Plan Review Details - Permit 15020567
Plan Review Stops For Permit 15020567
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-08-04 Cont ID  
Sent By jwitmer Date 2015-08-04 Time 08:43 Rev Time 0.00
Received By jwitmer Date 2015-08-04 Time 08:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-05-26 Cont ID  
Sent By jwitmer Date 2015-05-29 Time 10:30 Rev Time 0.00
Received By jwitmer Date 2015-05-28 Time 07:45 Sent To  
Notes
2015-05-26 10:30:19BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15020567
 ADD: 901 45TH ST ST. MARYS HOSPITAL
 CONT: WESTBROOKE
 TEL: (561)395-4126
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. MAY 26/2015
 ACTION: BUILDING PROVISO
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) SHEET A1.0 OFFICE CL 107 HAD THE 2 DOORS IN SERIES,
 THE NEW DESIGN NOW HAS THE DOOR THAT LEADS INTO THE
 CORRIDOR IS NOW IN CONFLICT WITH DOOR # CL105A 21.02N.
 THE OFFICE DOOR CL 107 AT THE CORRIDOR DOES NOT HAVE
 THE REQUIRED 60 INCHES CLEAR FLOOR SPACE AS REQUIRED BY
 THE 2010 FBC-ACCESSIBILITY SEE FIGURE 404.2.4.1(A). THE
 DOUBLE ACTING DOOR ON THE FAR SIDE OF THE CORRIDOR WILL
 HIT A WHEELCHAIR WITH THIS TYPE OF CONFIGURATION.
  
 2) SHEET A2.0. THE CUSTOM CURB FOR THE EXHAUST FANS AND
 AIR HANDLER UNITS WILL REQUIRE THE ENGINEERED SHOP
 DRAWINGS AND CALCULATIONS AS WELL AS THE ATTACHMENT
 FROM THE EXHAUST FAN & AIR HANDLER UNIT, AND THE CUSTOM
 CURB TO THE STRUCTURAL ROOF SYSTEM. THE DELEGATE
 ENGINEERS DESIGN MUST 1ST BE SUBMITTED TO THE ENGINEER
 OF RECORD FOR REVIEW AN APPROVAL BEFORE SUBMISSION TO
 THE BUILDING DEPARTMENT. FL 61G-15-30.006 (3) THE
 DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
 2010 FBC-B 1609.6.4.4.1 COMPONENTS & CLADDING.
 2010 FBC-B 1609.8 ROOFTOP STRUCTURES & EQUIPMENT.
 2010 FBC-M 301.12 WIND RESISTANCE.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-03-05 Cont ID  
Sent By jwitmer Date 2015-03-05 Time 12:01 Rev Time  
Received By jwitmer Date 2015-03-05 Time 07:46 Sent To  
Notes
2015-03-05 12:01:01BUILDING PLAN REVIEW
 W. P. B. PERMIT: 15020567
 ADD: 901 45TH ST ST. MARYS HOSPITAL
 CONT: WESTBROOKE
 TEL: (561)395-4126
 E-MAIL: [email protected]
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE
  
 1ST REVIEW
 DATE: THURS. MARCH 5/2015
 ACTION: DENIED
  
 1) SHEET A1.0 OFFICE CL 107 HAS (2) DOORS IN SERIES,
 CL107 & CL107A WITH LESS THAN 4 FT IN BETWEEN. PLEASE
 REVIEW 2010 FBC ACCESS. CODE 404.2.6 DOORS IN SERIES .
 THE DISTANCE BETWEEN TWO HINGED OR PIVOTED DOORS IN
 SERIES AND GATES IN SERIES SHALL BE 48 INCHES (1220 MM)
 MINIMUM PLUS THE WIDTH OF DOORS OR GATES SWINGING INTO
 THE SPACE.
  
 2) SHEET S-1 NOTE FOR ALL ROOF TOP UNITS INDICATES ALL
 RTUS TO BE SUPPORTED BY A 36 INCH HIGH CURB. NO PRODUCT
 APPROVALS WERE SUBMITTED FOR ROOF TOP CURBS. NOTE IF NO
 PRODUCT APPROVALS CAN BE FOUND FOR A 36 INCH HIGH CURB
 THEN THEY WILL NEED TO BE ENGINEERED SYSTEM. NOTE THIS
 IS A RISK CATEGORY III BUILDING. 1609.8 ROOFTOP
 STRUCTURES AND EQUIPMENT.
  
 3) SHEET S1 AND S2 SHOW NEW EXHAUST FANS AND ROOF
 CURBING, NONE OF THE STRUCTURAL SHEETS PROVIDE THE VASD
 PRESSURES NOR THE ROOF ZONE LOCATIONS 1,2 OR 3 ROOF
 ZONES. THIS IS NEEDED TO EVALUATE THE PRODUCT APPROVALS
 FOR CODE COMPLIANCE FOR PRESSURES. FBC-B1609.
 COMPONENTS AND CLADDING SECTION.
  
 4) MISSING ROOF CURBS FOR EXHAUST FANS, 2010 FBC-B
 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS
 & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31) (D) ROOFING PRODUCTS AND ASSEMBLIES
  
 5) THE SUBMITTED ROOFING NOA 13-0529.07 JOHN MANVILLE
 BUILT -UP ROOF SYSTEMS OVER CONCRETE DECK. PLEASE
 IDENTIY WHICH SUB-SYSTEM IS TO BE INSTALLED AND
 ASSOCIATED PRESSURES. PLEASE NOTE IF LIMITATION # 7,
 ENHANCED FASTENING BY A FL. ENGINEER IS REQUIRED.
  
 6) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561) 805-6715
 FAX: (561)805-6676
 E-MAIL: [email protected]
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-05-05 Cont ID  
Sent By rlecky Date 2015-05-05 Time 10:47 Rev Time 0.00
Received By rlecky Date 2015-05-04 Time 14:22 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2015-02-24 Cont ID  
Sent By rlecky Date 2015-02-24 Time 13:19 Rev Time 0.00
Received By rlecky Date 2015-02-24 Time 10:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2015-05-05 Cont ID  
Sent By pleduc Date 2015-05-05 Time   Rev Time 0.00
Received By pleduc Date 2015-05-05 Time 16:48 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2015-02-24 Cont ID  
Sent By pleduc Date 2015-02-24 Time   Rev Time 0.00
Received By pleduc Date 2015-02-19 Time 11:36 Sent To  
Notes
2015-02-24 13:29:44THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 ALL TEMPORARY EXITS SHALL BE CLEARLY MARKED AND
 ILLUMINATED.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-08-04 Cont ID  
Sent By jwitmer Date 2015-08-04 Time 08:43 Rev Time 0.00
Received By jwitmer Date 2015-06-26 Time 15:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-06-12 Cont ID  
Sent By skennedy Date 2015-06-12 Time 10:47 Rev Time 0.00
Received By skennedy Date 2015-04-23 Time 12:58 Sent To  
Notes
2015-04-23 12:58:30C30
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-03-20 Cont ID  
Sent By hmoser Date 2015-03-20 Time 09:36 Rev Time 0.00
Received By hmoser Date 2015-02-18 Time 16:51 Sent To  
Notes
2015-02-18 16:51:41C29

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-07-09 Cont ID  
Sent By ccole Date 2015-07-09 Time 10:09 Rev Time 0.00
Received By ccole Date 2015-07-09 Time 10:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-05-29 Cont ID  
Sent By ccole Date 2015-05-29 Time 07:46 Rev Time 0.00
Received By ccole Date 2015-05-28 Time 07:46 Sent To  
Notes
2015-05-29 07:42:03MECHANICAL APPROVED WITH EXCEPTION.
 REVISION REQUIRED FOR MISSING FIRE DAMPERS AT THE
 FOLLOWING LOCATIONS:
 1) SHEET M1.5- EXHAUST DUCT PENETRATING
 CORRIDOR/HISTOLOGY WALL (SEE NOTE 22)
 2) M1.6- EXHAUST INLET AT BREAKROOM/JANITOR CLOSET WALL
 (SEE NOTE 5)
 3) M1.7- THE TWO RATED ENCLOSURES AT LAB STORAGE SHOW
 DAMPERS ON ONLY ONE SIDE OF EACH ENCLOSURE. DAMPERS
 REQUIRED ON ALL FOUR WALLS BEING PENETRATED.
  
 PRODUCT DATA SHEETS TO BE ONSITE FOR FIRE DAMPERS,
 FIRE/SMOKE DAMPERS, DUCT SMOKE DETECTORS, AHU'S, REHEAT
 COILS, EXHAUST FANS, HEAT EXHANGE COMPONENTS, CHILLER
 PIPING AND VALVES, HYDRONIC PUMPS, AIR SCRUBBERS AND
 HEPA FILTERS.
 SMOKE TEST, AND TEST AND BALANCE REPORT REQUIRED FOR
 FINAL APPROVAL.
  
 CHRISTOPHER COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-03-20 Cont ID  
Sent By hmoser Date 2015-03-20 Time 09:36 Rev Time 0.00
Received By hmoser Date 2015-03-19 Time 12:57 Sent To  
Notes
2015-03-20 09:36:30PLAN DENIED
 1) MISSING 3 FIRE DAMPERS ON EXHAUST FAN 103
 16 X 8 DUCT AND 8 X 8 DUCT. PAGE M1.7 SHOWS
 A 2 HR WALL AND PAGE M1.6 SHOWS NO RATING
 AT ALL. PLEASE CLARIFY. SECTION 607.5.2 FIRE
 BARRIERS 2010 FBC (M)
 2) EXHAUST DUST IN BLOOD BANK ROOM PAGE
 M1.7 8 X 8 DUCT WHERE IS THE DUCT GOING AND
 WHAT EXHAUST FAN IS IT GOING TO. 107 FBC 2010
 3) WALK IN COOLERS REQUIRE SEPARATE APPLICATION
 PLAN AND PERMIT.
  
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 567-805-6676

Review Stop P PLUMBING
Rev No 3 Status P Date 2015-07-28 Cont ID  
Sent By tklarge Date 2015-07-21 Time 11:50 Rev Time 0.00
Received By tklarge Date 2015-07-21 Time 09:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2015-05-09 Cont ID  
Sent By tklarge Date 2015-05-09 Time 05:05 Rev Time 0.00
Received By tklarge Date 2015-05-09 Time 03:56 Sent To  
Notes
2015-05-09 04:20:421)THE MANNER IN WHICH THE RISERS HAVE BEEN LABELED TO
 ADDRESS MY REVIEW COMMENT MAKES IT EVEN MORE DIFFICULT
 TO LOCATE THE RISERS AND CONFIRM COMPLIANCE WITH THE
 PLUMBING CODE. PLEASE CALL TO ARRANGE AN APPOINTMENT TO
 REVIEW AND DISCUSS A METHOD OF IDENTIFYING THE WATER
 AND SANITARY DIAGRAMS IN ORDER TO GET THE PLUMBING
 APPROVED.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-03-16 Cont ID  
Sent By tklarge Date 2015-03-16 Time 05:41 Rev Time 0.00
Received By tklarge Date 2015-03-14 Time 08:25 Sent To  
Notes
2015-03-14 11:40:341) SUBMIT SPECIFICATIONS FOR THE NEUTRALIZATION
 TANKS/SYSTEM. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 2) SHT. P2.2 - PLEASE LABEL ALL THE RISERS TO CORRELATE
 WITH SHT.P5.1. AS DESIGNED NOW, IT IS EXTREMELY
 DIFFICULT TO LOCATE THE RISER SECTIONS ON SHT. P2.2.
 THE RISERS DO NOT APPEAR TO CORRELATE WITH EACH
 OTHER.WPB AMEND. TO 2010 FBC SEC. 107.2.1.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved