Plan Review Details - Permit 15020842
Plan Review Stops For Permit 15020842
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-03-11 Cont ID  
Sent By shill Date 2015-03-11 Time 13:31 Rev Time 0.00
Received By shill Date 2015-03-05 Time 17:40 Sent To Z
Notes
2015-03-11 13:53:09****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. ENGINEER (ALI ABOLHASSANI, PE) HAS SIGNED AND SEALED
 A PLAN WITH AN ARCHITECT'S TITLE BLOCK (CUHACI &
 PETERSON). SEE FS 471, 481, FAC61G15-23. RESPONSIBILITY
 FOR THIS SHEET IS NOT CLEAR. DOES THE ENGINEER WORK FOR
 CUHACI & PETERSON? IF THIS IS THE CASE, INCLUDE THE
 ENGINEERING CERTIFICATE OF AUTHORIZATION FOR CUHACI &
 PETERSON. THE CALCS SEALED BY THIS ENGINEER INCLUDES
 ANOTHER COMPANY'S NAME (STRUCTURAL CONCEPTS
 ENGINEERING) IN THE TITLE BLOCK, NOT CUHACI & PETERSON.
  
 2. CALCULATIONS SIGNED AND SEALED BY ALI ABOLHASSANI,
 PE / STRUCTURAL CONCEPTS ENGINEERING LACK THE
 CERTIFICATE OF AUTHORIZATION NUMBER, FS471. THE
 CERTIFICATE OF AUTHORIZATION IS IN DELINQUENT STATUS.
  
 ENGINEER HAS BEEN DISCIPLINED, HAD HIS LICENSE
 SUSPENDED (AND SUBSEQUENTLY REINSTATED) OVER THESE
 ISSUES. PLEASE REVISE PLANS AND CALCS TO BE IN
 COMPLIANCE WITH FS471 AND FAC61G15-23 AND ENSURE THAT
 ALL FUTURE PLANS WILL BE IN COMPLIANCE. IF ENGINEER
 DOES NOT UNDERSTAND THE REQUIREMENTS (LAWS AND RULES),
 PLEASE CONTACT FBPE FOR CLARIFICATION.
  
 3. FBC 2010 BUILDING 1008.1.4.5, SECURITY GRILLS -
 PROVIDE A PLAN WHICH SHOWS COMPLIANCE WITH ALL
 REQUIREMENTS. THE PARTIAL FLOOR PLAN PROVIDED DOES NOT
 SHOW THE EXITS OR REQUIRED NUMBER OF EXITS. COMPLIANCE
 WITH THE OPERATIONAL REQUIREMENTS CAN BE DEMONSTRATED
 IN THE FORM OF A NOTES ON THE PLAN WHICH SHOWS
 COMPLIANCE WITH OTHER REQUIREMENTS.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-03-16 Cont ID  
Sent By scaldero Date 2015-03-16 Time 15:12 Rev Time 0.00
Received By scaldero Date 2015-03-16 Time 15:08 Sent To I
Notes
2015-03-16 15:12:33PERMIT #15020842
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED:
 1) DRAWINGS WILL BE STAMPED, INITIALED, AND DATED BY
 THE FIRE DEPARTMENT AFTER ALL PLAN REVIEWER COMMENTS
 HAVE BEEN SATISFIED.
  
 2) A COPY OF THE KEY FOR THE KEYED LOCK ON THE SHUTTERS
 MUST BE PROVIDED FOR PLACEMENT IN THE FIRE DEPT. KNOX
 BOX, ALONG WITH THE STORE KEY.
  
  
 SUE ELLEN CALDERON
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-03-16 Cont ID  
Sent By scaldero Date 2015-03-16 Time 15:12 Rev Time 0.00
Received By shill Date 2015-03-11 Time 14:17 Sent To  
Notes
2015-03-11 14:18:013/11 TO ES (ZONING)
  

Review Stop Z ZONING
Rev No 1 Status F Date 2015-03-11 Cont ID  
Sent By eschneid Date 2015-03-11 Time 14:36 Rev Time 0.00
Received By eschneid Date 2015-03-11 Time 14:36 Sent To  
Notes
2015-03-11 14:45:39FAILED
  
 1) THE PALM BEACH OUTLETS MANAGEMENT APPROVAL STAMP IS
 REQUIRED ON ALL PLANS. ZONING WILL PERFORM COMPLETE
 REVIEW UPON THE OUTLETS APPROVING THE SECURITY
 SHUTTERS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
  