Plan Review Details - Permit 15030014
Plan Review Stops For Permit 15030014
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-07-20 Cont ID  
Sent By jwitmer Date 2015-07-20 Time 16:39 Rev Time 0.00
Received By jwitmer Date 2015-07-20 Time   Sent To FIRE
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-06-12 Cont ID  
Sent By jwitmer Date 2015-06-12 Time 12:29 Rev Time 0.00
Received By jwitmer Date 2015-06-12 Time 09:57 Sent To  
Notes
2015-06-12 11:54:37BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15030014
 ADD: 1717 EDGER ST.
 CONT: BATTEN
 TEL: (561)655-3344
 E-MAIL: ????
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: FRI. JUNE / 2015
 ACTION: DENIED
  
 1) COMPLIED. NOTE THE NEW MEZZANINE LEVEL DOE NOT NEED
 VERTICAL ACCESSIBILITY. AREA STORAGE/ DESIGNED FOR 125
 LB LIGHT STORAGE, OCCUPANT LOAD OF (2).
  
 2) 2ND REQUEST. SEMI-COMPLIED. HAND RAIL SYSTEM.
 SECTION # 2 SHOWS THE HAND RAIL ON THE EXTERIOR OF THE
 GUARD RAIL SYSTEM ON THE MEZZANINE PLATFORM. PLEASE
 PROVIDE A CUT SECTION THROUGH THE STAIR SHOWING THE
 GUARDRAIL AND HAND RAIL SYSTEM. FBC-B 1012.2 HEIGHT,
 ALSO REVIEW THE REQUIRED CLEARANCE BETWEEN THE HANDRAIL
 AND WALL OR BACKING OF GUARDRAIL, FBC-B 1012.7.
 .
  
 3) 2ND REQUEST, SEMI COMPLIED. PLEASE REVIEW THE
 DIMENSION LINES AT THE BOTTOM OF THE STAIRS, THE HEIGHT
 DIMENSION STOPS AT THE 1ST RISER NOT THE FLOOR LEVEL.
 THE 2ND ISSUE IS THE 42 INCHES IS TO BE TAKEN AT THE
 FRONT OF THE STAIR, NOT THE BACK OF THE STAIR, SEE THE
 TOP O FTHE STAIR, THE 42 INCHES IS TAKEN FROM THE BACK
 OF THE STAIR, THE GUARDRAIL IS NOT 42 INCHES TALL.
 FBC-B 1013.2.
  
 4) WITH THE GUARDS GOING TO THE REQUIRED 42 INCHES,
 PLEASE SHOW COMPLIANCE WITH 2010 FBC-B1012 HANDRAILS
 SECTIONS 1-8.
  
 5A) PROVISO: TO BE POSTED AT THE JOBSITE. 2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, ADMINISTRATION, 106.1 LIVE LOADS POSTED.
 WHERE THE LIVE LOADS FOR WHICH EACH FLOOR OR PORTION
 THEREOF OF A COMMERCIAL OR INDUSTRIAL BUILDING IS OR
 HAS BEEN DESIGNED TO EXCEED 50 PSF (2.40 KN/M2), SUCH
 DESIGN LIVE LOADS SHALL BE CONSPICUOUSLY POSTED BY THE
 OWNER IN THAT PART OF EACH STORY IN WHICH THEY APPLY,
 USING DURABLE SIGNS. IT SHALL BE UNLAWFUL TO REMOVE OR
 DEFACE SUCH NOTICES.
  
 15B) SEMI COMPLIED, THE ENGINEER OF RECORD HAS PROVIDED
 CALCULATIONS FOR THE LOADING OF THE LEDGER, PLEASE
 PROVIDE VERIFICATION OF THE ALLOWABLE LOADS THAT CAN BE
 TAKEN FOR THE SPECIFIC TYPE OF FASTENER TO BE USED IN
 THE INSTALATION, PLEASE ALSO VERIFY THE ALLOWABLE LOADS
 THAT CAN BE TAKEN FOR MASONRY UNITS VERSES THAT FOR
 2,000 PSI CONCRETE.
  
 106.3 RESTRICTIONS ON LOADING. IT SHALL BE UNLAWFUL TO
 PLACE, OR CAUSE OR PERMIT TO BE PLACED, ON ANY FLOOR OR
 ROOF OF A BUILDING, STRUCTURE OR PORTION THEREOF, A
 LOAD GREATER THAN IS PERMITTED BY THIS CODE. PLEASE
 PROVIDE CALCULATIONS FOR THE LOADS O BE IMPOSED ON THE
 WALL LEDGER AND TAPCONS THAT WILL BE HOLDING THE FLOOR
 LOADS. THE PLANS INDICATE THE USE OF 1/4 INCH TAPCONS
 WITH 1 1/4 EMBEDMENT @ 8 INCHES O. C. THE PLANS DO NO
 INDICATE THE VALUE OF THE TAPCONS ULTAMENT OR
 ALLOWABLE, THE VALUES FOR CONCRETE AND OR CMU UNITS.
 THE UNKNOWNS OF IFTHERE IS A CONCRTE TIE BEAM VERSES
 CONCRETE BLOCK, THERE ARE GREAT DIFFERENCES IN VALUES
 THAT ARE UNKNOWN FOR THE LIVE LOADS (VALUE NOT PROVIED)
 OF FBC- TABLE 1607.1 (36) LIGHT 125 PSF UNIFORM
 LOADING.
  
 6) COMPLIED. THE PLANS FAIL TO PROVIDE THE LIVE LOADS
 FOR THE STAIRS, FBC-B TABLE 1607.1 (35) 100 PSF.
  
 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 8) NOE ONLY (1) SET OF NEW PLANS WERE SUBMITTED.
  
 9) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-03-19 Cont ID  
Sent By jwitmer Date 2015-03-19 Time 10:18 Rev Time 0.00
Received By jwitmer Date 2015-03-19 Time 08:00 Sent To  
Notes
2015-03-19 10:18:21BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15030014
 ADD: 1717 EDGER ST.
 CONT: BATTEN
 TEL: (561)655-3344
 E-MAIL: ????
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE
  
 1ST REVIEW
 DATE: THURS. MARCH 19/ 2015
 ACTION: DENIED
  
 1) THE FLOOR PLANS INDICATE THE SQ. FT. OF THE FLOOR
 PLAN TO BE 1700 SQ. FT. INVARIOUS AREAS THIS EFFECTS,
 SQUARE FOOTAGE, OCCUPANCY LOADS. THRERE IS NO OVERALL
 DIMENSIONS TO SIZE THE TENANT SQUARE FOOTAGE. THE FLOOR
 PLAN INDICATES IT IS DRAWN TO 1/4 INCH SCALE = 1'-0".
 THE OVERALL SQUARE FOOTAGE OF THE FLOOR LEVEL (WITHOUT
 MEZZANINE) MEASURES 636 SQ. FT. THE OFFICE AREA REMOVED
 FROM THE 1ST FLOOR AREA (THIS AREA DOES NOT COMMUNITE
 WITH THE MEZZANINE). SEE 2010 FBC-B 505.2. THE NET 1ST
 FLOOR AREA IS 576.5 SQ. FT.
  
 2010 FBC-B 505.2
 ALLOWABLE AREA OR AREA LIMITATION 505.2. 576.5 SQ.
 FT./3= 192 SQ. FT. OF MEZZANINE AREA. THE AREA OVER THE
 ENCLOSED ROOM IS TO ALSO TO BE PART O FTHE NEW
 MEZZANINE, THIS AREA WILL NEED TO BE ENCLUDED INTO THE
 ALLOWABLE SQUAR FOOTAGE OF THE MEZZANINE. WITH THIS
 AREA INCLUDED IN THE MEZZANINE SQ. FOOTAGE THE TOTAL
 SQ. FT. OF THE MEZZANINE IS NOW 263.5 SQ. FT. OR 71.5
 FT. OVER THE ALLOWABLE AREA.
  
 2) PLEASE SEE GENERAL NOTE # 2 STATING THE EXST .BLDG
 CODE THIS SECTION IS FOR EXISTING STAIRWAYS, EXISTING
 HANDRAIL CONDITIONS. THIS IS NEW WORK AND COMPLIES WITH
 2010 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 3)
 THE PLANS SHOW A STAIR SECTION OF THE HANDRAIL/
 GUARDRAIL PLEASE NOTE THE GUARDRAIL IS ONLY 2'-10 TALL,
 THE REQUIRED HEIGHT OF 42 INCHES IS REQUIRED. 2010
 FBC-B 1013.2. PLEASE SEE EXCEPTION 1 & 2 ARE FOR WITH
 DWELLING UNITS OF R2 & R3 OCCUPANCIES ALLOW A THE
 GUARDS TO BE BETWEEN 34 & 38 INCHES.
  
 4) WITH THE GUARDS GOING TO THE REQUIRED 42 INCHES,
 PLEASE SHOW COMPLIANCE WITH 2010 FBC-B1012 HANDRAILS
 SECTIONS 1-8.
  
 5) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 106.1 LIVE
 LOADS POSTED. WHERE THE LIVE LOADS FOR WHICH EACH FLOOR
 OR PORTION THEREOF OF A COMMERCIAL OR INDUSTRIAL
 BUILDING IS OR HAS BEEN DESIGNED TO EXCEED 50 PSF (2.40
 KN/M2), SUCH DESIGN LIVE LOADS SHALL BE CONSPICUOUSLY
 POSTED BY THE OWNER IN THAT PART OF EACH STORY IN WHICH
 THEY APPLY, USING DURABLE SIGNS. IT SHALL BE UNLAWFUL
 TO REMOVE OR DEFACE SUCH NOTICES.
  
 106.3 RESTRICTIONS ON LOADING. IT SHALL BE UNLAWFUL TO
 PLACE, OR CAUSE OR PERMIT TO BE PLACED, ON ANY FLOOR OR
 ROOF OF A BUILDING, STRUCTURE OR PORTION THEREOF, A
 LOAD GREATER THAN IS PERMITTED BY THIS CODE. PLEASE
 PROVIDE CALCULATIONS FOR THE LOADS O BE IMPOSED ON THE
 WALL LEDGER AND TAPCONS THAT WILL BE HOLDING THE FLOOR
 LOADS. THE PLANS INDICATE THE USE OF 1/4 INCH TAPCONS
 WITH 1 1/4 EMBEDMENT @ 8 INCHES O. C. THE PLANS DO NO
 INDICATE THE VALUE OF THE TAPCONS ULTAMENT OR
 ALLOWABLE, THE VALUES FOR CONCRETE AND OR CMU UNITS.
 THE UNKNOWNS OF IFTHERE IS A CONCRTE TIE BEAM VERSES
 CONCRETE BLOCK, THERE ARE GREAT DIFFERENCES IN VALUES
 THAT ARE UNKNOWN FOR THE LIVE LOADS (VALUE NOT PROVIED)
 OF FBC- TABLE 1607.1 (36) LIGHT 125 PSF UNIFORM
 LOADING.
  
 6) THE PLANS FAIL TO PROVIDE THE LIVE LOADS FOR THE
 STAIRS, FBC-B TABLE 1607.1 (35) 100 PSF.
  
 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 8) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2015-03-31 Cont ID  
Sent By rlecky Date 2015-03-31 Time 14:00 Rev Time 0.00
Received By rlecky Date 2015-03-31 Time 13:57 Sent To  
Notes
2015-03-31 14:00:00NO ELECTRICAL PROPOSED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2015-07-24 Cont ID  
Sent By pleduc Date 2015-07-24 Time   Rev Time 0.00
Received By pleduc Date 2015-07-24 Time 15:26 Sent To PC
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-06-03 Cont ID  
Sent By pleduc Date 2015-06-03 Time   Rev Time 0.00
Received By pleduc Date 2015-06-03 Time 13:42 Sent To  
Notes
2015-06-03 14:02:02THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 ONLY 1 NEW PLAN SHEET PROVIDED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-03-04 Cont ID  
Sent By pleduc Date 2015-03-04 Time   Rev Time 0.00
Received By pleduc Date 2015-03-04 Time 15:26 Sent To  
Notes
2015-03-04 17:04:10THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE PROVIDE A LIFE SAFETY PLAN INDICATING OCCUPANCY
 LOADS, COMMON PATHS OF TRAVEL WITH DIMENSIONS, EXIT
 SIGNS, EMERGENCY LIGHTS, EXITS LEADING TO A PUBLIC WAY
 AND FIRE EXTINGUISHER LOCATIONS.
  
 PLEASE PROVIDE A OCCUPANCY SITE PLAN THAT LOCATES THE
 PROPOSED MEZZANINE WITHIN THE OCCUPANCY AREA WITH ALL
 DIMENSIONS THAT CONFIRM IT MEETS THE 1/3 OF THE AREA
 REQUIREMENT.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-08-13 Cont ID  
Sent By jwitmer Date 2015-08-13 Time 14:37 Rev Time 0.00
Received By jwitmer Date 2015-08-13 Time 14:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-07-24 Cont ID  
Sent By pleduc Date 2015-07-24 Time   Rev Time 0.00
Received By pleduc Date 2015-07-13 Time 15:23 Sent To  
Notes
2015-07-13 15:24:03ON JWITMER DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-06-08 Cont ID  
Sent By   Date 2015-06-08 Time   Rev Time 0.00
Received By shill Date 2015-05-28 Time 11:43 Sent To  
Notes
2015-05-28 11:45:43B30
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-04-04 Cont ID  
Sent By tklarge Date 2015-04-04 Time 04:36 Rev Time 0.00
Received By tklarge Date 2015-03-02 Time 13:27 Sent To  
Notes
2015-03-02 15:42:05SENT TO B08.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status N Date 2015-08-13 Cont ID  
Sent By jwitmer Date 2015-08-13 Time 14:37 Rev Time 0.00
Received By jwitmer Date 2015-08-13 Time 14:34 Sent To  
Notes
2015-08-13 14:47:06IMPACT FEES;
 PLANS STAMPED 8/13/15
 MEZZANINE 214 SQ. FT. UNOCCUPIED STORAGE SPACE
 NO FEES. MAB
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2015-07-20 Cont ID  
Sent By jwitmer Date 2015-07-20 Time 16:38 Rev Time 0.00
Received By jwitmer Date 2015-07-20 Time   Sent To  
Notes
2015-07-20 16:39:40IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2015-06-12 Cont ID  
Sent By jwitmer Date 2015-06-12 Time 12:26 Rev Time 0.00
Received By jwitmer Date 2015-06-12 Time 12:26 Sent To  
Notes
2015-06-12 12:26:20IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-03-19 Cont ID  
Sent By jwitmer Date 2015-03-19 Time 10:18 Rev Time 0.00
Received By jwitmer Date 2015-03-19 Time 10:18 Sent To  
Notes
2015-03-19 10:18:58IMPACT FEES
 BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2015-03-19 Cont ID  
Sent By   Date 2015-03-19 Time   Rev Time  
Received By   Date 2015-03-19 Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2015-04-04 Cont ID  
Sent By tklarge Date 2015-04-04 Time 04:36 Rev Time 0.00
Received By tklarge Date 2015-04-04 Time 04:35 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-03-10 Cont ID  
Sent By sgraham Date 2015-03-10 Time 15:31 Rev Time 0.00
Received By sgraham Date 2015-03-10 Time 15:31 Sent To  
Notes
2015-03-10 13:52:093/10/15