Plan Review Details - Permit 15020678
Plan Review Stops For Permit 15020678
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-06-19 Cont ID  
Sent By jwitmer Date 2015-06-19 Time 14:56 Rev Time 0.00
Received By jwitmer Date 2015-06-19 Time 14:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-03-11 Cont ID  
Sent By jwitmer Date 2015-03-11 Time 14:57 Rev Time 0.00
Received By jwitmer Date 2015-03-10 Time 09:24 Sent To  
Notes
2015-03-11 13:05:02 
 BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15020678
 ADD: 1309 N FLAGLER DR.
 CONT: WESTBROOKE
 TEL: (561)395-4126
 E-MAIL:
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE:
 ACTION: DENIED
  
 IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE
  
 1) SHEET EP-O DETAIL # 4 SEE SINGLE LINE AT PARKING
 STALL NOT CITY STANDARD. NOTE DET-1/ DETAIL 7 IS NOT
 CITY STANDARD EITHER, SEE W. P. B. MUNI CODE 94-485 FOR
 DOUBLE STRIPE.
  
 2) SHEET EP-1:
 2A) DETAIL # 5 DOESN'T INDICATE THE CHANGE TO BE MADE.
 DOOR TO ROOM 473A DOES NOT HAVE THE REQUIRED 18" ON THE
 LATCH SIDE OF DOOR. FBC-ACC. CODE 404.2.4.
  
 2B) DETAIL # 10 DOESN'T INDICATE THE CHANGE TO BE MADE.
 SEE ROOM 3146 DOORS IN SERIES. FL ACC. CODE 404.2.6.
  
 3) SHEET EP-3:
 3A) DETAIL # 2 NEW ACCESSIBLE BENCH LOCATION. SEE DET 4
 DETAIL 11 THE DETAIL IS NOT CLEAR THE BENCH IS ATTACHED
 TO THE WALL( NUMBER OF FASTENERS NOR SIZE) NOR DOES IT
 INDICATE A BACK SUPPORT. FL ACC. CODE 903.4.
  
 3B) DETAIL # 3 DOES NOT SHOW ANY CHANGE. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 3C) DETAIL # 6 NO CHANGE. MENS TOILET ROOM TB044 AT
 ENTRY DOOR MISSING THE 18 INCHES LATCH SIDE OF DOOR. FL
 ACC. CODE 404.2.4 MANEUVERING CLEARANCES.
  
 4)SHEET DET-2 SEE FIGURE 608.2.1 36X36 INCH SHOWER, THE
 48 INCHES IS TO BE TAKEN FROM THE FACE OF THE CONTROL
 WALL. FL ACC. CODE FIGURE 608.2.1.
  
 5) SHEET DET-4:
 5A) DETAIL # 3 TYPICAL DUCT PENETRATION SHOW EITHER UL
 LISTING OR GYPSUM LISTING FOR PENETRATION THROUGH FIRE
 RATED WALLS. 713.1.1 DUCTS AND AIR TRANSFER OPENINGS.
 PENETRATIONS OF FIRE-RESISTANCE-RATED WALLS BY DUCTS
 THAT ARE NOT PROTECTED WITH DAMPERS SHALL COMPLY WITH
 SECTIONS 713.2 THROUGH 713.3.3. PENETRATIONS OF
 HORIZONTAL ASSEMBLIES NOT PROTECTED WITH A SHAFT AS
 PERMITTED BY EXCEPTION 4 OF SECTION 708.2, AND NOT
 REQUIRED TO BE PROTECTED WITH FIRE DAMPERS BY OTHER
 SECTIONS OF THIS CODE, SHALL COMPLY WITH SECTIONS 713.4
 THROUGH 713.4.2.2. DUCTS AND AIR TRANSFER OPENINGS THAT
 ARE PROTECTED WITH DAMPERS SHALL COMPLY WITH SECTION
 716.
  
 5B) DETAIL # 4 SHOWS IN PRINT THIS IS A MASONRY WALL
 SECTION, WHERE AS IN VIEWING THE SECTION IT IS SOLID AS
 A POURED CONCRETE WALL WOULD BE. PLEASE PROVIDE CODE
 COMPLIANCE WITH :
 FBC-B 713.3.1.1 FIRE-RESISTANCE-RATED ASSEMBLIES.
 PENETRATIONS SHALL BE INSTALLED AS TESTED IN AN
 APPROVED FIRE-RESISTANCE-RATED ASSEMBLY.
  
 FBC-B 713.3.1.2 THROUGH-PENETRATION FIRESTOP SYSTEM.
 THROUGH PENETRATIONS SHALL BE PROTECTED BY AN APPROVED
 PENETRATION FIRESTOP SYSTEM INSTALLED AS TESTED IN
 ACCORDANCE WITH ASTM E 814 OR UL 1479, WITH A MINIMUM
 POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH (2.49 PA)
 OF WATER AND SHALL HAVE AN F RATING OF NOT LESS THAN
 THE REQUIRED FIRE-RESISTANCE RATING OF THE WALL
 PENETRATED.
  
 5C) DETAIL # 8 SHOWS A FIRE EXTINGUISHER BOX WITH THE
 BACK WALL ONLY ONE LAYER OF DRYWALL PLEASE PROVIDE
 COMPLIANCE WITH FBC-B 713.3.2 MEMBRANE PENETRATIONS.
 MEMBRANE PENETRATIONS SHALL COMPLY WITH SECTION
 713.3.1. WHERE WALLS OR PARTITIONS ARE REQUIRED TO HAVE
 A FIRE-RESISTANCE RATING, RECESSED FIXTURES SHALL BE
 INSTALLED SUCH THAT THE REQUIRED FIRE-RESISTANCE WILL
 NOT BE REDUCED. IF AN APPROVED FIRE STOP SYSTEM IS
 PROVIDED PLEASE PROVIDE THE ASSEMBLY.
  
 5D) DETAIL # 12 THE RECEPTION DESKDOES NOT PROVIDE THE
 LENGTH OF THE ACCESSIBLE PORTION OF THE UNIT. SHOW
 COMPLIANCE FOR :
 2010 FBC- ACC. CODE 904.4.1 PARELLEL APPROACH AND
 904.4.2 FORWARD APPROACH.
  
 6) SHEET A7.0 DETAILS 1 & 2 BOTH INDICATE A U L LISTING
 OR EQUAL TO. PLEASE REVIEW 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES. SUCH INFORMATION SHALL BE SPECIFIC,
 AND THE TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE
 OR IN PART, NOR SHALL THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561) 805-6715
 FAX: (561)805-6676
 E-MAIL: [email protected]
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-03-16 Cont ID  
Sent By dhayes Date 2015-03-16 Time 15:21 Rev Time 0.00
Received By dhayes Date 2015-03-16 Time 14:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-03-02 Cont ID  
Sent By pleduc Date 2015-03-02 Time   Rev Time 0.00
Received By pleduc Date 2015-02-25 Time 16:49 Sent To  
Notes
2015-03-02 14:50:56THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 SHEET COV - 1, AS WELL AS ALL OTHER APPLICABLE
 INDICATING SHEETS THROUGHOUT THE SUBMITTAL SET,
 INDICATES INCORRECT FIRE CODE REFERENCES.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
  
 IT DOES NOT APPEAR THAT THIS ERROR NEGATIVELY AFFECTS
 THE PROPOSED PROJECT; HOWEVER, IT SHALL BE INSPECTED IN
 COMPLIANCE WITH THE NOTED FIRE CODE ABOVE.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-06-19 Cont ID  
Sent By jwitmer Date 2015-06-19 Time 14:36 Rev Time 0.00
Received By jwitmer Date 2015-05-05 Time 11:23 Sent To  
Notes
2015-05-06 11:24:20RE-SUBMITTAL SENT TO C34 SHELF FOR REVIEW. JG. .

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-03-20 Cont ID  
Sent By hmoser Date 2015-03-20 Time 13:56 Rev Time 0.00
Received By hmoser Date 2015-02-19 Time 14:51 Sent To  
Notes
2015-02-24 14:51:53SENT TO C4 BIN FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2015-03-20 Cont ID  
Sent By hmoser Date 2015-03-20 Time 13:56 Rev Time 0.00
Received By hmoser Date 2015-03-20 Time 09:55 Sent To  
Notes
***NONE***

Review Stop MEDGAS MEDICAL GAS
Rev No 1 Status P Date 2019-04-26 Cont ID  
Sent By gjohnson Date 2019-04-26 Time 11:50 Rev Time 0.00
Received By gjohnson Date 2019-04-26 Time 11:50 Sent To  
Notes
2019-04-26 11:52:39APPROED UNDER REVISION NUMBER 15120641
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-06-08 Cont ID  
Sent By tklarge Date 2015-06-08 Time 14:35 Rev Time 0.00
Received By tklarge Date 2015-06-08 Time 13:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-03-12 Cont ID  
Sent By tklarge Date 2015-03-12 Time 11:37 Rev Time 0.00
Received By tklarge Date 2015-03-09 Time 12:02 Sent To  
Notes
2015-03-12 11:36:131) SHT. DET-2 , DETAIL # 3 - THE REQUIRED KNEE
 CLEARANCCE SHALL BE 11 INCHES DEEP MINIMUM AT 9 INCHES
 ABOVE THE FINISH FLOOR OR GROUND AND 8 INCHES DEEP
 MINIMUM AT 27 INCHES ABOVE THE FINISH FLOOR OR GROUND.
 FAC SEC.306.3.3.
 2) SHT. DET - 2, DETAIL #2 - FIGURE 608.2.1. - THE 36"
 X 48" CLEAR FLOOR SPACE AT THE SHOWER ENTRANCE IS
 MISALIGNED. THE CLEAR FLOOR SPACE SHALL BEGIN AT THE
 INSIDE OF THE CONTROL WALL. THE PLAN SHOWS THE CLEAR
 FLOOR SPACE STARTING LINE IN THE CENTER OF THE WALL.
 3) SHT. DET-2 - SOME OF HE NUMBERS FOR THE ACCCESSIBLE
 FIGURES DO NOT MATCH THE FIGURE NUMBERS THAT ARE LISTED
 IN THE FL. ACCESSIBILITY CODE IF YOUR INTENT WAS TO
 MATCH THOSE DETAILS. CLARIFY.
 4) SHT. P6.31A - THERE IS NO WATER OR SANITARY RISER
 FOR ROOMS T3200 , T3283 & T3284. CLARIFY.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop Z ZONING
Rev No 1 Status P Date 2015-03-09 Cont ID  
Sent By eschneid Date 2015-03-09 Time 10:47 Rev Time 0.50
Received By eschneid Date 2015-03-04 Time 15:48 Sent To  
Notes
2015-03-09 10:53:51PASSED
  
 THE PARKING LOT STRIPING REQUIRES A SEPARATE PERMIT
 WITH PLANS. PLEASE NOTE THAT DRIVE AISLE DIMENSIONS
 SHALL BE SHOWN AND THE PARKING SPACE DETAIL NEEDS TO
 MEET CITY STANDARDS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.