Plan Review Details - Permit 15020572
Plan Review Stops For Permit 15020572
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-03-07 Cont ID  
Sent By dhayes Date 2015-03-07 Time 12:00 Rev Time 0.00
Received By dhayes Date 2015-03-07 Time 11:58 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-02-19 Cont ID  
Sent By   Date 2015-02-19 Time 09:43 Rev Time 0.00
Received By dhayes Date 2015-02-19 Time 08:06 Sent To FIRE
Notes
2015-02-19 09:42:592/19/2015
 PROJECT: BRAMAN AUDI - CCTV/PHONE-DATA/ACCESS CONTROL
 PERMIT#: 15020572
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) THE PRIMARY PERMIT NUMBER INDICATED ON THE
 APPLICATION 14070892 IS ACTUALLY A PLUMBING SUB
 PERMIT.. THIS IS NOT A SUB PERMIT APPLICATION SO A
 PRIMARY PERMIT NUMBER IS NOT REQUIRED.
  
 2) WPB AMENDMENTS TO FBC 107.2.1
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
 PLEASE PROVIDE A NEW SET OF DESIGN DOCUMENTS THAT
 CLEARLY AND ACCURATELY DEPICT THE COMPLETE SCOPE OF
 WORK AS DEFINED ON THE APPLICATION. I WOULD SUGGEST
 THAT YOU SUBMIT A PLAN THAT INLUDES ONLY YOUR SPECIFIC
 DISIPLINE SO AS NOT TO BE CONFLICTING WITH THE BALANCE
 OF WORK SHOWN ON THE PLANS SUBMITTED WHICH A COPY OF A
 SITE POWER PLAN DESIGNED BY FSMY ARCHITECTS AND
 PLANNERS AND KAMM CONSULTING. THERE ARE ADDITIONAL
 SHEETS INCLUDED THAT ARE NOT NEEDED AND ONLY HELP TO
 CONFUSE THE ISSUE. PLEASE ONLY SUBMIT THE RELEVENT
 INFORMATION.
  
 3) FBC, WPB AMENDMENTS 107.2.1
 THE DESIGN DOCUMENTS SUBMITTED WERE ISSUED FOR PERMIT
 AND CONSTRUCTION BY FSMY ARCHITECTS AND PLANNERS AND
 KAMM CONSULTING. THE PLANS SUBMITTED HAVE NOT BEEN
 SIGNED OR SEALED.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN.
 FL SS 471, 668.001-668.006
 ALL FINAL DRAWINGS, SPECIFICATIONS, PLANS, REPORTS, OR
 DOCUMENTS PREPARED OR ISSUED BY THE LICENSEE AND BEING
 FILED FOR PUBLIC RECORD AND ALL FINAL DOCUMENTS
 PROVIDED TO THE OWNER OR THE OWNER?S REPRESENTATIVE
 SHALL BE SIGNED BY THE LICENSEE, DATED, AND SEALED WITH
 SAID SEAL.
  
 4) FBC WPB AMENDMENTS. SECTION 109.3
 FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, INTERIOR
 FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN
 FEES, MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING
 ONLY LAND VALUE.
 THE VALUE OF THE SCOPE OF WORK NEEDS TO BE CLARIFIED.
 THE VALUE INDICATED ON THE PERMIT APPLICATION IS ONLY
 FOR THE EQUIPMENT TO BE PROVIDED. THE PROPOSAL
 SUBMITTED IS FOR EQUIPMENT TO BE SUPPLIED BY A VENDOR
 TO BRAMAN AUDI. THE VALUE OF THE SCOPE OF WORK SHALL
 INCLUDE THE LABOR, PARTS, EQUIPMENT, O/H AND PROFIT FOR
 THE COMPLETE INSTALLATION. AS PRESCRIBED IN SECTION
 109.3 OF THE WPB AMENDMENTS TO THE FBC. IF A PORTION OF
 THE SCOPE OF WORK INVOLVED WAS INCLUDED ON THE MASTER
 PERMIT 14040379 PLEASE BREAK OUT THAT PORTION OF THE
 VALUE ON YOUR APPLICATION AND MAKE APPROPRIATE
 ADJUSTMENT TO THE VALUE INDICATED ON THE APPLICATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  
2015-02-19 08:01:07 
  
2015-02-18 17:55:13TO DHAYES TO EXPEDITE

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-02-24 Cont ID  
Sent By scaldero Date 2015-02-24 Time 13:50 Rev Time 0.00
Received By scaldero Date 2015-02-24 Time 13:50 Sent To E
Notes
2015-02-24 13:53:27PERMIT #15020572
  
 COMMENTS: PERMIT DESCRIPITON INDICATED ACCESS CONTROL,
 HOWEVER NONE WAS FOUND ON THE SUBMITTED PLANS.
 PLAN APPROVED BASED ON POSSIBLE ERROR IN PERMIT
 DESCRIPTION AND THIS WAS ONLY A LOW-VOLTAGE PERMIT.
 IF ACCESS CONTROL IS TO BE USED, IT WILL BE VERFIIED
 AND APPROVED IN THE FIELD.
  
 SUE ELLEN CALDERON
 INSPECTOR II / INVESTIGATOR
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-03-07 Cont ID  
Sent By dhayes Date 2015-03-07 Time 12:00 Rev Time 0.00
Received By dhayes Date 2015-03-06 Time 18:35 Sent To  
Notes
2015-03-06 18:35:35RE-SUBMITTAL SENT TO DAVID HAYES FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-03-07 Cont ID  
Sent By dhayes Date 2015-02-19 Time 12:00 Rev Time 0.00
Received By dhayes Date 2015-02-17 Time 08:06 Sent To E
Notes
***NONE***