Plan Review Details - Permit 15020485
Plan Review Stops For Permit 15020485
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-04-06 Cont ID  
Sent By dhayes Date 2015-04-06 Time 09:37 Rev Time 0.00
Received By dhayes Date 2015-04-06 Time 08:27 Sent To  
Notes
2015-04-06 09:42:18SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR FIRE ALARM.
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-03-16 Cont ID  
Sent By dhayes Date 2015-03-16 Time 08:42 Rev Time 0.00
Received By dhayes Date 2015-03-16 Time 07:57 Sent To  
Notes
2015-03-16 08:24:073/16/2015
 PROJECT: 5335 MILITARY TR
 PERMIT#: 14060910, REVISION TRACKING #15020485
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) THE REVISED PLAN SHOWS 4 SETS OF 4, 500 MCM WITH A
 #2 EQUIPMENT GROUND. RISER DIAGRAM. REVISE TO INDICATE
 ONE SET AND INDICATE THE CONDUCTOR TYPE.
  
 2) INDICATE THE LOCATION OF THE EXISTING 200AMP PANEL,
 THE NEW GUTTER AND NEW 200AMP PANEL ADDED IN SUITE #20.
  
 3) CREATE A NEW SHEET THAT SHOWS THE REVIESD RISER
 DIAGRAM AND THE REVISED DEMO INCLUDING THE PANEL
 LOCATIONS IN SUITE #20
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-02-24 Cont ID  
Sent By dhayes Date 2015-02-20 Time 17:05 Rev Time 0.00
Received By dhayes Date 2015-02-20 Time 17:05 Sent To  
Notes
2015-02-24 17:20:072/24/2015
 PROJECT: 5335 MILITARY TR
 PERMIT#: 14060910, REVISION TRACKING #15020485
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) REVISE THE RISER DIAGRAM TO ADDRESS THE RIVISION 5
 CLOUDED AREA FEEDING THE 400AMP METER FOR BAY 20.
  
 2) VERIFY THE ELECTRICAL SERVICE DISCONNECTING MEANS
 HAS A FAULT CURRENT RATING THAT IS SUFFICIENT AT
 NOMINAL CIRCUIT VOLTAGE FOR THE CURRENT THAT MUST BE
 INTERRUPTED. NEC 110.9
  
 3) PROVIDE SAFETY LABELING FOR ARC FLASH PROTECTION FOR
 THE PANEL BOARDS AND MAIN DISCONNECTING MEANS. NEC
 110.16.
  
 4)PROVIDE A LOAD CALCULATION TO SHOW CAPACITY ON THE
 EXISTING SERVICE MAIN IS ADAQUATE TO SUPPORT THE
 ADDITIONAL LOAD. LOADS FOR NEW CIRCUITS OR EXTENDED
 CIRCUITS IN PREVIOUSLY WIRED DWELLING UNITS SHALL BE
 CALCULATED IN ACCORDANCE WITH EITHER 220.12 OR 220.14,
 AS APPLICABLE. NEC 220.16(2)
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-04-06 Cont ID  
Sent By dhayes Date 2015-04-06 Time 09:42 Rev Time 0.00
Received By dhayes Date 2015-04-03 Time 08:06 Sent To  
Notes
2015-04-03 08:06:24TO DAH DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-03-16 Cont ID  
Sent By dhayes Date 2015-03-16 Time 08:42 Rev Time 0.00
Received By dhayes Date 2015-03-13 Time 17:46 Sent To  
Notes
2015-03-13 17:46:02SENT TO D HAYES

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-02-24 Cont ID  
Sent By dhayes Date 2015-02-20 Time 17:05 Rev Time  
Received By dhayes Date 2015-02-13 Time   Sent To  
Notes
2015-02-18 08:39:42SENT TO D. HAYES'S DESK.