| 2015-03-03 09:13:44 | BUILDING PLAN REVIEW |
| | MASTER: 14040379 |
| | PERMIT: 15020521 |
| | ADD: 2101 OKEECHOBEE BLVD |
| | CONT: FLORES CONSTRUCTION |
| | TEL: (813) 323-7895 |
| | E-MAIL:[email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | IMPORTANT NOTICE: EFFECTIVE MARCH 30, 2015 |
| | ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED |
| | ELECTRONICALLY |
| | UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS |
| | SUBMISSION OPTIONS ARE AS FOLLOWS: |
| | 1 UPLOAD VIA THE PROJECT DOX PORTAL WITH DIGITAL |
| | SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE |
| | THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| | 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL |
| | SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED |
| | NAMING CONVENTION FOR EACH DOCUMENT |
| | 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER |
| | DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE |
| | REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| | 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT |
| | TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS |
| | ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES |
| | AVAILABLE |
| | |
| | 1ST REVIEW |
| | DATE: MARCH 03/ 2015 |
| | ACTION: DENIED |
| | |
| | 1) A LETTER FROM THE QUALIFIER OF BOTH THE PRIME/ |
| | MASTER CONTRACTOR (HEDRICK BROTHERS) AND MEZZANINE |
| | CONTRACTOR MUST BE PROVIDED BEFORE THE MEZZINE PERMIT |
| | CAN BE ISSUED, IF THE MEZZANINE CONTRACTOR WISHES TO |
| | START WORK BEFORE THE SHELL / MASTER/ PRIME PERMIT WORK |
| | HAS RECEIVED A CERTIFICATE OFOCCUPANCY, AGREEING THEY |
| | WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE |
| | DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER. |
| | PLEASE PROVIDE THE PERMIT NUMBER, ADDRESS WITH SUITE |
| | NUMBER WITHIN THE DOCUMENT. |
| | |
| | 2) THE SUBMITTED MEZININE PLANS WERE NOT REVIEWED BY |
| | THE DESIGNER OF RECORD. FL 61G1-23.015 (2) THE |
| | ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| | ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC... |
| | |
| | 3A) THE MEZZININE PLANS DO NOT SHOW ANY GUARD RAIL |
| | SYSTEM AROUND THE OPEN AREA AT THE PART DELIVERY AREA |
| | OR THE VLM. 2010 FBC-B 1013.1 WHERE REQUIRED. |
| | GUARDS SHALL BE LOCATED ALONG OPEN-SIDED WALKING |
| | SURFACES, INCLUDING MEZZANINES, EQUIPMENT PLATFORMS, |
| | STAIRS, RAMPS AND LANDINGS THAT ARE LOCATED MORE THAN |
| | 30 INCHES (762 MM) MEASURED VERTICALLY TO THE FLOOR. |
| | |
| | 3B) SHOW COMPLIANCE WITH; 1013.3 OPENING LIMITATIONS. |
| | EXCEPTIONS: 4. IN AREAS THAT ARE NOT OPEN TO THE PUBLIC |
| | WITHIN OCCUPANCIES IN GROUP I-3, F, H OR S, AND FOR |
| | ALTERNATING TREAD DEVICES AND SHIP LADDERS, GUARDS |
| | SHALL NOT HAVE OPENINGS WHICH ALLOW PASSAGE OF A SPHERE |
| | 21 INCHES (533 MM) IN DIAMETER. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |