| 2015-04-01 07:17:06 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FROM PREVIOUS LIST: |
| | |
| | 1. PLANS TO BE ARCHITECTURAL QUALITY TO SCALE. ONE |
| | APPLICATION (15030034) IS FOR "MINOR DRYWALL REPAIR" |
| | BUT NOTHING ON PLAN SHOWING SCOPE / LOCATION. THERE |
| | SHOULD BE AN EXISTING AND PROPOSED PLAN. APPLICATION TO |
| | INCLUDE ALL WORK INCLUDED IN THE VIOLATION ISSUED. FBC |
| | 107 |
| | |
| | 2ND REVIEW, NOTE STATES "MINOR DRYWALL REPAIRS (HOLES)" |
| | - DOES NOT SHOW LOCATIONS. IF A PART OF A FIRE RATED |
| | TENANT SEPARATION WALL, A DETAIL WILL BE REQUIRED. PER |
| | INSPECTOR AND PHOTOGRAPHS OF THE JOB, DRYWALL REPAIR |
| | WAS MORE EXTENSIVE THAN INDICATED ON THE PLANS. SCOPE |
| | ALSO INCLUDED WALL FRAMING. SEE FIRST LIST; PROVIDE AN |
| | ARCHITECTURAL PLAN WHICH SHOWS WORK STARTED WITHOUT |
| | PERMIT. |
| | |
| | 2. OK |
| | |
| | NEW COMMENT: |
| | |
| | 3. VALUE TOO LOW. PROVIDE A REASONABLE VALUE OR A |
| | VALUATION WILL BE DETERMINED FOR YOU, FBC 109. |
| | |
| | 4. THE RESUBMITTAL SHEET STATES THAT ASPHALT WILL BE |
| | REPLACED WITH GRASS AND PAVERS. A FENCE SKETCH WAS |
| | PROVIDED. BOTH REQUIRE SEPARATE PERMITS. |
| | |
| | 5. THE NEW PLAN SHOWS TILE FLOORS. IS THIS EXISTING OR |
| | PROPOSED? IF PROPOSED, TEST REPORTS REQUIRED FOR 2ND |
| | FLOOR UNITS: |
| | |
| | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| | IF A SUSPENDED CEILING WAS USED AS A PART OF THE TEST, |
| | PROVIDE INFORMATION AS TO HOW IT HAS BEEN DETERMINED |
| | THAT THIS CONDITION CURRENTLY EXISTS AND HOW IT CAN BE |
| | GUARANTEED THAT THE CONDITIONS IN THE UNIT BELOW WILL |
| | NOT BE ALTERED. |
| | |
| | PLEASE PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. IF A SUSPENDED CEILING WAS USED AS A PART |
| | OF THE TEST, PROVIDE INFORMATION AS TO HOW IT HAS BEEN |
| | DETERMINED THAT THIS CONDITION CURRENTLY EXISTS AND HOW |
| | IT CAN BE GUARANTEED THAT THE CONDITIONS IN THE UNIT |
| | BELOW WILL NOT BE ALTERED. |
| | |
| | PLEASE PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | IF TILE EXISTING, REVISE PLAN TO INCLUDE THAT |
| | INFORMATION. SCOPE WILL BE CONFIRMED WITH THE INSPECTOR |
| | / PHOTOGRAPHS. |
| | |
| | |
| | |