| 2015-04-01 18:27:07 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | COMMENTS FROM PREVIOUS LIST: |
| | |
| | 1. COMPLETE THE SAMPLE INSTALLATION SCHEDULE OR PROVIDE |
| | ALL INFORMATION TO SHOW CODE COMPLIANCE IN ANOTHER |
| | FORMAT, FBC*106, FBC R301, FBC1609. TWO SETS REQUIRED. |
| | THIS FORM IS AVAILABLE IN THE LOBBY OR ON THE INTERNET |
| | AT |
| | |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/SCHEDULE_FOR_INSTALLATION.PDF |
| | |
| | 2ND REVIEW - THE PRODUCT APPROVAL IS EXPIRED (FBC 2007 |
| | RATHER THAN FBC 2010). THE INSTALLATION SCHEDULE CANNOT |
| | BE REVIEWED UNTIL THE CORRECT PRODUCT APPROVAL IS |
| | PROVIDED. HOWEVER, PLEASE NOTE THE FOLLOWING: |
| | |
| | SEE PAGE 5 OF THE PRODUCT APPROVAL, AND OTHER ANCHOR |
| | CHARTS. A 3 1/2" EDGE DISTANCE IS REQUIRED FOR THIS |
| | PRODUCT APPROVAL, BUT 3" SPECIFIED ON THE INSTALLATION |
| | SCHEDULE. |
| | |
| | SEE PAGE 5 OF THE PRODUCT APPROVAL, AND OTHER ANCHOR |
| | CHARTS. FASTENER SHOULD CORRELATE WITH THE CHARTS. NOTE |
| | THAT TAPCON IS NOT ALLOWED FOR SOME OF THE ANCHOR |
| | TYPES. INSTALLATION SCHEDULE STATES THAT THIS IS CB |
| | SUBSTRATE. |
| | HORIZONTAL INSTALLATION IS TYPICALLY CB OR GROUT FILLED |
| | CELLS (IF THIS IS AN OPTION ON THE PRODUCT APPROVAL), |
| | VERTICAL INSTALLATIONS ARE USUALLY CONCRETE TOP, BLOCK |
| | BOTTOM. |
| | |
| | SHUTTER CONNECTION MOUNTING TYPE SHOULD CORRELATE WITH |
| | THE ANCHOR CHARTS. SEE PAGE 5 AND OTHER SHEETS. THE |
| | MOUNTING TYPES IN THIS PRODUCT APPROVAL ARE NAMED 1 |
| | (TOP), 1 (BOTTOM) THROUGH 8 (TOP), 8 (BOTTOM). SHEETS 2 |
| | THROUGH 4 PROVIDE DETAILS OF THE MOUNTING TYPES. |
| | |
| | SPAN SHOULD BE ONE DIMENSION (DISTANCE ANCHOR TO |
| | ANCHOR). |
| | |
| | 2. SHOW THE EMERGENCY MEANS OF ESCAPE, FBC R310.4. |
| | INCLUDE THE ROOM DESIGNATION. |
| | |
| | THE "EGRESS" SHOWN ON THE PLAN HAS SHUTTERS PROPOSED. |
| | GARAGE ROLL UP DOOR CANNOT BE EMERGENCY MEANS OF ESCAPE |
| | AND RESCUE. |
| | |
| | 3. OK |
| | |
| | 4. PROVIDE THE FLORIDA STATE PRODUCT APPROVAL COVER |
| | PAGE. THIS WILL INCLUDE THE NUMBER AND STATUS (SHOULD |
| | BE "APPROVED"). |
| | |
| | THE PRODUCT APPROVAL PROVIDED IS EXPIRED (FBC 2007). |
| | PROVIDE A CURRENT PRODUCT APPROVAL (FBC 2010). |
| | |
| | TWO COMPLETE, COLLATED SETS OF PLANS REQUIRED FOR |
| | PERMIT ISSUANCE. |
| | |
| | 5. ALTHOUGH THE OWNER'S AND CONTRACTOR'S SIGNATURES |
| | HAVE BEEN NOTARIZED, NEITHER HAS SIGNED ON THE LINE FOR |
| | THE SIGNATURE. COUNTY INFORMATION FOR OWNER IS BLANK. |
| | PLEASE SEE FS117. |
| | |
| | |
| | IMPORTANT NOTICE: COMING SOON IN 2015 |
| | ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED |
| | ELECTRONICALLY |
| | UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS |
| | SUBMISSION OPTIONS ARE AS FOLLOWS: |
| | 1 UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL |
| | SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE |
| | THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| | 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL |
| | SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED |
| | NAMING CONVENTION FOR EACH DOCUMENT |
| | 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER |
| | DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE |
| | REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| | 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT |
| | TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS |
| | ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES |
| | AVAILABLE |
| | |
| | |