| 2015-06-23 11:06:37 | 705 NORTH OLIVE AVENUE |
| | TRACKING #15060302 |
| | MASTER #14030096 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | *****PROVISO - SUBMIT REVISION ADDRESSING REVIEW |
| | COMMENTS***** |
| | |
| | GENERAL: COULD NOT LOCATE ANY VISIBLE SIGNALS WITHIN |
| | THE DWELLING UNITS. VISIBLE SIGNALS SHALL BE INSTALLED |
| | IN UNITS DESIGNED FOR THE HEARING IMPAIRED. |
| | |
| | GENERAL: EXPLAIN WHY THERE ARE MANUAL PULL STATIONS |
| | THROUGHOUT THE1ST FLOOR BUT NOT ON ANY OTHER LEVEL. |
| | |
| | GENERAL: VOICE EVACUATION - PROVIDE A PRE-RECORDED FIRE |
| | ALARM EVACUATION MESSAGE NOTIFYING OCCUPANTS AN |
| | EMERGENCY HAS BEEN REPORTED IN THE BUILDING, LOCATE THE |
| | NEAREST EXIT, AND EXIT THE BUILDING IMMEDIATELY. DO NOT |
| | USE THE ELEVATOR. |
| | |
| | GENERAL: PROVIDE FIRE INSPECTOR WITH A COPY OF THE |
| | RECORD OF COMPLETION DOCUMENTS PER NFPA 72. |
| | |
| | SHEET FA-101: PARKING GARAGE SEVERELY LACKING VISUAL |
| | NOTIFICATION DEVICES; TYPICAL ALL LEVELS. PROVIDE |
| | ADEQUATE NOTIFICATION PER NFPA 72. |
| | |
| | SHEET FA-102: NO NOTIFICATION APPLIANCE PROVIDED IN |
| | TRASH ROOM ADJACENT TO STAIR #3. |
| | |
| | SHEET FA-102: THERE APPEARS TO BE 6 TOILET ROOMS IN THE |
| | FITNESS AREA THAT HAVE FULL HEIGHT WALLS AND NO |
| | NOTIFICATION APPLIANCES WITHIN EACH UNIT. |
| | |
| | SHEET FA-102: MAIL ROOM APPEARS TO HAVE A FULL HEIGHT |
| | WALL OBSTRUCTING THE APPLIANCE STROBE. |
| | |
| | SHEET FA-103: NO NOTIFICATION APPLIANCE PROVIDED IN |
| | STORAGE ROOM #248. |
| | |
| | SHEET FA-104: AMENITIES AREA IS UTILIZING CEILING |
| | MOUNTED NOTIFICATION DEVICES. THIS AREA IS SURROUNDED |
| | BY GLAZING (VAST AMOUNTS OF NATURAL LIGHTING) THAT MAY |
| | REQUIRE ADDITIONAL VISUAL NOTIFICATION DEVICE TO COMPLY |
| | WITH NFPA 72. |
| | |
| | SHEET FA-104: NO NOTIFICATION APPLIANCE PROVIDED IN |
| | STORAGE ROOM #245. |
| | |
| | SHEET FA-104: NO NOTIFICATION APPLIANCE PROVIDED IN |
| | STORAGE ROOMS #242 AND #243; TYPICAL ALL LEVELS ABOVE. |
| | |
| | SHEET FA-117: SMOKE DETECTORS SHALL NOT BE INSTALLED IN |
| | UNSPRINKLERED ELEVATOR HOISTWAYS UNLESS THEY ARE |
| | INSTALLED TO ACTIVATE THE ELEVATOR HOISTWAY SMOKE |
| | RELIEF EQUIPMENT (NFPA 72 SECTION 21.3.6). |
| | |
| | SHEET FA-118: SMOKE DETECTORS SHALL NOT BE INSTALLED IN |
| | UNSPRINKLERED ELEVATOR HOISTWAYS UNLESS THEY ARE |
| | INSTALLED TO ACTIVATE THE ELEVATOR HOISTWAY SMOKE |
| | RELIEF EQUIPMENT (NFPA 72 SECTION 21.3.6). |
| | |
| | CENTRAL STATION SERVICE: THE PRIME CONTRACTOR SHALL |
| | CONSPICUOUSLY INDICATE THAT THE FIRE ALARM SYSTEM |
| | PROVIDING SERVICE AT A PROTECTED PREMISES COMPLIES WITH |
| | ALL THE REQUIREMENTS OF THIS CODE THROUGH THE USE OF A |
| | SYSTEMATIC FOLLOW-UP PROGRAM UNDER THE CONTROL OF THE |
| | ORGANIZATION THAT HAS LISTED THE PRIME CONTRACTOR. |
| | DOCUMENTATION INDICATING CODE COMPLIANCE OF THE |
| | FIRE ALARM SYSTEM SHALL BE ISSUED BY THE ORGANIZATION |
| | THAT HAS LISTED THE PRIME CONTRACTOR. THE DOCUMENTATION |
| | SHALL INCLUDE, AT A MINIMUM, THE FOLLOWING INFORMATION: |
| | (1) NAME OF THE PRIME CONTRACTOR INVOLVED WITH THE |
| | ONGOING CODE COMPLIANCE OF THE CENTRAL STATION SERVICE |
| | (2) FULL DESCRIPTION OF THE FIRE ALARM SYSTEM AS |
| | INSTALLED (3) ISSUE AND EXPIRATION DATES OF THE |
| | DOCUMENTATION |
| | (4) NAME, ADDRESS, AND CONTACT INFORMATION OF THE |
| | ORGANIZATION ISSUING THE DOCUMENT |
| | (5) IDENTIFICATION OF THE AUTHORITY(IES) HAVING |
| | JURISDICTION FOR THE CENTRAL STATION SERVICE |
| | INSTALLATION |
| | THE DOCUMENTATION SHALL BE PHYSICALLY POSTED WITHIN 3 |
| | FEET OF THE FIRE ALARM CONTROL UNIT, AND COPIES OF THE |
| | DOCUMENTATION SHALL BE MADE AVAILABLE TO THE AHJ. |
| | |
| | NOTE: FIRE ALARM ACCEPTANCE TESTING WILL REQUIRE |
| | 24-HOURS ON STANDBY FOLLOWED BY 5-MINUTES OF ALARM AND |
| | 15-MINUTES OF ALARM FOR THE VOICE EVACUATION SYSTEM. |
| | |
| | WESLEY JOLIN |
| | ASSISTANT FIRE MARSHAL |
| | FIRE INVESTIGATOR & INSPECTOR |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | (561) 805-6730 |
| | |
| | |
| | |
| | CONTRACTOR'S FIRE ALARM DRAWINGS ARE AWAITING REVIEW |
| | UNTIL THE ENGINEER OF RECORD REVISES THE CONSTRUCTION |
| | DRAWINGS AND INDICATES THE CHANGES MADE FROM THE |
| | ORIGINAL DESIGN. THE EOR DRAWINGS (REVISED PERMIT |
| | #15060302) WERE SUBMITTED, REVIEWED AND FAILED ON |
| | 06/11/15 DUE TO THE COMMENTS SHOWN BELOW: |
| | |
| | NO ADDRESS INDICATED ON THE PLANS OR IN THE TITLEBLOCK. |
| | |
| | NO REVISION CLOUDS, DELTAS OR DETAILED SUMMARY PROVIDED |
| | INDICATED WHAT HAS CHANGED ON THE PLANS. |
| | |
| | PLANS WERE ORIGINALLY SUBMITTED DIGITALLY; REVISION WAS |
| | SUBMITTED AS HARD COPY. PLEASE RESUBMIT THE REVISED |
| | PLANS DIGITALLY. |
| | |
| | |