| 2015-03-01 07:36:00 | 1) SUBMIT MANFACTURING SPECIFICATIONS FOR ALL GAS |
| | EQUIPMENT. THE ONLY SPECS ON FILE WITH THE CITY ARE FOR |
| | THE FIREPLACE AND THE BBQ GRIL UNDER PERMIT |
| | #14020415.L. ALL APPLIANCES SHALL BE LISTED AND LABELED |
| | PER THE 2010 FUEL GAS CODE SEC.301.3. |
| | 2) SHOW THE TOTAL BTU LOAD ON THE SYSTEM.WPB AMEND. TO |
| | 2010 FBC SEC.107.2.1.107.3.5.3. |
| | 3) SHOW THE DISTANCE FROM THE METER TO THE MOST REMOTE |
| | OUTLET ON THE SYSTEM. 2010 FGC SEC.402.4.1. |
| | 4) SUBMIT CALCULATIONS FOR COMBUSTION AIR FOR THE |
| | APPLIANCES ON THE INTERIOR OF THE BUILDING.2010 FGC |
| | SEC. 304. |
| | 5) SUBMIT A PLAN SHOWING THE LOCATION OF ALL GAS |
| | APPLIANCES. WPB AMEND. TO 2010 FBC SEC.107.2.1. |
| | 6) SUBMIT A PLAN SHOWING HE TYPE, LOCATION, SIZE AND |
| | TERMINATION POINTS OF ALL THE GAS VENTS.2010 FGC |
| | SECS.502 THROUGH 505. |
| | 7) THE GAS DRAWING SHOWS PE PIPE TO THE FIRE PIT. PE |
| | PIPE CAN ONLY BE USED OUTSIDE UNDERGROUND. SUBMIT |
| | INFORMATION FOR THE ABOVE GROUND PIPE. (MATERIAL & |
| | SIZE).WPB AMEND. TO 2010 FBC SEC.107.2.1, 2010 FGC |
| | SEC.404.15. |
| | 8) SHOW THE TYPE OF PIPE MATERIAL FOR THE CONNECTIONS |
| | AT THE WATER HEATERS, FUTURE DRYER, BBQ, AND THE |
| | GENERATOR. |
| | 9) INDICATE THE PIPE SIZE OF THE PIPE SECTION BETWEEN |
| | THE METER AND THE TEE TO THE GENERATOR AND BETWEEN THE |
| | TEE FOR THE GENERATOR AND THE TEE AT THE BASE WHERE THE |
| | PE PIPE SPLITS INTO 2 SECTIONS.WPB AMEND. TO 2010 FBC |
| | SEC.107.2.1, 107.3.5.3. |
| | 10) THE DESCRIPTION OF WORK ON THE GAS PERMIT |
| | APPLICATION DOES NOT SHOW THE THREE WATER HEATERS. |
| | INCLUDE THE THREE HEATERS ON THE SYSTEM AND ADD THE |
| | ADDITIONAL VALUE ONTO THE THE JOB VALUATION ON THE |
| | APPLICATION. WPB AMEND. TO 2010 FBC SEC.109.3. |
| | |