 PERMIT NO.: 15030098
 ADDRESS: 401 OGSTON STREET
 CONTRACTOR/CONTACT: JASON BLACK
 TELEPHONE NO.: 712.258.6690
 SCOPE OF REVIEW: MODULAR BUILDING FOR COMMUNICATIONS
 TOWER.
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. ALL EQUIPMENT COMPOUNDS SHALL BE ENCLOSED BY A SOLID
 OPAQUE FENCE OR WALL. CHAIN LINK, CHAIN LINK WITH
 SLATS, OR CHAIN LINK WITH FABRIC SCREENING, IS NOT
 ACCEPTABLE. SEPARATE PERMIT APPLICATIONS SHALL BE
 SUBMITTED FOR THE FENCE/WALL.
  
 2. ALL EQUIPMENT COMPOUNDS SHALL BE LANDSCAPED WITH
 SHRUBS/HEDGES PLANTED AT TWO (2) FOOT INTERVALS. SUCH
 LANDSCAPING SHALL BE SERVED BY AN AUTOMATIC IRRIGATION
 SYSTEM PROVIDING 120% COVERAGE. LANDSCAPE PLANS SHALL
 BE PREPARED BY A REGISTERED LANDSCAPE ARCHITECT. AND
 ALL LANDSCAPING AND IRRIGATION WORK SHALL BE SUBMITTED
 UNDER SEPARATE PERMIT APPLICATIONS.
  
 3. ADDITIONAL INFORMAITON SHALL BE PROVIDED REGARDING
 THE GENERATOR, PROPANE TANK, ETC. SPECIFICALLY, WHAT IS
 THE HEIGHT OF EACH. THEY WILL NEED TO BE ADEQUATELY
 SCREENED BY THE ABOVE-METIONED OPAQUE WALL/FENCE.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1448
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.WPB.ORG
  
 3/10/15


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved