Plan Review Details - Permit 15020495
Plan Review Stops For Permit 15020495
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2015-10-05 Cont ID  
Sent By rmcdouga Date 2015-10-05 Time 19:17 Rev Time 0.00
Received By rmcdouga Date 2015-10-05 Time 13:45 Sent To P
Notes
2015-10-05 18:12:00APPROVED WITH EXCEPTION. THIS PLAN HAS BEEN APPROVED
 PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES IN THIS PLAN PRIOR TO INSPECTION WILL
 RESULT IN FAILED INSPECTION(S) AND ASSESSMENT OF
 RE-INSPECTION FEE(S).
  
 1) SUBMIT TWO SETS OF SHOP DRAWINGS THAT HAVE BEEN
 APPROVED BY THE DESIGNER OF RECORD FOR THE GLASS
 BALCONY AND STAIR GUARDS.
  
 2) SUBMIT TWO SETS OF SHOP DRAWINGS THAT HAVE BEEN
 APPROVED BY THE DESIGNER OF RECORD FOR THE HOLLOW CORE
 PLANK INSTALLATION.
  
 3) SUBMIT TWO COMPLETE SETS OF INSTALLATION
 INSTRUCTIONS FOR THE ELEVATOR AND ALL RELATED
 EQUIPMENT.
  
 4) SUBMIT TWO COMPLETE SETS OF INSTALLATION
 INSTRUCTIONS FOR THE OUTDOOR BBQ GRILL.
  
 5) SUBMIT TWO COMPLETE SETS OF MANUALS WITH
 INSTALLATION INSTRUCTIONS FOR THE SPECIFIC MODEL OF
 SPARK MODERN FIRES INDOOR AND OUTDOOR LINEAR BURNER
 SYSTEMS THAT WILL BE INSTALLED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-09-04 Cont ID  
Sent By rmcdouga Date 2015-09-04 Time 16:41 Rev Time 0.00
Received By rmcdouga Date 2015-08-31 Time 18:41 Sent To E
Notes
2015-09-04 17:46:54PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) ACCORDING THE DRAWING INDEX ON SHEET A-0.2, THERE
 APPEARS TO BE SOME SHEETS MISSING FROM THE PLANS.
 SHEETS S-10, SP-1.3 AND A-6.4 ARE NOT IN THE PLANS. FBC
 107.2.1
  
 2) THERE ARE SHEETS IN THE PLANS THAT ARE NOT LISTED IN
 THE DRAWING INDEX. SHEETS A-8.3, S0 AND S12 ARE NOT
 LISTED. FBC 107.2.1
  
 3) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY
 EFFICIENCY FORMS. FBC ENERGY SECTION 405.
  
 4) REVISE THE PRODUCT APPROVAL NUMBERS IN THE EXTERIOR
 DOOR SCHEDULE ON SHEET A3.1 AND SUBMIT THE CORRECT
 CURRENT ONES. NOA NO. 14-0123.10 AND NOA NO.14-1117.05
 ARE EXPIRED. NOA NO. 12-1231.06 IS FOR FRENCH DOORS AND
 PLANS SPECIFY SLIDING GLASS DOORS.
  
 5) THE PRODUCT APPROVALS ARE REQUIRED TO BE APPROVED IN
 WRITING BY THE DESIGNER OF RECORD. FBC 107.3.4.1
  
 SUBMIT TWO SETS OF SHOP DRAWINGS THAT HAVE BEEN
 APPROVED BY THE DESIGNER OF RECORD FOR THE GLASS
 BALCONY AND STAIR GUARDS.
  
 6) SUBMIT TWO SETS OF SHOP DRAWINGS THAT HAVE BEEN
 APPROVED BY THE DESIGNER OF RECORD FOR THE HOLLOW CORE
 PLANK INSTALLATION.
  
 7) SUBMIT TWO COMPLETE SETS OF INSTALLATION
 INSTRUCTIONS FOR THE ELEVATOR.
  
 8) SUBMIT TWO COMPLETE SETS OF INSTALLATION
 INSTRUCTIONS FOR THE OUTDOOR BBQ GRILL.
  
 9) SUBMIT TWO COMPLETE SETS OF MANUALS WITH
 INSTALLATION INSTRUCTIONS FOR THE SPECIFIC MODEL OF
 SPARK MODERN FIRES INDOOR AND OUTDOOR LINEAR BURNER
 SYSTEMS THAT WILL BE INSTALLED.
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2015-06-04 Cont ID  
Sent By rmcdouga Date 2015-06-04 Time 16:58 Rev Time 0.00
Received By rmcdouga Date 2015-06-02 Time 13:47 Sent To  
Notes
2015-06-04 16:58:13APPROVED WITH EXCEPTION. THIS PLAN HAS BEEN APPROVED
 PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES IN THIS PLAN PRIOR TO INSPECTION WILL
 RESULT IN FAILED INSPECTION(S) AND ASSESSMENT OF
 RE-INSPECTION FEE(S).
  
 1) SUBMIT TWO SETS OF SHOP DRAWINGS THAT HAVE BEEN
 APPROVED BY THE DESIGNER OF RECORD FOR THE GLASS
 BALCONY AND STAIR GUARDS.
  
 2) SUBMIT TWO SETS OF SHOP DRAWINGS THAT HAVE BEEN
 APPROVED BY THE DESIGNER OF RECORD FOR THE HOLLOW CORE
 PLANK INSTALLATION.
  
 3) SUBMIT TWO COMPLETE SETS OF INSTALLATION
 INSTRUCTIONS FOR THE ELEVATOR.
  
 4) SUBMIT TWO COMPLETE SETS OF INSTALLATION
 INSTRUCTIONS FOR THE OUTDOOR BBQ GRILL.
  
 5) SUBMIT TWO COMPLETE SETS OF MANUALS WITH
 INSTALLATION INSTRUCTIONS FOR THE SPECIFIC MODEL OF
 SPARK MODERN FIRES INDOOR AND OUTDOOR LINEAR BURNER
 SYSTEMS THAT WILL BE INSTALLED.
  
 6) REVISE THE PRODUCT APPROVAL NUMBERS IN THE EXTERIOR
 DOOR SCHEDULE FOR THE SLIDING GLASS DOORS AND SUBMIT
 TWO SETS OF CURRENT PRODUCT APPROVALS FOR THEM. ( THE
 ONES THAT ARE SPECIFIED ARE EITHER EXPIRED OR FOR
 FRENCH DOORS.)
  
 7) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY
 CALCULATIONS FOR THE BUILDING ENVELOPE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-03-24 Cont ID  
Sent By rmcdouga Date 2015-03-24 Time 18:01 Rev Time 0.00
Received By rmcdouga Date 2015-03-20 Time 17:20 Sent To  
Notes
2015-03-24 10:26:13PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THIS PROJECT IS LOCATED IN AN A5 FLOOD ZONE WHICH IS
 A SPECIAL FLOOD HAZARD AREA (SFHA). THE BASE FLOOD
 ELEVATION (BFE) OF 7.5 FEET NGVD (INCLUDING THE SIX
 INCH FREEBOARD REQUIRED BY CITY ORDINANCE). A
 CONSTRUCTION DRAWING ELEVATION CERTIFICATE IS REQUIRED.
 NOTE: ALL EQUIPMENT SERVICING THE BUILDINGS ARE
 REQUIRED TO BE AT OR ABOVE 7.5 FEET NGVD. AN UNDER
 CONSTRUCTION ELEVATION CERTIFICATE IS RECOMMENDED. A
 FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS REQUIRED
 TO BE SUBMITTED FOR REVIEW AND APPROVED BEFORE A
 CERTIFICATE OF OCCUPANCY WILL BE ISSUED.
  
 2) THE FLOOD ZONE IS INCORRECTLY SPECIFIED AS AE5 ON
 SHEET A-0.2. IT SHOULD BE A5.
  
 3) PROVIDE TWO SETS OF A SITE DRAINAGE PLAN SHOWING
 COMPLIANCE WITH FBC-R 401.3 DRAINAGE.
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT
 DOES NOT CREATE A HAZARD. LOTS SHALL BE GRADED TO DRAIN
 SURFACE WATER AWAY FROM FOUNDATION WALLS. THE GRADE
 SHALL FALL A MINIMUM OF 6 INCHES (152 MM)WITHIN THE
 FIRST 10 FEET (3048 MM).
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL
 WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE
 CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE.
 IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE
 BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2
 PERCENT AWAY FROM THE BUILDING.
  
 4) THE ADDRESS ON THE APPLICATION 6505 S. FLAGLER (PCN
 74434410340000010) IS FOR LOT 1. BASED ON THE SURVEY
 AND OTHER DOCUMENTS THIS STRUCTURE WILL BE LOCATED ON
 LOT 2. THE ADDRESS FOR LOT 2 IS 6511 S FLAGLER DR (PCN
 74434410340000020). THIS NEEDS TO BE CLARIFIED BEFORE
 THE PERMIT CAN BE ISSUED. FBC 107.2.1
  
 5) THE SUBSURFACE SOIL REPORT AND GEOTECHNICAL
 EVALUATION ARE FOR LOT 1, 6505 SOUTH FLAGLER DRIVE AND
 THIS PROJECT IS LOCATED ON LOT 2. PLEASE CLARIFY.
  
 6) ONLY ONE ENERGY COMPLIANCE FORM WAS SUBMITTED FOR
 THE MAIN HOUSE AND THE CABANA. SUBMIT ONE ADDITIONAL
 FORM FOR EACH. TWO OF EACH DOCUMENT IS REQUIRED BY FBC
 107.1.
  
 7) THE ELEVATOR IS REQUIRED BY FBC-R 321.1 TO COMPLY
 WITH ASME A17.1-2007 / CSA B44-07. SUBMIT TWO SETS OF
 SPECIFICATIONS FOR THE ELEVATOR EQUIPMENT. THE ELEVATOR
 IS LOCATED IN A SPECIAL FLOOD HAZARD AREA (SFHA). IT IS
 REQUIRED TO COMPLY WITH ASCE 24-05. YOU SHOULD ALSO
 REFER TO FEMA TECHNICAL BULLETIN 4/ NOVEMBER 2010.
  
 8) FBC-R 905.9.1 REQUIRES BUILT-UP ROOFS TO HAVE A 1/4"
 PER FOOT SLOPE, EXCEPT FOR COAL-TAR BUILT-UP ROOFS,
 WHICH SHALL HAVE A MINIMUM 1/8" PER FOOT SLOPE. SHEETS
 A2.3 AND S9 SPECIFY 1/8" SLOPES AND OTHERS SPECIFY 1/4"
 SLOPES.
  
 9) THE FRAMING NOTES NUMBER 1 - 4 ARE BLANK ON SHEETS
 S3, S6, S7, S8 AND S9. FBC 107.2.1.4
  
 10) THERE IS WHAT APPEARS TO BE A PRINTING ERROR WHICH
 CONSISTS OF A STREAK THAT RUNS FROM SHEET S2 THROUGH
 SHEET S12 WHICH BLANKS OUT PARTS OF THE TEXT ON THOSE
 SHEETS. FBC 107.2.1.4
  
 11) THE DOOR ELEVATIONS ON SHEET A-3.1 HAS TEXT STATING
 THAT TYPE E DOOR IS NOT USED. HOWEVER, THE DOOR
 SCHEDULE LISTS TYPE E FOR THE SLIDING GLASS DOORS. FBC
 107.1.2
  
 12) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS FOR THE OUT DOOR BBQ GRILL. FBC
 107.2.1.3
  
 13) THE SPARK MODERN FIRES SPECIFICATIONS THAT WERE
 SUBMITTED ARE FOR AN UNVENTED SEE-THRU GAS FIREPLACE.
 THE ONE IN THE LIVING ROOM IS NOT A SEE THRU MODEL. FBC
 107.2.1
  
 14) SPECIFY THE SYSTEM AND MAXIMUM DESIGN PRESSURE FOR
 THE ELASTIZELL LIGHT WEIGHT INSULATING CONCRETE ( NOA
 NO. 13-0617.20 ). FBC-R301.1
  
 15) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE BUR
 FOR CONCRETE DECK (NOA NO. 13-0424.11) HAS BEEN
 SUPERSEDED BY NOA NO. 13-0930.08. SPECIFY THE APPROVED
 ASSEMBLY, FASTENING OPTION AND MAXIMUM DESIGN PRESSURE
 THAT WILL BE INSTALLED.
  
 16) THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR THE BUR
 IS FOR INSTALLATION TO A CONCRETE DECK. THE PLANS
 INDICATE THAT THERE WILL BE A MINIMUM OF 2 " OF LIGHT
 WEIGHT CONCRETE OVER THE CONCRETE DECK. SUBMIT TWO
 COPIES OF THE PRODUCT APPROVALS FOR ROOFING INSTALLED
 TO A LIGHT WEIGHT CONCRETE DECK. DCA RULE 9N-3
  
 17) THE PRODUCT APPROVAL FOR THE "PGT FD 750" FRENCH
 DOOR W/ SIDELITES ( NOA NO. 11-1013.24 ) IS NOT LISTED
 IN THE DOOR SCHEDULE ON A-3.1 AND IT EXPIRED ON
 2/24/15. FBC 107.2.1
  
 18) NOA NO. 11-0302.03 FOR THE CAOBA ENTRY DOOR IS
 CLOSED. DCA RULE 9N-3
  
 19) NOA NO. 11-0922.01FOR THE PGT MULLIONS WAS
 SUPERSEDED ON 2/12/15 BY NOA NO. 14-1105.01. DCA RULE
 9N-3
  
 20) NOA NO. 11-0121.04 WAS SUPERSEDED ON 4/5/12. THE
 CURRENT ONE IS NOA NO. 14-0903.02. DCA RULE 9N-3
  
 21) THE REQUIRED COMPONENT & CLADDING PRESSURE ( -57.0
 PSF ) EXCEEDS THE DESIGN PRESSURE IN THE JELD-WEN ( FL
 1063.5 ) PRODUCT APPROVAL (-50 PSF ) FOR THE GARAGE
 ENTRY DOOR.
  
 22) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.
 - YOU CAN DOWNLOAD THE CURRENT NOAS AT THE FOLLOWING
 WEB SITE:
 HTTP://WWW.MIAMIDADE.GOV/BUILDING/PC-SEARCH_APP.ASP
 - YOU CAN DOWNLOAD FLORIDA PRODUCT APPROVALS AT THE
 FOLLOWING WEB SITE:
 HTTPS://FLORIDABUILDING.ORG/PR/PR_APP_SRCH.ASPX
  
 RE-SUBMITTAL PROCEDURE
  
 YOU ARE REQUIRED TO FILL OUT A RE-SUBMITTAL FORM TO BE
 SUBMITTED WITH THE CORRECTED PLANS AND/OR OTHER
 DOCUMENTS. THE PERMIT CLERK WILL RETRIEVE THE DENIED
 APPLICATION, PLANS AND OTHER DOCUMENTS FOR YOU. YOU ARE
 REQUIRED TO REMOVE THE OLD PLAN SHEETS THAT HAVE BEEN
 CORRECTED AND REPLACE THEM WITH THE NEW ONES. THE CLERK
 WILL PROVIDE YOU WITH A STAPLE REMOVER AND A STAPLER.
 ONE SET OF THE OLD PLAN SHEETS THAT HAVE BEEN REMOVED
 SHALL BE MARKED AS VOIDED AND RESUBMITTED ALONG WITH
 THE TWO (OR MORE) SETS THAT CONTAIN THE CORRECTED
 SHEETS. IF THERE ARE ANY SHEETS THAT HAVE BEEN STAMPED
 FOR COUNTY IMPACT FEES, HOA APPROVAL STAMPS OR OTHERS,
 RESUBMIT THOSE SHEETS.
 IF ALL OF THE PLAN SHEETS HAVE BEEN CORRECTED, THEN TWO
 (OR MORE) SETS OF THE NEW PLANS AND ANY OTHER DOCUMENTS
 SHALL BE SUBMITTED.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2015-10-07 Cont ID  
Sent By albarran Date 2015-10-07 Time 11:56 Rev Time 0.00
Received By albarran Date 2015-10-07 Time 09:34 Sent To I
Notes
2015-10-07 12:01:23THIS PERMIT IS BEING APPROVED WITH PROVISO MAKING
 REFERENCE TO NEC 406.8. PLEASE NOTE THAT SEPARATE
 PERMIT SHALL BE OBTAINED FOR THE INSTALLATION OF THE
 GENERATOR AND ANY LOW VOLTAGE WORK, (ALARM, CCTV, A/V
 SYSTEMS ETC.)
 OTHERWISE ALL PREVIOUSLY MENTIONED DEFICIENCIES HAVE
 BEEN SATISFACTORILY ADDRESSED.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2015-09-15 Cont ID  
Sent By dhayes Date 2015-09-15 Time 18:39 Rev Time 0.00
Received By albarran Date 2015-09-15 Time 11:20 Sent To I
Notes
2015-09-15 18:43:42PLEASE NOTE THAT I, MIKE ALBARRAN, ELECTRICAL PLANS
 EXAMINER HAVE COMPLETED THE REVIEW OF THE ABOVE
 MENTIONED JOB. BELOW ARE THE COMMENTS WITH REGARDS TO
 THE REQUIRED CORRECTIONS. THE FOLLOWING ITEMS SHALL BE
 CORRECTED AND THE PLANS RESUBMITTED FOR ANOTHER REVIEW.
 1. THE FBC IN EFFECT IS THE 5TH EDITION 2014 NOT THE
 2010.
 2. PER NEC 406.9(B), ALL OUTDOOR 15 ? 20 AMP
 NON-LOCKING RECEPTACLES SHALL BE LISTED
 WEATHER-RESISTANT TYPE ?WR?.
 3. LOADS AS REFLECTED ON SHEET E.1 FOR PANELS A, B & D
 DO NOT MATCH THE CALCS EXPRESSED ON SHEET E.0.
 4. THE FIRE STOPPING NOTES AS EXPRESSED ON THE PLANS
 ONLY APPLY WHEN USING A NON-COMMUNICATING PARTITION,
 OTHERWISE ALL ELECTRICAL BOXES IN A RATED WALL SHALL BE
 PROPERLY FIRE STOPPED.
 5. THE SMOKE DETECTOR PLACEMENT NOTES SHALL ALSO
 INCLUDE ?36 INCHES AWAY FROM THE TIP OF A CEILING FAN
 BLADE, OR THE DOOR TO A BATHROOM HOUSING A SHOWER OR
 TUB?.
 6. PANEL ?E? APPEARS TO HAVE A CONNECTED LOAD GREATER
 THAN THE BUS RATING INDICATED.
 7. CLARIFY THE GENERATOR SIZE. THE PLANS CALL FOR A 25
 KW, AND THE SUBMITTED SPEC SHEET IS FOR A 22 OR 27 KW
 UNIT. PROVIDE THE PROPER SPEC SHEET FOR THE APPLICABLE
 GENERATOR AND IF THE SHEET IS MORE MULTIPLE UNITS
 MARK/HIGHLIGHT THE PROPOSED/INTENDED UNIT.
 8. THE CALCS FOR THE MDP FAIL TO INCLUDE THE LOADS TO
 PANEL ?E?.
 9. THE CONNECTED LOAD AT THE MDP EXCEEDS THE MCB RATING
 INDICATED.
 10. THE LOADS FOR THE MDP OF SHEET E.0 DO NOT MATCH
 THOSE OF SHEET E.1
 11. NEC 210.70(A)(3), REQUIRES THAT THERE BE A LIGHT IN
 THE CLOSET WHERE THE SMART BOX IS LOCATED.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND LEAVE THE
 PREVIOUSLY REVIEWED SHEETS.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2015-06-05 Cont ID  
Sent By dhayes Date 2015-06-05 Time 14:43 Rev Time 0.00
Received By dhayes Date 2015-06-05 Time 13:15 Sent To  
Notes
2015-06-05 14:54:11SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR THE GENERATOR / ATS, GAS, SWIMMING
 POOL, SITE LIGHTING, AND ALL LOW VOLTAGE SYSTEMS SUCH
 AS: SECURITY, CCTV, AUDIO/VIDEO, NETWORK, DATA, AND,
 COMMUNICATION.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-03-24 Cont ID  
Sent By dhayes Date 2015-03-24 Time 12:38 Rev Time 0.00
Received By dhayes Date 2015-03-23 Time 15:41 Sent To  
Notes
2015-03-24 12:38:053/24/2015
 PROJECT: WILLIAMS RESIDENCE
 PERMIT#: 15020495
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) NEC 220.16(2)
 PROVIDE A COMPLETE LOAD CALCULATION. LOADS FOR NEW
 CIRCUITS OR EXTENDED CIRCUITS IN PREVIOUSLY WIRED
 DWELLING UNITS SHALL BE CALCULATED IN ACCORDANCE WITH
 220.12 OR 220.14, AS APPLICABLE.
  
 2) NEC 702.5 CAPACITY AND RATING.
 A) INDICATE THE PROPOSED ATS HAS LOAD MANAGEMENT
 CAPABILITY WITH THE CAPACITY TO MANAGE THE LOAD THAT IS
 ILLUSTRATED BY THE LOAD CALCULATION TO BE OVER AND
 ABOVE THE ACTUAL CAPACITY OF THE PROPOSED GENERATOR OR
 INDICATE A GENERATOR AND ATS WITH THE CAPACITY TO
 TRANSFER AND CARRY THE TOTAL CONNECTED LOAD THAT IS
 ILLUSTRATED THE LOAD CALCULATION.
 B) A SEPARATE PERMIT APPLICATION ACCOMPANIED BY THE
 MANUFACTURER?S EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 IS REQUIRED FOR THE GENERATOR SYSTEM.
  
 3) ADDITIONAL PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURER?S EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR ANY PROPOSED LOW VOLTAGE OR SPECIALTY
 SYSTEM SUCH AS ELEVATOR, SAUNA, MOTORIZED BLINDS,
 ACCESS CONTROL, MOTORIZED GATE, SECURITY, CCTV,
 AUDIO/VIDEO, NETWORK, OR DATA, AND COMMUNICATION
 SYSTEMS.
  
 4) WPB AMENDMENTS TO FBC 107.3.2
 CLARIFY ROOM #118. IT IS INDICATED AS A WALK IN CLOSET
 OR A SAUNA.
  
 5) WPB AMENDMENTS TO FBC 107.3.2
 PROVIDE THE ELECTRICAL CIRCUITRY ON THE PLAN FOR ALL OF
 THE EXHAUST AND DRYER FANS.
  
 6) WPB AMENDMENTS TO FBC 107.3.2
 INDICATE THE LOCATION OF THE ?SMART BOX?
  
 7) NEC 250.94
 INDICATE THE LOCATION OF THE INTERSYSTEM BONDING STRIP.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
  
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2015-09-01 Cont ID  
Sent By tklarge Date 2015-09-01 Time 12:26 Rev Time 0.00
Received By tklarge Date 2015-09-01 Time 12:26 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2015-07-28 Cont ID  
Sent By tklarge Date 2015-07-28 Time 11:44 Rev Time 0.00
Received By tklarge Date 2015-07-28 Time 11:28 Sent To  
Notes
2015-07-28 11:44:06COMMENTS DELETED BY ERROR. TKL.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-10-07 Cont ID  
Sent By albarran Date 2015-10-07 Time 12:01 Rev Time 0.00
Received By albarran Date 2015-09-24 Time 11:15 Sent To  
Notes
2015-10-07 12:08:1410/7/15 PASSED ALL REVIEWS. CONTRACTOR NOTIFIED VIA
 EMAIL. SENT TO LARGE READY BIN "T". MA
2015-09-24 11:15:42RESUB ROUTED TO RMCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-09-15 Cont ID  
Sent By albarran Date 2015-09-15 Time 18:45 Rev Time 0.00
Received By albarran Date 2015-07-06 Time 09:03 Sent To  
Notes
2015-09-15 18:48:059/15/15 - FAILED ELECTRICAL REVIEW AS NOTED. CONTRACTOR
 NOTIFIED VIA EMAIL. SENT TO LARGE DENIED BIN "T". MA

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-06-05 Cont ID  
Sent By dhayes Date 2015-06-05 Time 14:44 Rev Time 0.00
Received By dhayes Date 2015-04-17 Time 15:25 Sent To  
Notes
2015-04-17 15:29:19R31

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-03-24 Cont ID  
Sent By rmcdouga Date 2015-03-24 Time 18:02 Rev Time  
Received By rmcdouga Date 2015-02-13 Time   Sent To  
Notes
2015-02-18 08:16:11R26

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status P Date 2015-10-15 Cont ID  
Sent By rmcdouga Date 2015-10-15 Time 13:46 Rev Time 0.00
Received By rmcdouga Date 2015-10-14 Time 14:05 Sent To  
Notes
2015-10-15 14:16:19MU 2015 - 24141, NO FEES WERE DUE.
2015-10-14 14:05:41RMCDOUGAL'S DESK

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2015-10-05 Cont ID  
Sent By rmcdouga Date 2015-10-05 Time 17:41 Rev Time 0.00
Received By rmcdouga Date 2015-10-05 Time 17:41 Sent To  
Notes
2015-10-05 17:41:22BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2015-08-31 Cont ID  
Sent By rmcdouga Date 2015-08-31 Time 18:44 Rev Time 0.00
Received By rmcdouga Date 2015-08-31 Time 18:44 Sent To  
Notes
2015-08-31 18:44:17BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-03-20 Cont ID  
Sent By rmcdouga Date 2015-03-20 Time 13:31 Rev Time 0.00
Received By rmcdouga Date 2015-03-20 Time 13:31 Sent To  
Notes
2015-03-20 13:31:57BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2015-09-01 Cont ID  
Sent By rmcdouga Date 2015-09-01 Time 09:43 Rev Time 0.00
Received By rmcdouga Date 2015-09-01 Time 09:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2015-03-20 Cont ID  
Sent By rmcdouga Date 2015-03-20 Time 17:20 Rev Time 0.00
Received By rmcdouga Date 2015-03-20 Time 16:38 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status P Date 2019-04-25 Cont ID  
Sent By shill Date 2019-04-25 Time 15:31 Rev Time 0.00
Received By shill Date 2019-04-25 Time 15:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2015-10-07 Cont ID  
Sent By tklarge Date 2015-10-07 Time 05:40 Rev Time 0.00
Received By tklarge Date 2015-10-07 Time 04:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2015-07-28 Cont ID  
Sent By tklarge Date 2015-07-28 Time 11:25 Rev Time 0.00
Received By tklarge Date 2015-07-28 Time 09:02 Sent To  
Notes
2015-07-28 11:27:291) SUBMIT A NARRATIVE THAT CLEARLY DETAILS THE CHANGES
 THAT WERE MADE TO THE PLUMBING SYSTEM.WPB AMEND. TO FBC
 SEC. 107.2.1.
  
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-05-26 Cont ID  
Sent By tklarge Date 2015-05-26 Time 10:21 Rev Time 0.00
Received By tklarge Date 2015-05-23 Time 13:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2015-03-03 Cont ID  
Sent By tklarge Date 2015-03-03 Time 14:17 Rev Time 0.00
Received By tklarge Date 2015-03-01 Time 08:27 Sent To  
Notes
2015-03-03 13:39:491) SHT. A7.5 SHOWS THE HEIGHT OF THE GRAB BARS MEASURED
 TO THE CENTERLINE OF THE GRAB BARS. THE GRAB BARS SHALL
 BE MEASURED TO THE TOP OF THE GRIPPING SURFACE PER 2010
 FAC SEC.609.4.
 2) SHT. P.1 - THE PLAN REFERES TO CIVIL DRAWINGS FOR
 THE CONTINUATION OF THE STORM DRAIN.THE SUBMITTED CIVIL
 DRAWINGS DO NOT SHOW ANY STORM DRAIN/STORM SEWER
 PIPING. CLARIFY.
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS/INSTALLATION
 INSTRUCTIONS FOR THE STEAM GENERATING UNIT.WPB AMEND.
 TO 2010 FBC SEC. 107.2.1.
 4) SHT.P.1 - SHOWS A NOTE BY THE ELEVATOR STATING "4"
 STORM DRAIN FROM 2ND FLOOR" BUT NOTHING IS SHOWN.
 CLARIFY.
 5) SHT.P.2 - SHOWS A NOTE BY THE ELEVATOR STATING "3"
 STORM DRAIN DOWN TO FIRST FLOOR BUT NOTHING IS
 SHOWN.CLARIFY.
 6) THE PLUMBING FIXTURES SHOWN ON THE SANITARY RISER
 DIAGRAM MAKE IT A LITTLE DIFFICULT TO SEE THE SANITARY
 LINES AT PLACES. IF POSSIBLE, PLEASE DELETE THE FIGURES
 FROM THE SANITARY RISER DIAGRAM.WPB AMEND. TO 2010 FBC
 SEC.107.2.1.
 7) SHT. P.6 APPEARS TO SHOW ASHP #6 CONNECTED TO THE
 SANITARY SYSTEM. CLARIFY.
 8) SHT. P.7 - INDICATE HOW THE HANGER RODS WILL BE
 CONNECTED TO THE BOTTOM OF THE CONCRETE SLAB.WPB AMEND.
 TO 2010 FBC SEC. 107.2.1.
 9) SIZE ALL SECTIONS OF THE SANITARY RISERR.WPB AMEND.
 TO 2010 FBC SEC. 107.2.1.
  
 WATER
 9) AN RPZ BACKFLOW PREVENTER IS REQUIRED ON THE WATER
 SERVICE AT THE METER. WPB CROSS CONNECTION MANUAL.
 10) SHT. P.5 - IDENTIFY ALL THE FIXTURES/APPLIANCES
 CONNECTED TO THE WATER RISER IN THE CABANA BATH.WPB
 AMEND. TO 2010 FBC SEC. 107.2.1.
 11) IDENTIFY THE LAUNDRY FIXTURES ON THE WATER RISER.
 WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 12) SHT. P.5 - THE V. SINK IS SHOWN ON THE WATER RISER
 BUT NOT SHOWN ON THE PLAN VIEW ON SHT.P.3.CLARIFY.
 13) SHT. P.5 - GW-3 IS SHOWN ON SHT. P.3 BUT NOT ON P.5
 - CLARIFY.
 14) SHOW THE STEAM GENERATING UNIT ON THE WATER RISER
 IF APPLICABLE.
 15) SIZE THE HOT WATER RETURN LINE ON SHT. P.5.WPB
 AMEND. TO 2010 FBC SEC. 107.2.1.
 16) SHT. P.5 - THERE ARE VARIOUS SECTIONS OF THE WATER
 RISER THAT ARE NOT SIZED. SIZE THE RISER DIAGRAM AS
 NEEDED. ( SEE PIPE TO FIXTURES, BRANCH LINES, ETC.).
  
 STORM
 17) INDICATE THE SLOPE OF THE HORIZONTAL STORM DRAINAGE
 PIPE.
 18) SHT. P.8 - THERE IS ONE ROOF DRAIN THAT IS NOT
 LABELED/IDENTIFIED ON THE RISER. CLARIFY.WPB AMEND. TO
 2010 FBC SEC. 107.2.1.
 19) SIZE ALL VERTICAL AND HORIZONTAL SECTIONS OF THE
 STORM DRAIN SYSTEM.WPB AMEND. TO 2010 FBC SEC. 107.2.1.
  
 GAS
 21) SUBMIT MANUFACTURER'S SPECIFICATIONS/INSTALLATION
 INSTRUCTIONS FOR ALL GAS EQUIPMENT. EQUIPMENT SHALL BE
 LAISTED AND LABELED. 2010 FGC SEC. 301.3, 402.2.
 22) SUBMIT MANUF . SPECIFICATIONS FOR THE VENTLESS
 PRESSURE REGULATORS.2010 FBCR SEC.G2421.3.
 23) SUBMIT A SITE PLAN THAT SHOWS THE LOCATION OF THE
 LP TANK, DISTANCE FROM THE STRUCTURE, PROPERTY LINES
 TANK CAPACITY, ANCHORING, ETC. AND THE LOCATION OF ALL
 EXTERIOR GAS EQUIPMENT.WPB AMEND. TO 2010 FBC SEC.
 107.2.1.
 24) SUBMIT DETAILS SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION POINTS OF ALL GAS VENTS PER 2010 FBCR
 SEC.G2407.
 25) SHT. P.3 APPEARS TO SHOW PE GAS PIPNG UNDER THE
 SLAB.PE PIPE CAN ONLY BE USED UNDERGROUND OUTDOORS.
 FBCR SEC.G2415.15.1. PIPING UNDER A BUILDING SHALL BE
 ENCASED IN CONDUIT PER 2010 FBCR SEC.G2415.12.
 26) SIZE THE GAS LINE TO APPLIANCES G-102, G-WH1,
 G-103, G-105.WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 27) SHT. P.3 - IDENTIFY ALL THE GAS APPLIANCES ON THE
 GAS RISER. WPB AMEND. TO 2010 FBC SEC. 107.2.1.
 28) P.7 NOTES APPLIANCE G-106 AS NATURAL GAS BUT SHT.
 P.3 REFERS TO LP GAS. CLARIFY.
 29) THE SUBMITTED SPECS ON THE PA SHEETS FOR THE
 FIREPLACE LIST THE MAXIMUM BTU LOAD AS 39,000 AND THE
 SCHEDULE ON SHT.P.4 SHOWS 40,000. CLARIFY. INDICATE THE
 MODEL OF THE FIREPLACE BEING USED ON THE PA SHEEET.
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2015-07-23 Cont ID  
Sent By sgraham Date 2015-07-23 Time 15:52 Rev Time 0.00
Received By sgraham Date 2015-07-23 Time 15:52 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2015-04-23 Cont ID  
Sent By sgraham Date 2015-04-23 Time 08:42 Rev Time 0.00
Received By sgraham Date 2015-04-23 Time 08:42 Sent To  
Notes
2015-04-23 08:43:304/23/15
  
 SEPARATE PERMIT AND PLANS LANDSCAPING REQUIRED

Review Stop Z ZONING
Rev No 1 Status F Date 2015-02-26 Cont ID  
Sent By sgraham Date 2015-02-26 Time 15:34 Rev Time 0.00
Received By sgraham Date 2015-02-26 Time 15:34 Sent To  
Notes
2015-02-26 15:36:042/26/15 ZONING FAILED
  
 1. PROVIDE TWO UP TO DATE SURVEYS SHOWING THE REPLAT.
2015-02-25 10:56:482/25/15