| 2015-02-19 09:37:00 | BUILDING PLAN REVIEW |
| | PERMIT: 15020491 |
| | ADD: 550 OKEECHOBEE BLVD. # 1801 |
| | CONT: BENCHMARK |
| | TEL: (561)375-6249 |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | IMPORTANT NOTICE: EFFECTIVE MARCH 2, 2015 |
| | ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED |
| | ELECTRONICALLY |
| | UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS |
| | SUBMISSION OPTIONS ARE AS FOLLOWS: |
| | 1 UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL |
| | SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE |
| | THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| | 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL |
| | SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED |
| | NAMING CONVENTION FOR EACH DOCUMENT |
| | 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER |
| | DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE |
| | REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| | 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT |
| | TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS |
| | ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES |
| | AVAILABLE |
| | |
| | 1ST REVIEW |
| | DATE: THURS. FEB. 19/ 2015 |
| | ACTION: DENIED |
| | |
| | 1) THE SOUND REPORT SUBMITTED IS FOR A 8 INCH CONCRETE |
| | SLAB W/ DROPPED CEILING. THIS BUILDING IS POST TENSION |
| | 6 INCH SLAB. THE SOUND TEST HAS TO BE WITHOUT A DROPPED |
| | CEILING. |
| | |
| | 1A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 1B) FBC-B 2010 1207.2 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 2) HIGH-RISE BUILDING TYPE I. FLAME SPREAD- FBC-B 2010 |
| | 603.2 EXCEPTION 2. INSULATION INSTALLED BETWEEN A |
| | FINISHED FLOOR AND SOLID DECKING WITHOUT INTERVENING |
| | AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX |
| | OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 703.4 NONCOMBUSTIBILITY TESTS. |
| | THE TESTS INDICATED IN SECTIONS 703.4.1 AND 703.4.2 |
| | SHALL SERVE AS CRITERIA FOR ACCEPTANCE OF BUILDING |
| | MATERIALS AS SET FORTH IN SECTIONS 602.2, 602.3 AND |
| | 602.4 IN TYPE I, II, III AND IV CONSTRUCTION. THE TERM |
| | ?NONCOMBUSTIBLE? DOES NOT APPLY TO THE FLAME SPREAD |
| | CHARACTERISTICS OF INTERIOR FINISH OR TRIM MATERIALS. A |
| | MATERIAL SHALL NOT BE CLASSIFIED AS A NONCOMBUSTIBLE |
| | BUILDING CONSTRUCTION MATERIAL IF IT IS SUBJECT TO AN |
| | INCREASE IN COMBUSTIBILITY OR FLAME SPREAD BEYOND THE |
| | LIMITATIONS HEREIN ESTABLISHED THROUGH THE EFFECTS OF |
| | AGE, MOISTURE OR OTHER ATMOSPHERIC CONDITIONS. |
| | |
| | 703.4.1 ELEMENTARY MATERIALS. |
| | MATERIALS REQUIRED TO BE NONCOMBUSTIBLE SHALL BE TESTED |
| | IN ACCORDANCE WITH ASTM E 136. |
| | |
| | 703.4.2 COMPOSITE MATERIALS. |
| | MATERIALS HAVING A STRUCTURAL BASE OF NONCOMBUSTIBLE |
| | MATERIAL AS DETERMINED IN ACCORDANCE WITH SECTION |
| | 703.4.1 WITH A SURFACING NOT MORE THAN 0.125 INCH (3.18 |
| | MM) THICK THAT HAS A FLAME SPREAD INDEX NOT GREATER |
| | THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 OR UL |
| | 723 SHALL BE ACCEPTABLE AS NONCOMBUSTIBLE MATERIALS |
| | |
| | FBC-B 2010 |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | |
| | |