Plan Review Details - Permit 15020828
Plan Review Stops For Permit 15020828
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-03-24 Cont ID  
Sent By dhayes Date 2015-03-24 Time 12:56 Rev Time 0.00
Received By dhayes Date 2015-03-24 Time 12:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-02-28 Cont ID  
Sent By wjolin Date 2015-02-28 Time 12:03 Rev Time 0.00
Received By dhayes Date 2015-02-25 Time 12:03 Sent To FIRE
Notes
2015-02-28 12:15:09REVISE THE SUBMITTAL IN COMPLIANCE WITH THE FOLLOWING
 COMMENTS:
  
 1) PROVIDE A FLOOR PLAN INDICATING ALL ACCESS CONTROL
 POINTS, THE DIRECTION OF THE SWING OF THE CONTROLLED
 DOOR, THE DIMENSION OF THE DOOR AND THE DIMENTIONS OF
 THE MEANS OF EGRESS.
 2) PROVIDE THE MANUFACTURER EQUIPMENTS SUBMITALS ON ALL
 EQUIPMENT NOT JUST MAG LOCKS.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-03-13 Cont ID  
Sent By wjolin Date 2015-03-13 Time 13:12 Rev Time 0.00
Received By wjolin Date 2015-03-13 Time 13:11 Sent To E
Notes
2015-03-13 13:12:29PER SECTION 7.2.1.6.2, ACCESS-CONTROLLED EGRESS DOORS
 ARE PERMITTED PROVIDED THAT ALL SEVEN OF THE FOLLOWING
 CRITERIA ARE MET:
 1. A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE,
 ARRANGED TO DETECT AN OCCUPANT APPROACHING DOORS THAT
 ARE ARRANGED TO UNLOCK IN THE DIRECTION OF EGRESS UPON
 DETECTION OF AN APPROACHING OCCUPANT OR LOSS OF POWER
 TO THE SENSOR.
 2. LOSS OF POWER TO THE PART OF THE ACCESS CONTROL
 SYSTEM THAT LOCKS THE DOORS SHALL AUTOMATICALLY UNLOCK
 THE DOORS IN THE DIRECTION OF EGRESS.
 3. THE DOORS SHALL BE ARRANGED TO UNLOCK IN THE
 DIRECTION OF EGRESS FROM A MANUAL RELEASE DEVICE
 LOCATED VERTICALLY 40 TO 48 INCHES ABOVE THE FLOOR AND
 WITHIN 60 INCHES HORIZONTALLY OF THE SECURED DOORS.
 4. THE MANUAL RELEASE DEVICE SHALL BE READILY
 ACCESSIBLE AND CLEARLY IDENTIFIED BY A SIGN THAT READS
 PUSH TO EXIT.
 5. WHEN OPERATED, THE MANUAL RELEASE DEVICE SHALL
 RESULT IN DIRECT INTERRUPTION OF POWER TO THE LOCK,
 INDEPENDENT OF THE ACCESS CONTROL SYSTEM ELECTRONICS,
 AND THE DOORS SHALL REMAIN UNLOCKED FOR NOT LESS THAN
 30 SECONDS.
 6. ACTIVATION OF THE BUILDING FIRE ALARM SYSTEM SHALL
 AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF
 EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE
 FIRE ALARM SYSTEM HAS BEEN MANUALLY RESET.
 7. ACTIVATION OF THE BUILDING AUTOMATIC SPRINKLER
 SYSTEM OR AUTOMATIC DETECTION SYSTEM SHALL
 AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF
 EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE
 FIRE ALARM SYSTEM HAS BEEN MANUALLY RESET.
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2015-03-04 Cont ID  
Sent By scaldero Date 2015-03-04 Time 12:49 Rev Time 0.00
Received By scaldero Date 2015-03-04 Time 12:49 Sent To I
Notes
2015-03-04 12:51:47PERMIT # 15020828
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FAILED COMMENTS:
 1) SEE BUILDING DEPARTMENT COMMENTS.
 2) PLEASE PROVIDE PRODUCT DATA SHEET FOR MAG LOCKS IN
 ENGLISH.
  
  
 SUE ELLEN CALDERON
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 644-7326
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-03-24 Cont ID  
Sent By dhayes Date 2015-03-24 Time 12:56 Rev Time 0.00
Received By dhayes Date 2015-03-09 Time   Sent To  
Notes
2015-03-09 17:26:43SENT TOFIRE BOX.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status   Date 2015-03-04 Cont ID  
Sent By dhayes Date 2015-03-04 Time 12:51 Rev Time 0.00
Received By scaldero Date 2015-02-25 Time 12:02 Sent To E
Notes
***NONE***