| | 1ST ELECTRICAL PLAN REVIEW |
| | ACTION: DENIED |
| | |
| | 1) REVISE THE RISER DIAGRAM TO ADDRESS THE RIVISION 5 |
| | CLOUDED AREA FEEDING THE 400AMP METER FOR BAY 20. |
| | |
| | 2) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS |
| | HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT |
| | NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE |
| | INTERRUPTED. NEC 110.9 |
| | |
| | 3) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR |
| | THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC |
| | 110.16. |
| | |
| | 4)PROVIDE A LOAD CALCULATION TO SHOW CAPACITY ON THE |
| | EXISTING SERVICE MAIN IS ADAQUATE TO SUPPORT THE |
| | ADDITIONAL LOAD. LOADS FOR NEW CIRCUITS OR EXTENDED |
| | CIRCUITS IN PREVIOUSLY WIRED DWELLING UNITS SHALL BE |
| | CALCULATED IN ACCORDANCE WITH EITHER 220.12 OR 220.14, |
| | AS APPLICABLE. NEC 220.16(2) |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. SEE LINK: |
| | HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/ |
| | 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF |
| | |
| | ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED |
| | PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE |
| | PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE |
| | REVIEW. |
| | |
| | DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421, |
| | 561-805-6717 OR [email protected] |
| | |