Plan Review Details - Permit 15030089
| Plan Review Stops For Permit 15030089 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2015-03-06 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2015-03-06 |
Time |
16:54 |
Rev Time |
0.00 |
| Received By |
dhayes |
Date |
2015-03-06 |
Time |
16:54 |
Sent To |
FIRE |
|
| Notes |
| 2015-03-06 16:55:30 | SEPARATE PERMIT APPLICATION REQUIRED BY ELECTRICAL | | | CONTRACTATOR FOR 120V CONNECTION OF ELECTRICAL SUPPLY | | | CIRCUIT TO NAC POWER SUPPLY. | | | | | | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, | | | 561-805-6717 OR [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2015-03-09 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2015-03-09 |
Time |
11:08 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2015-03-09 |
Time |
10:58 |
Sent To |
I |
|
| Notes |
| 2015-03-09 11:08:01 | PERMIT # 15030089 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PROVISO: | | | THIS PLAN HAS BEEN APPROVED WITH PROVISIONS. BECAUSE | | | DRAWING PROVIDED STATES "NOT TO SCALE" THE FINAL | | | APPROVAL OF LOCATION AND NUMBER OF DEVICES NEEDED WILL | | | BE DONE IN THE FIELD AT THE TIME OF INSPECTION. | | | ADDITIONAL DEVICES MAY BE NEEDED OR DEVICES MAY NEED TO | | | BE RELOCATED IF FIELD INSPECTOR DEEMS THAT PROPER | | | COVERAGE IS NOT PROVIDED. | | | | | | IN THE FUTURE, PLEASE PROVIDE DRAWINGS THAT ARE "TO | | | SCALE" AT A MINIMUM OF 1/8" = 1' AND/OR PROVIDE | | | APPROPRIATE DIMENSIONS. | | | | | | SUE ELLEN CALDERON | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 644-7326 | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2015-03-04 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2015-03-04 |
Time |
14:40 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2015-03-04 |
Time |
14:32 |
Sent To |
E |
|
| Notes |
| 2015-03-04 14:40:41 | PERMIT # 15030089 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | FAILED COMMENTS: | | | 1) PLAN PROVIDED IS NOT TO SCALE AND THE DRAWINGS ARE | | | TOO SMALL FOR A DETAILED AND ACCURATE REVIEW. PROVIDE 2 | | | SETS OF PLANS THAT ARE SCALED AT A MINIMUM OF 1/8" = | | | 1'. | | | | | | | | | SUE ELLEN CALDERON | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 644-7326 | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2015-03-09 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2015-03-09 |
Time |
11:08 |
Rev Time |
|
| Received By |
scaldero |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
|