| 2015-03-12 10:26:40 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | 1. PLANS TO BE ARCHITECTURAL QUALITY, TO SCALE. TEXT ON |
| | THE PLAN IS IN THREE DIFFERENT ORIENTATIONS. PLANS |
| | SHOULD BE READABLE WITHOUT ROTATION. APPLICATION IS FOR |
| | "FLOORS, DOORS, KITCHEN, PAINT." PLANS SHOULD REFLECT |
| | WORK PROPOSED, FBC 107. |
| | |
| | 2. PROVIDE THE FLORIDA STATE PRODUCT APPROVAL COVER |
| | SHEET, FAC9N-3. THIS SHOWS THE NUMBER AND STATUS. ON |
| | THE EVALUATION REPORT PROVIDED, INDICATE WHICH OF THE |
| | DOORS IS PROPOSED. |
| | |
| | 3. FOR THE TWO STORY BUILDING, LABEL THE UNITS. IF THE |
| | FLOOR CEILING ASSEMBLY IS A TENANT SEPARATION, PROVIDE |
| | FLOORING UNDERLAYMENT TEST REPORTS: |
| | |
| | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| | IF A SUSPENDED CEILING WAS USED AS A PART OF THE TEST, |
| | PROVIDE INFORMATION AS TO HOW IT HAS BEEN DETERMINED |
| | THAT THIS CONDITION CURRENTLY EXISTS AND HOW IT CAN BE |
| | GUARANTEED THAT THE CONDITIONS IN THE UNIT BELOW WILL |
| | NOT BE ALTERED. |
| | |
| | PLEASE PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. IF A SUSPENDED CEILING WAS USED AS A PART |
| | OF THE TEST, PROVIDE INFORMATION AS TO HOW IT HAS BEEN |
| | DETERMINED THAT THIS CONDITION CURRENTLY EXISTS AND HOW |
| | IT CAN BE GUARANTEED THAT THE CONDITIONS IN THE UNIT |
| | BELOW WILL NOT BE ALTERED. |
| | |
| | PLEASE PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | IF THE FLOOR/CEILING ASSEMBLY IS NOT A TENANT |
| | SEPARATION, FLOORING UNDERLAYMENT INFORMATION NOT |
| | REQUIRED. |
| | |
| | 4. KITCHEN RENOVATION IS PROPOSED. PLANS SHOULD SHOW |
| | EXISTING AND PROPOSED. INCLUDE ANY PLUMBING AND |
| | ELECTRICAL WORK. |