Plan Review Details - Permit 15020803
Plan Review Stops For Permit 15020803
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-04-22 Cont ID  
Sent By jwitmer Date 2015-04-22 Time 07:30 Rev Time 0.00
Received By jwitmer Date 2015-04-22 Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-03-05 Cont ID  
Sent By jwitmer Date 2015-03-05 Time 07:29 Rev Time  
Received By jwitmer Date 2015-03-05 Time 05:30 Sent To  
Notes
2015-03-05 07:29:30 
 BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15020803
 ADD: 777 S. FLAGLER DR. FLOORS 9 & 11
 CONT: CITY CONSTRUCTION GROUP
 TEL: (305)448-1118
 E-MAIL: TAMIA.PROPERMITSERVICES.COM
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE
  
 1ST REVIEW
 DATE: THURS. MARCH 05/ 2015
 ACTION: DENIED
  
 1) SHEET LS1.09 & LS1.11 BOTH SHOW A MIXED OCCUPANCY,
 THE 9TH FLOOR BUSSINESS & EDUCATION AND THE 11TH FLOOR
 BUSINESS AND ASSEMBLY OCCUPANCY. ON BOTH FLOORS THE
 TOTAL FLOOR PLATE OF 14,210 SQ. FT. ON THE 9TH FLOOR
 THE BUSINESS TRAINING (EDUCATIONAL) IS 1817 SQ. FT OR
 OVER THE 10% OF THE FLOOR PLATE, ON THE 11TH FLOOR THE
 ASSEMBLY OCCUPANCY OF 1,450 SQ.FT. ALSO OVER THE 10% OF
 THE FLOOR PLATE CREATING A MIXED OCCUPANCY. PLEASE
 INDICATE HOW CODE COMPLIANCE WITH 2010 FBC-B 508.1 WILL
 BE SATISFIED.
  
 2010 FBC-B WHERE A BUILDING CONTAINS MORE THAN ONE
 OCCUPANCY GROUP, THE BUILDING OR PORTION THEREOF SHALL
 COMPLY WITH THE APPLICABLE PROVISIONS OF SECTION 508.2,
 508.3 OR 508.4, OR A COMBINATION OF THESE SECTIONS.
  
 2) SHEET LS1.11 JUST TO THE RIGHT OF THE ELEVATOR LOBBY
 THERE ARE DOUBLE DOORS THAT LEED INSIDE THE TENANT
 SPACE, MARKED ONLY AS SCOPE OF WORK, THIS AREA IS NOT
 IDENTIFIED, NOR IS THE SQ. FT. IT APPEARS THIS MAY BE
 THE RECEPTION AREA THAT WOULD ADD TO THE ASSEMBLY SQ.
 FT. AREA. ADDITIONAL INFOMATION IS REQUIRED. 2010 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1, ADMINISTRATION, 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED FOR CODE COMPLIANCE.
  
 3) NEITHER THE 9TH FLOOR PLAN NOR THE 11TH FLOOR PLAN
 SHOWS ACCESSIBLE DRINKING FOUNTAINS WITHIN THE TENANT
 SPACE NOR THE CORE COMMON AREAS, PLEASE PROVIDE
 COMPLIANCE WITH:
  
 2010 FL ACCESSIBILITY CODE 211.2 MINIMUM NUMBER. NO
 FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
  
 FL ACCESS. CODE 202.4.1 DISPROPORTIONATE COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 4) SHEET A1.09 EXISTING DOOR # 1D/ 3D NEEDS TO BE AN
 ACCESSIBLE DOOR, SHEET LS1.09 SHOWS 1,817 SQ FT/ 20= 90
 OCCUPANTS WHICH REQUIRES 2 EXITS FROM THIS ROOM. SINCE
 2 MEANS OF ERGESS ARE REQUIRED THEN 2 ACCESSIBLE MEANS
 OF EGRESS ARE ALSO REQUIRED. 2010 FBC ACCESSIILITY CODE
 207.1 GENERAL. MEANS OF EGRESS SHALL COMPLY WITH
 SECTION 1003.2.13 OF THE INTERNATIONAL BUILDING CODE
 (2000 EDITION AND 2001 SUPPLEMENT) OR SECTION 1007 OF
 THE INTERNATIONAL BUILDING CODE (2003 EDITION)
 (INCORPORATED BY REFERENCE, SEE ?REFERENCED STANDARDS?
 IN CHAPTER 1).
 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS
 IS REQUIRED BY SECTION 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE SPACEEACH ACCESSIBLE PORTIONOF THE SPACE
 SHALL BE SERVED BY NOT LESS THAN TWO ACCESSIBLE MEANS
 OF EGRESS. PLEASE ALSO SEE THE DISPROPORTIONATE COST
 BREAK DOWN WHERE FUNDS ARE TO BE SPENT IN ACCESSIBLE
 UPGRADES. FL ACCESS. CODE 202.4.1.
  
 5) SHEET A1.09 DOES NOT SHOW A DETAIL FOR THE BREAK
 ROOM # 917 ON DETAIL SHEET A6.01 AS THE OTHER
 BREAKROOMS ARE DETAILEDSHOWING AN ACCESSIBLE SINK. 2010
 FL ACC CODE SECTION 606.1-5.
  
 SHEET A1.11 THIS SHEET DOES NOT SHOW DETAIL TAGS
 INDICATING WHERE THE ACCESSIBLE BREAK ROOM ELEVATIONS
 ARE LOCATED AND COMPLIANCE WITH, 2010 FL ACCESS. CODE
 SECTION 606. 1-5.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561) 805-6715
 FAX: (561)805-6676
 E-MAIL: [email protected]
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-04-16 Cont ID  
Sent By rlecky Date 2015-04-16 Time 10:06 Rev Time 0.00
Received By rlecky Date 2015-04-14 Time 13:35 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-03-03 Cont ID  
Sent By rlecky Date 2015-03-03 Time 12:30 Rev Time 0.00
Received By rlecky Date 2015-03-03 Time 11:53 Sent To  
Notes
2015-03-03 13:03:1215020803
 777 S. FLAGLER DR. #1100W
 PHILLIPS POINT INTERIOR ALTERATION
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 REVIEW COMMENTS.
  
 PANEL SCHEDULES DO NOT APPEAR TO MATCH THE ELECTRIC
 RISER PLAN. PROVIDE A RISER PLAN FOR THE NEW WORK WHICH
 SHOWS ALL CONDUIT AND WIRE SIZED. SHOW LOCATION AND
 PROVIDE A MOUNTING DETAIL FOR THE TRANSFORMER. SHOW
 LOCATION FOR ALL PANELS. NEC 215.5
  
 PROVIDE A FIRE STOP DETAIL FOR ANY WALL OR FLOOR
 PENETRATIONS OF FIRE RATED ASSEMBLIES. NEC 300.21
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS REVIEW
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-04-10 Cont ID  
Sent By pleduc Date 2015-04-10 Time   Rev Time 0.00
Received By pleduc Date 2015-04-10 Time 16:47 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-03-03 Cont ID  
Sent By pleduc Date 2015-03-03 Time   Rev Time 0.00
Received By pleduc Date 2015-03-02 Time 15:51 Sent To  
Notes
2015-03-03 10:40:41THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF THE
 FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE AND
 COMPLIANCE.
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-04-22 Cont ID  
Sent By tklarge Date 2015-04-22 Time 09:00 Rev Time 0.00
Received By tklarge Date 2015-04-09 Time 14:38 Sent To  
Notes
2015-04-09 14:41:09***EXPEDITED***
 C26
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-03-16 Cont ID  
Sent By tklarge Date 2015-03-16 Time 10:59 Rev Time 0.00
Received By tklarge Date 2015-02-25 Time 14:03 Sent To  
Notes
2015-02-28 14:03:52B29

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2015-03-13 Cont ID  
Sent By hmoser Date 2015-03-13 Time 15:30 Rev Time 0.00
Received By hmoser Date 2015-03-13 Time 14:36 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-04-22 Cont ID  
Sent By tklarge Date 2015-04-22 Time 08:59 Rev Time 0.00
Received By tklarge Date 2015-04-22 Time 08:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-03-16 Cont ID  
Sent By tklarge Date 2015-03-16 Time 10:57 Rev Time 0.00
Received By tklarge Date 2015-03-16 Time 10:39 Sent To  
Notes
2015-03-16 10:40:421) THE NINTH FLOOR DOES NOT SHOW ANY ACCESSIBLE
 DRINKING FOUNTAINS WITHIN THE TENANT SPACE OR THE
 COMMON CORE AREA.COMPLY WITH THE 2010 FAC SEC. 211.2.
 2) SUBMIT AN ELEVATION DETAIL FOR THE SINK IN BREAK
 ROOM # 917 IF THE ROOM IS WITHIN THE SCOPE OF WORK FOR
 THIS PROJECT. THE SINK SHALL COMPLY WITH THE FAC SEC.
 606.
 3) THE COFFEE MACHINES AND ANY WATER DISPENSERS SHALL
 BE PROTECTED AGAINST BACKFLOW PER 2010 FBC
 SEC.608.16.10.BACKFLOW PREVENTERS SHALL CONFORM TO ASSE
 1022.
 4) SHT. P1.09 - THE 2" VENT APPEARS TO BE OVER 40 FT.
 IN DEVELOPED LENGTH THEREFORE THE VENT SHALL BE
 INCREASED ONE PIPE SIZE FOR THE ENTIRE LENGTH PER THE
 2010 FPC SEC.916.2 & 916.4.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  