| 2015-03-02 17:20:34 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | SHEET G - 010 INCORRECT REFERENCES TO THE CURRENT |
| | EDITION OF THE FIRE CODE. PLEASE CORRECT AND REFERENCE |
| | THAT THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS |
| | OF THE 5TH EDITION OF FLORIDA FIRE PREVENTION CODE |
| | INCLUDING THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND |
| | ALL OTHER APPLICABLE CODES OR STANDARDS. |
| | |
| | IT IS UNCLEAR ON THE SUBMITTED PLAN WHAT IS EXISTING. |
| | PLEASE CLEARLY INDICATE WHAT IS EXISTING AND WHAT IS |
| | PROPOSED. IF A NEW WALL IS BEING INSTALLED IT SHALL BE |
| | FIRE RATED ACCORDING TO THE SEPARATION REQUIREMENTS OF |
| | STORAGE AND BUSINESS/MERCANTILE. |
| | |
| | THE NATURE OF THE REMODEL REQUIRES AN EVALUATION OF THE |
| | FIRE ALARM AND SPRINKLER SYSTEM FOR CODE COVERAGE AND |
| | COMPLIANCE. |
| | |
| | PLEASE MAKE REFERENCE TO THE FOLLOWING ON THE SUBMITTED |
| | PLAN: |
| | |
| | THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE |
| | SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE |
| | CONSTRUCTION PERIOD. |
| | |
| | ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER |
| | SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND |
| | BY CERTIFIED LIFE SAFETY CONTRACTORS. |
| | |
| | ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, |
| | SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE |
| | WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL |
| | AND COMPLETE PROTECTION IS RETURNED. |
| | |