| 2015-03-13 10:26:22 | 3/13/2015 |
| | PROJECT: SITE LIGHTING |
| | PERMIT#: 15020847 |
| | CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC |
| | ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1, |
| | ADMINISTRATION, 2012 FBC SUPPLEMENTS. |
| | 2ND ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) 505.2.4 EXTERIOR LIGHTING CONTROLS. |
| | LIGHTING FOR ALL EXTERIOR APPLICATIONS NOT EXEMPTED IN |
| | SECTION 505.1 SHALL HAVE AUTOMATIC CONTROLS CAPABLE OF |
| | TURNING OFF EXTERIOR LIGHTING WHEN SUFFICIENT DAYLIGHT |
| | IS AVAILABLE OR WHEN THE LIGHTING IS NOT REQUIRED |
| | DURING NIGHTTIME HOURS. LIGHTING NOT DESIGNATED FOR |
| | DUSK-TO-DAWN OPERATION SHALL BE CONTROLLED BY EITHER A |
| | COMBINATION OF A PHOTOSENSOR AND A TIME SWITCH, OR AN |
| | ASTRONOMICAL TIME SWITCH. A TIME SWITCH IS NOTED ON |
| | SHEET E101 HOWEVER THERE IS NO NOTES OR PRODUCT |
| | APPROVAL ON TIME SWITCH THAT INDICATE COMPLIANCE WITH |
| | FBC 505.2. PROVIDE PRODUCT APPROVAL ON TIME SWITCH. |
| | |
| | 2) 2010 FBC-BUILDING SECTION 1609 |
| | PROVIDE ENGINEERED WIND LOAD CALCULATIONS FOR ALL LIGHT |
| | POLE CONFIGURATIONSINCLUDING LUMINAIRE IN COMPLIANCE |
| | WITH THE FBC 1609. |
| | |
| | 3) NEC 215.5 |
| | PROVIDE A LOAD CALCULATION FOR THE ELECTRICAL PANELS |
| | AND SERVICE PROPOSED TO FEED THE LIGHT POLES. |
| | |
| | 4) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS |
| | HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT |
| | NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE |
| | INTERRUPTED. NEC 110.9 |
| | |
| | 5) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR |
| | THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC |
| | 110.16. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |