Plan Review Details - Permit 15020676
Plan Review Stops For Permit 15020676
Review Stop E ELECTRICAL
Rev No 1 Status N Date 2015-04-08 Cont ID  
Sent By dhayes Date 2015-04-08 Time 08:44 Rev Time 0.00
Received By dhayes Date 2015-04-08 Time 08:44 Sent To  
Notes
2015-04-08 08:49:01NO ELECTRICAL PLAN HAS BEEN INCLUDED IN THE SUBMITTAL
 PACKAGE. NO ELECTRICAL REVIEW HAS BEEN PERFORMED AT
 THIS TIME. AN ELECTRICAL PERMIT IS REQUIRED FOR AN
 ELECTRICAL CONTRACTOR TO COMPLETE THE ELECTRICAL
 CONNECTION REQUIRED FOR THE IGNITER IN A GAS TANKLESS
 WATER HEATER.
  
 1) PROVIDE AN ELECTRICAL PERMIT APPLICATION WITH A
 FLOOR PLAN AND A PANEL SCHEDULE INDICATING THE
 ELECTRICAL CIRCUIT AND DISCONNECT REQUIRED FOR THE NEW
 GAS TANKLESS WATER HEATER. NEC 422.31
  
 2) PROVIDE ADDITIONAL INFORMATION ON THE FLOOR PLAN AND
 PANEL SCHEDULE THAT INDICATE THE DEMOLITION OF THE
 ASSUMED PREVIOUSLY EXISTING STORAGE WATER HEATER. WPB
 AMENDMENTS TO THE FBC 107.3.2
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2015-04-08 Cont ID  
Sent By tklarge Date 2015-04-08 Time 04:47 Rev Time 0.00
Received By tklarge Date 2015-04-08 Time 04:14 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2015-03-05 Cont ID  
Sent By tklarge Date 2015-03-05 Time 05:54 Rev Time 0.00
Received By tklarge Date 2015-03-05 Time 05:53 Sent To  
Notes
2015-03-05 05:54:191) SUBMIT MANUF. SPECIFICATIONS /INSTALLATION
 INSTRUCTIONS FOR THE DRISCOPLEX PIPE. PIPE SHALL COMPLY
 W/ 2010 FBCR SEC.G 2414.6.
 2) SUBMIT MANUF. SPECIFICATIONS /INSTALLATION
 INSTRUCTIONS FOR ALL GAS EQUIPMENT PER THE 2010 FBCR
 SEC. GG2404.3.
 3) THE DOCUMENT FROM APS STATES THAT LAUNDRY ROOMS
 SHALL BE A MIN. OF 1400 CU. FT. INDICATE ON THE PLANS
 IF THE DRYER IS LOCATED IN A LAUNDRY ROOM AND IF SO,
 SUPPLY THE CU. FOOTAGE OF THE LAUNDRY ROOM.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-04-08 Cont ID  
Sent By lmarchan Date 2015-04-08 Time 09:38 Rev Time 0.00
Received By lmarchan Date 2015-04-01 Time 08:01 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-03-05 Cont ID  
Sent By tklarge Date 2015-03-05 Time 05:52 Rev Time 0.00
Received By tklarge Date 2015-02-19 Time 16:29 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-04-08 Cont ID  
Sent By tklarge Date 2015-04-08 Time 04:47 Rev Time 0.00
Received By tklarge Date 2015-04-08 Time 04:14 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-03-05 Cont ID  
Sent By tklarge Date 2015-03-05 Time 05:54 Rev Time 0.00
Received By tklarge Date 2015-03-05 Time 05:28 Sent To  
Notes
2015-03-05 05:52:341) SUBMIT MANUF. SPECIFICATIONS /INSTALLATION
 INSTRUCTIONS FOR THE DRISCOPLEX PIPE. PIPE SHALL COMPLY
 W/ 2010 FBCR SEC.G 2414.6.
 2) SUBMIT MANUF. SPECIFICATIONS /INSTALLATION
 INSTRUCTIONS FOR ALL GAS EQUIPMENT PER THE 2010 FBCR
 SEC. GG2404.3.
 3) THE DOCUMENT FROM APS STATES THAT LAUNDRY ROOMS
 SHALL BE A MIN. OF 1400 CU. FT. INDICATE ON THE PLANS
 IF THE DRYER IS LOCATED IN A LAUNDRY ROOM AND IF SO,
 SUPPLY THE CU. FOOTAGE OF THE LAUNDRY ROOM.
 4) SUBMIT A WATER PIPING DIAGRAM FOR THE HOT 7 COLD
 WATER FOR THE TANKLESS WATER HEATER. WPB AMEND. TO 2010
 FBC SEC. 107.3.5.1.3.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  