Plan Review Details - Permit 15020719
Plan Review Stops For Permit 15020719
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-03-30 Cont ID  
Sent By dhayes Date 2015-03-30 Time 09:16 Rev Time 0.00
Received By dhayes Date 2015-03-30 Time 09:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-02-27 Cont ID  
Sent By dhayes Date 2015-02-27 Time 07:47 Rev Time 0.00
Received By dhayes Date 2015-02-27 Time 07:44 Sent To  
Notes
2015-02-27 09:00:142/27/2015
 PROJECT: POOL HEATER 7441 MONTE VERDE LN
 PERMIT#: 15020719
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) WPB AMENDMENTS TO THE FBC 107.3.2
 PROVIDE ELECTRICAL PERMIT APPLICATION AS WELL AS
 ELECTRICAL PLANS AND SPECIFICATIONS TO INDICATE
 COMPLIANCE WITH CODE. INCLUDE THE FOLLOWING:
 THE LOCATION OF THE ELECTRICAL PANEL RELETIVE TO THE
 POOL HEATER. AND A PANEL SCHEDULE. NEC 408.4
 THE DEMOLITION OF THE PREVIOUS ELECTRIC POOL HEATER
 CIRCUIT AND TERMINATION OF PREVIOUS CIRCUITRY. NEC
 110.8
 THE INSTALLATIOON OF THE NEW ELECTRIC IGNIGHTER CIRCUIT
 INCLUDING EQUIPMENT GROUND. NEC 110.8, 250.4, 680.25(B)
 THE INSTALLATION OF THE BOND WIRE TO AN EQUIPOTENTIAL
 GROUND LOOP. NEC 680.26
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2015-03-04 Cont ID  
Sent By skennedy Date 2015-03-04 Time 15:59 Rev Time 0.00
Received By skennedy Date 2015-03-04 Time 15:59 Sent To  
Notes
2015-03-04 16:00:24A SEPARATE GAS PERMIT WILL BE APPLIED FOR BY BUCKEYE
 PLUMBING,

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2015-02-27 Cont ID  
Sent By tklarge Date 2015-02-27 Time 07:17 Rev Time 0.00
Received By tklarge Date 2015-02-25 Time 06:26 Sent To  
Notes
2015-02-27 06:41:071) A PERMIT APPLICATION SHALL BE SUBMITTED FROM A
 LICENSED GAS OR PLUMBING CONTRACTOR FOR THE
 INSTALLATION OF THE GAS PIPING FOR THE NEW POOL HEATER.
 A POOL CONTRACTOR CANNOT INSTALL THE GAS PIPING. WPB
 AMEND. TO 2010 FBC SEC. 105.1, FL. STATUTE 489.
 2) SUBMIT A GAS PIPNG RISER DIAGRAM FOR REVIEW.CLEARLY
 SHOW THE POINT OF DELIVERY, THE LENGTH OF ALL CUT
 SECTIONS OF PIPE, ALL PIPE SIZES. WPB AMEND. TO 2010
 FBC SEC. 107.2.1.
 3) INDICATE THE TYPE OF PIPE MATERIAL BEING INSTALLED
 FOR THE GAS SYSTEM.WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 4) INDICATE THE BTU LOAD OF THE POOL HEATER ON THE
 PLAN.WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 5) SHOW THE DISTANCE FROM THE GAS POINT OF DELIVERY TO
 THE POOL HEATER. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 6) INDICATE THE GAS DELIVERY PRESSURE. 2010 FBCR
 SEC.G2413.1.
 7) SUBMIT A DETAIL SHOWING THE THE TYPE, SIZE AND
 TERMINATION POINT OF THE GAS VENT IN RELATION TO THE
 STRUCTURE. COMPLY WITH 2010 FBCR SECTIONS G2426, G2427
 8) THE SUBMITTED POOL HEATER SPECIFICATIONS / MANUAL DO
 NOT INDICATE THE MANUFACTURER.SUBMIT SPECIFICATIONS
 THAT CLEARLY SHOW THE MANUFACTURER. 2010 FBCR SEC.
 G2404.3.
 9) SHOW THE LOCATION OF THE POOL HEATER ON THE
 SUBMITTED SURVEY. 2010 WPB AMEND. TO 2010 FBC SEC.
 107.2.1.
 10) SHOW THE SIZE OF THE INTAKE & RETURN LINES OF THE
 POOL HEATER ON THE PLANS. 2010 WPB AMEND. TO 2010 FBC
 SEC. 107.2.1.
 11) SUBMIT 2 COMPLETE COPIES OF THE POOL HEATER
 INSTALLATION MANUAL. ONLY SELECTED PAGES HAVE BEEN
 SUBMITTED. 2010 WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 12) INDICATE THE DIMENSIONS (L X W) AND THE THICKNESS
 OF THE EXISTING CONCRETE SLAB.2010 WPB AMEND. TO 2010
 FBC SEC. 107.2.1.
 13) INDICATE THE MODEL OF THE POOL HEATER ON THE
 SPECIFICATIONS.2010 WPB AMEND. TO 2010 FBC SEC.
 107.2.1.
 14) THE VALUE FOR THIS JOB APPEARS LOW ON THE
 APPLICATION. SUBMIT A DETAILED ESTIMATE OR A SIGNED
 CONTRACT SHOWING THE TOTAL VALUE OF THE JOB PER THE WPB
 AMEND. TO 2010 FBC SEC. 109.3.
 15) THE CITY OF WEST PALM BEACH IS LOCATED IN A 170 MPH
 WIND ZONE.THE MANUF. SPECIFICATIONS SHOW ANCHORING FRO
 A 150 MPH WIND ZONE. SUBMIT ENGINEERING FOR ANCHORING
 OF THE UNIT FOR 170 MPH WINDS OR SUBMIT
 DOCUMENTATION/DETAILS FROM THE MANUFACTURER FOR THE
 WIND LOAD ATTACHMENTS. 2010 FBCR SEC.G2404.6.
 16) PER THE 2010 FBCR SEC. G2404.7, STRUCTURES LOCATED
 IN FLOOD HAZARD AREAS SHALL HAVE THE APPLIANCE,
 EQUIPMENT, AND SYSTEM INSTALLATION REGULATED BY THE
 FLORIDA BUILDING CODE LOCATED AT OR ABOVE THE DESIGN
 FLOOD ELEVATION AND SHALL COMPLY WITH THE FLOOD
 RESISTANT CONSTRUCTION REQUIREMENTS OF 2010 FBCR
 SECTION R322.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-03-30 Cont ID  
Sent By dhayes Date 2015-03-30 Time 09:16 Rev Time 0.00
Received By dhayes Date 2015-03-30 Time 09:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-02-27 Cont ID  
Sent By tklarge Date 2015-02-27 Time 07:17 Rev Time 0.00
Received By tklarge Date 2015-02-23 Time   Sent To  
Notes
2015-02-24 11:37:48<5000 PLUMB DROPPED OFF ON 2-23-15 SYS DOWN