Plan Review Details - Permit 15020591
Plan Review Stops For Permit 15020591
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-04-21 Cont ID  
Sent By jwitmer Date 2015-04-21 Time 09:03 Rev Time 0.00
Received By jwitmer Date 2015-04-21 Time 09:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-04-01 Cont ID  
Sent By jwitmer Date 2015-04-01 Time 06:35 Rev Time 0.00
Received By jwitmer Date 2015-04-01 Time 06:01 Sent To  
Notes
2015-04-01 06:35:15BUILDING PLAN REVIEW
 PERMIT: 15020591
 ADD: 777 S FLAGLER #3RD FLOOR
 CONT: CITY CONSTRUCTION GROUP
 TEL: (305)448-1118
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: WED. APRIL 01/ 2015
 ACTION: DENIED
  
 1) 2ND REQUEST. PLEASE PROVIDE AN ITEMIZED BREAKDOWN OF
 THE MONIES SPENT AND IN THE ORDER THAT IS REQUIRED BY
 2010 FBC-ACCESSIBILITY CODE 202.4.1. (I) COSTS
 ASSOCIATED WITH PROVIDING AN ACCESSIBLE ENTRANCE AND AN
 ACCESSIBLE ROUTE TO THE ALTERED AREA; (II) COSTS
 ASSOCIATED WITH MAKING RESTROOMS ACCESSIBLE, SUCH AS
 INSTALLING GRAB BARS, ENLARGING TOILET STALLS,
 INSULATING PIPES, OR INSTALLING ACCESSIBLE FAUCET
 CONTROLS; (III) COSTS ASSOCIATED WITH PROVIDING
 ACCESSIBLE TELEPHONES, SUCH AS RELOCATING THE TELEPHONE
 TO AN ACCESSIBLE HEIGHT, INSTALLING AMPLIFICATION
 DEVICES, OR INSTALLING A TEXT TELEPHONE (TTY); (IV)
 COSTS ASSOCIATED WITH RELOCATING AN INACCESSIBLE
 DRINKING FOUNTAIN.
  
 THE 20% DISPROPORTIONANTE COST CAN BE WORK THAT WAS
 INCLUDED IN THE CONTRACT VALUE SHOWING THE TENANT IS
 TRYING TO MEET A CODE COMPLIANCY FOR ACCESSIBLITY OVER
 A SERIES OF ALTERATIONS. THE LETTER FROM CITY
 CONSTRUCTION LIST THE REPLACEMENT OF NON-COMPLIANT
 LAVATORY VANITIES, PLEASE NOTE THIS PERMIT IS FOR THE
 TENANT SPACE ONLY NOT THE COMMON AREAS OR RESTROOMS.
  
 NOTE THAT CLAIMS CAN STILL BE MADE AGAINST THE TENANT
 UNDER THE ADA FEDERAL GUIDLINES FOR ACCESSIBILITY.
  
 SHEET LS 1.03 PLEASE SHOW COMPLIANCE WITH 2010
 FBC-ACCESSIBILITY SECTION 404.2.4 MANEUVERING
 CLEARANCES AT DOORS FOR DOOR , 3019, 3020,3032, 3033,
 3042, 3043, 3087 & 3095. SEE FL ACCESS. CODE TABLE
 404.2.4.1 & FIGURE 404.2.1(A), NOTE THE
 DISPROPROTIONATE COST OF UP TO $174,000 IS TO BE SPENT
 IN ACCESSIBLE UPGRADES. FL ACCESS CODE 202.4.1.
  
 2010 FBC-ACCESSIBILITY 202.4.1 DISPROPORTIONATE COST.
 ALTERATIONS MADE TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL TO THE ALTERED AREA WILL BE DEEMED
 DISPROPORTIONATE TO THE OVERALL ALTERATION WHEN THE
 COST EXCEEDS 20% OF THE COST OF THE ALTERATION TO THE
 PRIMARY FUNCTION AREA. COSTS THAT MAY BE COUNTED AS
 EXPENDITURES REQUIRED TO PROVIDE AN ACCESSIBLE PATH OF
 TRAVEL MAY INCLUDE: (I) COSTS ASSOCIATED WITH PROVIDING
 AN ACCESSIBLE ENTRANCE AND AN ACCESSIBLE ROUTE TO THE
 ALTERED AREA; (II) COSTS ASSOCIATED WITH MAKING
 RESTROOMS ACCESSIBLE, SUCH AS INSTALLING GRAB BARS,
 ENLARGING TOILET STALLS, INSULATING PIPES, OR
 INSTALLING ACCESSIBLE FAUCET CONTROLS; (III) COSTS
 ASSOCIATED WITH PROVIDING ACCESSIBLE TELEPHONES, SUCH
 AS RELOCATING THE TELEPHONE TO AN ACCESSIBLE HEIGHT,
 INSTALLING AMPLIFICATION DEVICES, OR INSTALLING A TEXT
 TELEPHONE (TTY); (IV) COSTS ASSOCIATED WITH RELOCATING
 AN INACCESSIBLE DRINKING FOUNTAIN.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-02-26 Cont ID  
Sent By jwitmer Date 2015-02-26 Time 08:22 Rev Time 0.00
Received By jwitmer Date 2015-02-25 Time 16:46 Sent To  
Notes
2015-02-26 08:22:28BUILDING PLAN REVIEW
 PERMIT: 15020591
 ADD: 777 S FLAGLER #3RD FLOOR
 CONT: CITY CONSTRUCTION GROUP
 TEL: (305)448-1118
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 IMPORTANT NOTICE: EFFECTIVE MAY 11, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE
  
  
 1ST REVIEW
 DATE: THURS. FEB. 26/ 2015
 ACTION: DENIED
  
 1) SHEET LS 1.03 PLEASE SHOW COMPLIANCE WITH 2010
 FBC-ACCESSIBILITY SECTION 404.2.4 MANEUVERING
 CLEARANCES AT DOORS FOR DOOR , 3019, 3020,3032, 3033,
 3042, 3043, 3087 & 3095. SEE FL ACCESS. CODE TABLE
 404.2.4.1 & FIGURE 404.2.1(A), NOTE THE
 DISPROPROTIONATE COST OF UP TO $174,000 IS TO BE SPENT
 IN ACCESSIBLE UPGRADES. FL ACCESS CODE 202.4.1.
  
 2) SHEET LS 1.03 SHOWS A TOTAL SQ. FOOTAGE OF 19,774
 SQ. FT. TEN % OF THE FLOOR AREA WOULD BE 1,977 SQ. FT.
 THE ASSEMBLY OCCUPANCY SHOWS 2001 SQ. FEET WITHOUT THE
 BREAK ROOM BEING INCLUDED UPDATE BREAK ROOM TO A
 ASSEMBLY USAGE. THIS PUTS THE ASSEMBLY PORTION OF
 OCCUPANCY FROM BEING AN ACCESSORY OCCUPANCY TO A MIXED
 OCCUPANCY. 2010 FBC-B 508.2.1 THE ASSEMBLY USE AREAS
 MAY BE UNDER 750 SQ FT IN VARIOUS AERAS BUT WHEN
 TOTALED TOGETHER THEY EXCEED THE 10 % OF THE FLOOR
 PLATE CREATING A MIXED OCCUPANCY. FBC-B TABLE 508.4
 WILL REQUIRE A 1 HR. OCCUPANCY SEPARATION WAL AND TABLE
 7L5.4 OPENING PROTECTIVES WILL ALSO REQUIRE RATED
 DOORS.
  
 3) SHEET A6.01 SHOWS VARIOUS GLAS WALL DETAILS 7, 8 & 9
 THEY REFERANCE DETAILS ON SHEET A7.01 DETAIL# 3 AND
 A7.02 DETAIL # 8 ALL REFERANCE SEE THE GLASS SCHEDULE
 BUT NO SCHEDULE COULD BE FOUND. PLEASE PROVIDE
 COMPLIANCE WITH 2010 FBC-B 2406.4 HAZARDOUS LOCATIONS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-04-07 Cont ID  
Sent By rlecky Date 2015-04-07 Time 12:46 Rev Time 0.00
Received By rlecky Date 2015-04-07 Time 11:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-02-24 Cont ID  
Sent By rlecky Date 2015-02-24 Time 10:39 Rev Time 0.00
Received By rlecky Date 2015-02-24 Time 10:31 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-04-03 Cont ID  
Sent By pleduc Date 2015-04-03 Time   Rev Time 0.00
Received By pleduc Date 2015-04-03 Time 13:26 Sent To E
Notes
2015-03-31 17:37:05NEW DRAWINGS SUBMITTED. JG.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-02-19 Cont ID  
Sent By pleduc Date 2015-02-19 Time   Rev Time 0.00
Received By pleduc Date 2015-02-19 Time 11:53 Sent To  
Notes
2015-02-19 16:55:05THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 ON SHEET FS 0.1 THERE ARE REFERENCES TO INCORRECT FIRE
 CODE EDITIONS. THESE DO NOT APPEAR TO NEGATIVELY AFFECT
 THE PROJECT.
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
  
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2010 EDITION.
  
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2010 EDITION.
  
 ADDITIONALLY:
  
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2009 EDITION.
  
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2010 EDITION.
  
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION.
  
 THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE
 SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE
 CONSTRUCTION PERIOD.
  
 ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER
 SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND
 BY CERTIFIED LIFE SAFETY CONTRACTORS.
  
 ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS,
 SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE
 WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL
 AND COMPLETE PROTECTION IS RETURNED.
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-04-21 Cont ID  
Sent By jwitmer Date 2015-04-21 Time 09:04 Rev Time 0.00
Received By jwitmer Date 2015-04-20 Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-04-07 Cont ID  
Sent By rlecky Date 2015-04-07 Time 12:46 Rev Time 0.00
Received By rlecky Date 2015-03-31 Time 17:36 Sent To  
Notes
2015-03-31 17:36:40RE-SUBMITTAL SENT TO JIM WITMER FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-03-05 Cont ID  
Sent By tklarge Date 2015-03-05 Time 14:45 Rev Time 0.00
Received By tklarge Date 2015-02-18 Time 16:21 Sent To  
Notes
2015-02-18 16:21:54B28

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2015-03-02 Cont ID  
Sent By hmoser Date 2015-03-02 Time 14:21 Rev Time 0.00
Received By hmoser Date 2015-03-02 Time 12:08 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-03-05 Cont ID  
Sent By tklarge Date 2015-03-05 Time 14:42 Rev Time 0.00
Received By tklarge Date 2015-03-04 Time 13:49 Sent To  
Notes
2015-03-05 14:45:03***PROVISO**
 1) MANUFACTURER'S SPECS/INSTALLATION INSTRUCTIONS FOR
 TANKLESS WATER HEATERS SHALL BE ONSITE FOR INSPECTION.
 20 SODA DISPENSER, ICE MAKER & COFFEE MACHINES SHALL BE
 EQUIPPED WITH BACKFLOW PREVENTERS. 2010 FPC
 SEC.608.16.1, 608.16.10.