| 2015-02-19 07:37:51 | BUILDING PLAN REVIEW |
| | PERMIT : 15020438 |
| | EXPIRED:13050172 |
| | ADD: 3001 TUXEDO AVE. |
| | CONT: OLIVERI BROTHERS |
| | TEL: (561) 478-7233 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | IMPORTANT NOTICE: EFFECTIVE MARCH 2, 2015 |
| | ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED |
| | ELECTRONICALLY |
| | UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS |
| | SUBMISSION OPTIONS ARE AS FOLLOWS: |
| | 1 UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL |
| | SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE |
| | THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| | 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL |
| | SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED |
| | NAMING CONVENTION FOR EACH DOCUMENT |
| | 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER |
| | DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE |
| | REQUIRED NAMING CONVENTION FOR EACH DOCUMENT |
| | 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT |
| | TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS |
| | ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES |
| | AVAILABLE |
| | |
| | |
| | 1ST REVIEW |
| | DATE: THURS. FEB. 19/ 2015 |
| | ACTION: DENIED |
| | |
| | 1) THE ORIGINAL EXPIRED PERMIT # 13050172 FOR TRUSS |
| | REPAIR DOES NOT HAVE THE STRUCTURAL SHEETS S-1/ S-2 |
| | SHEETS INCLUDED IN THIS PERMIT PACKAGE. IT APPEARS THAT |
| | THE CONTRACTOR IS TRYING TO DO A RENEWAL PERMIT AS WELL |
| | AS ADDITIONAL WORK NOT COVERED UNDER THE ORIGINAL SCOPE |
| | OF THE PERMIT. THE PERMIT PLANS UNDER THE PERMIT |
| | 13050172 WILL NEED TO BE SUBMITTED FOR THE RESTAMP OF |
| | PLANS TO THE NEW PERMIT TRACKING NUMBER. A SECOND SET |
| | WILL ALSO BE REQUIRED FOR THE RECORD RETENSION FOR THE |
| | CITY. |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION 107.2 CONSTRUCTION |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL... |
| | |
| | 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS |
| | SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON |
| | SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. |
| | THE BUILDING OFFICIAL MAY ESTABLISH THROUGH |
| | DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND |
| | SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS |
| | RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH |
| | THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR |
| | OTHER ITEMS RELATED TO RECORDS MANAGEMENT. |
| | |
| | NEW WORK SHOWN ON THE OLIVERI MILLWORK PLANS. |
| | 2) SHEET A1.0 THE EAST ELEVATION SHOWS A SECTION LINE D |
| | THROUGH THE BUILDING WHERE A NEW WALL IS TO BE BUILT TO |
| | THE ROOF LINE. THIS LINE IS NOT SHOWN ON THE FLOOR |
| | PLAN. THE FLOOR PLANS DO SHOW A BLUE LINE BEING BUILT |
| | ON TOP OF AN EXISTING ROOM, IS THIS TO BE A |
| | CONTINUATION OF THE EXISTING MEZZANINE? |
| | IF SO, PLEASE PROVIDE THE LIFE SAFETY PLAN FOR THE |
| | MEZZANINE WITH THE FOLLOWING INFORMATION: |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | 107.3.5.1 COMMERCIAL BUILDINGS: |
| | 107.3.5.1.1 BUILDING |
| | 2.1) OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS |
| | SHALL BE DETERMINED. |
| | 2.2) MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED |
| | (SEE TABLE 503). |
| | 2.3) OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| | OCCUPANCY LOAD |
| | GROSS |
| | NET |
| | MEANS OF EGRESS |
| | EXIT ACCESS |
| | EXIT |
| | EXIT DISCHARGE |
| | STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION |
| | DOORS |
| | EMERGENCY LIGHTING AND EXIT SIGNS |
| | 2.4) STRUCTURAL REQUIREMENTS SHALL INCLUDE: |
| | DESIGN LOADS- FOR MEZZANINE FLOOR LOADS |
| | STRUCTURAL CALCULATIONS IF MEZZANINE IS FOR STORAGE |
| | 125/ 250 LBS |
| | WALLS SUPPORTING A MEZZANINE FLOOR LOAD |
| | 2,5) ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE |
| | FOLLOWING: |
| | ACCESSIBLE ROUTE/ VERTICAL ACCESSIBILITY |
| | 2.6) PROVIDE COMPLIANCE WITH 2010 FBC-B 505.2 AREA |
| | LIMITATION FOR MEZZANINES. |
| | 2.7) PROVIDE COMPLIANCE WITH 505.3 EGRESS |
| | 2.8) OPENNESS 505.4. |
| | |
| | 3) THE NEW OR MOVED MACHINERY WILL NEED TO SHOW |
| | COMPLIANCE WITH : |
| | 3A) 2010 FBC-B [F] 510.2.1 LUMBER YARDS AND WOODWORKING |
| | FACILITIES. |
| | EQUIPMENT OR MACHINERY LOCATED INSIDE BUILDINGS AT |
| | LUMBER YARDS AND WOODWORKING FACILITIES WHICH GENERATES |
| | OR EMITS COMBUSTIBLE DUST SHALL BE PROVIDED WITH AN |
| | APPROVED DUST-COLLECTION AND EXHAUST SYSTEM INSTALLED |
| | IN CONFORMANCE WITH THIS SECTION AND THE FLORIDA FIRE |
| | PREVENTION CODE. EQUIPMENT AND SYSTEMS THAT ARE USED TO |
| | COLLECT, PROCESS OR CONVEY COMBUSTIBLE DUSTS SHALL BE |
| | PROVIDED WITH AN APPROVED EXPLOSION-CONTROL |
| | SYSTEM. |
| | |
| | 3B) 2010 FBC-B 511.1 DUST, STOCK AND REFUSE CONVEYING |
| | SYSTEMS. |
| | DUST, STOCK AND REFUSE CONVEYING SYSTEMS SHALL COMPLY |
| | WITH THE PROVISIONS OF SECTION 510 AND SECTIONS 511.1.1 |
| | THROUGH 511.2. UNLESS OTHERWISE SPECIFIED IN THIS |
| | SECTION, DUST, STOCK AND REFUSE CONVEYING SYSTEMS SHALL |
| | ALSO COMPLY WITH SECTION 510 AND NFPA 91. |
| | |
| | 3C) 2010 FBC-B F] 903.2.4.1 WOODWORKING OPERATIONS. AN |
| | AUTOMATIC SPRINKLER SYSTEM SHALL BE PROVIDED THROUGHOUT |
| | ALL GROUP F-1 OCCUPANCY FIRE AREAS THAT CONTAIN |
| | WOODWORKING OPERATIONS IN EXCESS OF 2,500 SQUARE FEET |
| | (232 M2) IN AREA WHICH GENERATE FINELY DIVIDED |
| | COMBUSTIBLE WASTE OR USE FINELY DIVIDED COMBUSTIBLE |
| | MATERIALS. |
| | |
| | 4) THERE IS A TECHNICAL SHEET MARKED AS EQUIPMENT # 27 |
| | PLEASE PROVIDE THIS SHEET IN ENGLISH. 107.2.1.4 QUALITY |
| | OF BUILDING PLANS. THE BUILDING OFFICIAL MAY ESTABLISH |
| | THROUGH DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS |
| | AND SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO |
| | ITS RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE |
| | SUCH THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, |
| | OR OTHER ITEMS RELATED TO RECORDS MANAGEMENT. |
| | ELECTRONIC MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE |
| | REQUIREMENTS OF FLORIDA STATUTES. |
| | |
| | 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |