| 2015-04-29 08:28:56 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 15020419 |
| | ADD: 1309 N. FLAGLER DR. / ADDITION |
| | 1300 N. DIXIE HWY. |
| | 74/43/43/15/19/001/0010 |
| | CONT: TBD |
| | TEL: (239)594-1994 |
| | CONTACT: ??????? NOT FILLED IN ON FORM |
| | E-MAIL: [email protected] |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | GOOD SAMARITAN MEDICAL CENTER O?KEEFEE TOWER VERTICAL |
| | ADDITION |
| | 1ST REVIEW |
| | DATE: TUES. APRIL 28 |
| | ACTION: DENIED |
| | |
| | 1) THE DRAWING INDEX SHEET X1.1 IS NOT IN ORDER AS |
| | DESCRIBED ON SHEET X1.1. A INDEX IN GENERAL CAN BE |
| | LISTED (2) WAYS, BY ALPHABETICAL LIST AS IN A |
| | DICTIONARY OR BY A LIST OF ITEMS (AS TOPICS OR NAMES) |
| | TREATED IN A PRINTED WORK THAT GIVES FOR EACH ITEM THE |
| | PAGE NUMBER WHERE IT MAY BE FOUND . |
| | IT APPEARS THAT NEITHER HAS BEEN FOLLOWED COMPLETELY. |
| | IN THE ARCHITECTURAL SHEETS THE PAGES ARE NOT |
| | SEQUENTIALLY IN ORDER, THE DRAWING INDEX LIST IS |
| | MISSING A S-5.3.1 SHEET, LOCATED AFTER THE |
| | ARCHITECTURAL SHEETS. IT IS VERY, VERY TIME CONSUMING |
| | WHEN THE PLANS ARE NOT IN ORDER OF THE INDEX, TRYING TO |
| | LOCATE A PARTICULAR SHEET, WE HAVE NO WAY OF FINDING A |
| | CERTAIN SHEET IN A TIMELY MANNER. |
| | |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, |
| | 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | ELECTRONIC MEDIA DOCUMENTS SHALL BE |
| | SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL. |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED. |
| | |
| | 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS |
| | SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON |
| | SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM. |
| | THE BUILDING OFFICIAL MAY ESTABLISH THROUGH |
| | DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND |
| | SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS |
| | RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH |
| | THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR |
| | OTHER ITEMS RELATED TO RECORDS MANAGEMENT. ELECTRONIC |
| | MEDIA MUST BE COMPATIBLE WITH THE ARCHIVE REQUIREMENTS |
| | OF FLORIDA STATUTES. |
| | |
| | BEFORE THE NEXT ELECTRONIC SUBMITTAL PLEASE CONTACT THE |
| | ELECTRONIC DIGITAL LIBERIAN CAROLINE PUELL FOR FURTHER |
| | INSTRUCTIONS. CITY STAFF WILL HAVE TO PUT THE PAGES IN |
| | ORDER TO MATCH THE DRAWING INDEX SHEET. THE OTHER ISSUE |
| | IS THE NAMING CONVENTION THE CITY HAS RECOMMENDED WAS |
| | NOT USED EITHER AND THE CITY STAFF WILL ALSO NEED TO |
| | CLEAN UP THIS MATTER BEFORE THE NEXT UPLOAD CAN BE |
| | COMPLETED AND GIVEN OUT TO THE PLAN REVIEWERS. PLEASE |
| | CONTACT CAROLINE PUELL LIBERIAN FOR HOW THE RENAMING OF |
| | THE FILES WILL HAPPEN AND TO WHAT SHEETS THE RENAMING |
| | CONVENTION STARTS. |
| | |
| | 2) ART IN PUBLIC PLACES. THE CITY OF WEST PALM BEACH |
| | ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES |
| | TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH |
| | THE PERMIT APPLICATION WAS SUBMITTED AFTER 7/1/14, AND |
| | THE TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR |
| | GREATER THAN $500,000. PER CITY OF WEST PALM BEACH |
| | ORDINANCE NO. 4504-14, AND CITY OF WEST PALM BEACH CODE |
| | OF ORDINANCES, ARTICLE V, ART IN PUBLIC PLACES, SECTION |
| | 78-123(A) AND SECTION 78-126(A), THE ART ASSESSMENT IS |
| | 1% OF THE TOTAL PROJECT CONSTRUCTION COST. |
| | |
| | PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE |
| | V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND |
| | NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO |
| | THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE |
| | PROJECTS |
| | |
| | 3) ASBESTOS: IN ACCORDANCE WITH SECTION 553.79 F. S. |
| | THIS IS TO ADVISE YOU OF THE OWNERS OR OPERATORS? |
| | RESPONSIBILITY TO COMPLY WITH THE STATE & FEDERAL |
| | ASBESTOS REGULATIONS, INCLUDING SECTION 376.60 F. S. |
| | AND CFR 61- NESHAP REQUIREMENTS. REQUIREMENTS INCLUDE- |
| | ASBESTOS SURVEYS AND SUBMISSION OF WRITTEN NOTIFICATION |
| | TO THE DEPARTMENT OF ENVIRONMENTAL PROTECTION PRIOR TO: |
| | * DEMOLITION OF ALL REGULATED STRUCTURES; |
| | * MOST RENOVATION ACTIVITIES IN REGULATED STRUCTURES |
| | WHERE ASBESTOS IS DISTURBED OR REMOVED. |
| | NON-COMPLIANCE MAY RESULT IN SEVERE MONETARY PENALTY. |
| | |
| | FOR FURTHER INFORMATION IN PALM BEACH COUNTY, CONTACT |
| | THE DIVISION OF ENVIRONMENTAL HEALTH AND ENGINEERING |
| | HRS/ PALM BEACH COUNTY PUBLIC HEALTH UNIT |
| | (DIVISION OF ENGINEERING SCIENCE & ENGINEERING AIR |
| | POLLUTION CONTROL SECTION) |
| | |
| | 901 EVERNIA STREET |
| | WEST PALM BEACH, FL 33401 |
| | (561)355-3070 |
| | |
| | 4) THIS BUILDING QUALIFIES AS A THRESHOLD BUILDING. |
| | THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) ?THRESHOLD |
| | BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN |
| | (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN |
| | ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN |
| | AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500 |
| | PERSONS. |
| | |
| | 4A)COMPLIED> 109.3.6.1 THE ENFORCING AGENCY SHALL |
| | REQUIRE A (WRITTEN/ TYPED) SPECIAL INSPECTOR TO PERFORM |
| | STRUCTURAL INSPECTIONS ON A THRESHOLD BUILDING PURSUANT |
| | TO A STRUCTURAL INSPECTION PLAN PREPARED BY THE |
| | ENGINEER OF RECORD. THE STRUCTURAL INSPECTION PLAN MUST |
| | BE SUBMITTED TO THE ENFORCING AGENCY PRIOR TO THE |
| | ISSUANCE OF A BUILDING PERMIT FOR THE CONSTRUCTION OF A |
| | THRESHOLD BUILDING. THE PURPOSE OF THE STRUCTURAL |
| | INSPECTION PLAN IS TO PROVIDE SPECIFIC INSPECTION |
| | PROCEDURES AND SCHEDULES SO THAT THE BUILDING CAN BE |
| | ADEQUATELY INSPECTED FOR COMPLIANCE WITH THE PERMITTED |
| | DOCUMENTS. |
| | |
| | 4B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD |
| | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S |
| | 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS |
| | REQUIRED BY THIS CODE. FORMS MUST BE FILED OUT AND |
| | RETURNED TO THE BBUILDING DEPARTMENT CAN ISSUE A |
| | PERMIT. CONTACT KEN CONRAD MANAGER OF THE SPECIAL |
| | INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER |
| | INFORMATION BEFORE THE PERMIT MAY BE ISSUED. |
| | FORMS WERE E-MAILED TO: [email protected] |
| | 4/28/2015 08:32 AM |
| | |
| | 4C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B. |
| | AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH |
| | ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT |
| | OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE |
| | BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE |
| | PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE |
| | FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| | AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| | FLORIDA STATUTE. |
| | |
| | 4D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' |
| | OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE |
| | RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| | AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | CONTACT KEN CONRAD |
| | TEL: 561-805-6666 |
| | E-MAIL: [email protected] |
| | |
| | 4E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| | HISTORY FOR THIS TYPE OF CONSTRUCTION. THIS MAY BE |
| | SUBMITTED TO KEN CONRAD BY E-MAIL. KEN CONRAD: |
| | [email protected] |
| | |
| | 4F) NOTICE ONLY, NO ACTION NEED TO BE TAKEN FOR PLAN |
| | REVIEW. PAPER PLANS 3 SETS OF DOCUMENTS ARE REQUIRED. |
| | FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, THE PERMIT |
| | LIBRARIAN WILL E-MAIL YOU, THE APPROVED AND BATCH |
| | STAMPED PLANS SO YOU MAY PRINT YOUR PLANS, TWO SETS OF |
| | PLANS WILL NEED TO BE PRINTED IN COLOR, (1) FOR THE |
| | THRESHOLD INSPECTOR, THE OTHER FOR THE MEP INSPECTORS. |
| | |
| | 4G) NOTICE ONLY, NO ACTION NEED TO BE TAKEN FOR PLAN |
| | REVIEW. PLEASE CALL THE CITY OF WEST PALM BEACH?S |
| | AUTOMATED TELEPHONE INSPECTIONS LINE (561) 805-6700) |
| | FOR IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE |
| | INSPECTIONS. |
| | |
| | 4H) NOTICE ONLY, NO ACTION NEED TO BE TAKEN FOR PLAN |
| | REVIEW. SECTION 109.3.6 THRESHOLD BUILDINGS, OPERATING |
| | GUIDELINES FOR THRESHOLD INSPECTORS #26. ASSURE THAT |
| | THE DESIGNER HAS REQUIRED ON THE PLANS OR |
| | SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING |
| | PENETRATIONS, FOR WALLS AND CEILINGS. |
| | |
| | 5) THIS PROPERTY IS LOCATED IN AN A5 FLOOD ZONE. FBC |
| | BUILDING 1612 AND CITY OF WPB CODE OF ORDINANCES |
| | SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD |
| | ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. |
| | PLEASE REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS |
| | REQUIRE AN ADDITIONAL 6 INCHES OF ELEVATION. |
| | |
| | 5A) DURING THE PERMITTING OF THIS STRUCTURE THERE WILL |
| | BE REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES |
| | REQUIRED: |
| | (1) A FLOOD ZONE CERTIFICATE IS REQUIRED AS PART OF THE |
| | PLAN REVIEW DOCUMENTS WITH THE PROPOSED FINISH FLOOR |
| | HEIGHT. |
| | (2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND |
| | ELEVATION CERTIFICATE IS REQUIRED |
| | (3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY |
| | OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE |
| | CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR |
| | ATTENDANTS |
| | A/C PADS OR OTHER SLABS FOR GENERATORS |
| | FEMA FORM OMB NO. 1660-0008 EXPIRES: |
| | JULY 31/2015 |
| | FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR |
| | USE, EFFECTIVE AUGUST 1/ 2013, THROUGH JULY 31/ 2015. |
| | FORM. ADDITIONAL INFORMATION ON THE DIFFERENCES, THE |
| | NEW FORM, AND INSTRUCTIONS ARE AVAILABLE AT: |
| | HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM. |
| | |
| | 5B) THIS SUBMITTAL NO SURVEYS WERE SUBMITTED, PLEASE |
| | NOTE IF THE BUILDING LOWEST LEVEL IS BELOW THE 7?-6? |
| | NGVD THE REQUIREMENTS FOR FLOOD PROOFING CITY MUNI CODE |
| | SECTION 94-546(B)(2) NONRESIDENTIAL CONSTRUCTION AND |
| | SECTION 94-611 DEFINITIONS FOR SUBSTANTIAL |
| | IMPROVEMENTS. |
| | 5C) 2010 FBC-B 419.4.2.2.2 FOR ALL EXISTING FACILITIES, |
| | THE LOWEST FLOOR ELEVATIONS OF ALL ADDITIONS, AND ALL |
| | PATIENT SUPPORT AREAS INCLUDING FOOD SERVICE, AND ALL |
| | PATIENT SUPPORT UTILITIES, INCLUDING MECHANICAL, AND |
| | ELECTRICAL (EXCEPT FUEL STORAGE AS NOTED IN SECTION |
| | 419.4.2.9.3 OF THIS CODE) FOR THE ADDITIONS SHALL BE AT |
| | OR ABOVE THE ELEVATION OF THE EXISTING BUILDING, IF THE |
| | EXISTING BUILDING WAS DESIGNED AND CONSTRUCTED TO |
| | COMPLY WITH EITHER THE SITE STANDARDS OF SECTION 419.4 |
| | OF THIS CODE OR LOCAL FLOOD RESISTANT REQUIREMENTS IN |
| | EFFECT AT THE TIME OF CONSTRUCTION, WHICHEVER REQUIRES |
| | THE HIGHER ELEVATION, UNLESS OTHERWISE PERMITTED BY |
| | SECTION 1612 OF THIS CODE. IF THE EXISTING BUILDING WAS |
| | CONSTRUCTED PRIOR TO THE ADOPTION OF EITHER THE SITE |
| | STANDARDS OF 419.4 OF THIS CODE OR LOCAL FLOOD |
| | RESISTANT REQUIREMENTS, THEN THE ADDITION AND ALL |
| | PATIENT SUPPORT AREAS AND UTILITIES FOR THE ADDITION AS |
| | DESCRIBED IN THIS SECTION SHALL EITHER BE DESIGNED AND |
| | CONSTRUCTED TO MEET THE REQUIREMENTS OF SECTION |
| | 419.4.2.2.1 OF THIS CODE OR BE DESIGNED AND CONSTRUCTED |
| | TO MEET THE DRY FLOOD PROOFING REQUIREMENTS OF SECTION |
| | 1612 OF THIS CODE. |
| | |
| | 6) PLEASE PROVIDE WHERE THIS INFORMATION CAN BE FOUND? |
| | NOT FOUND ON A.2.1 CODE CRITERIA NOR LIFE SAFETY |
| | SHEETS. 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION 107.3.5.1.1 |
| | COMMERCIAL BUILDINGS: |
| | 6.1OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS |
| | SHALL BE DETERMINED. |
| | 6.2 MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED |
| | (SEE TABLE 503). |
| | 6.3 FIRE SPRINKLERS ? REQUIRED? |
| | 6.4 2010 FBC-EXISTING BLDG. CODE CHAPTER 10 |
| | |
| | 7) PLEASE PROVIDE A SURVEY OF THE EXISTING SITE. ZONING |
| | COMMENT OF THE FOOTPRINT OF THE EXISTING BUILDINGS CAN |
| | NOT BE INCREASED. PLEASE PROVIDE THE SURVEY SO A |
| | COMPARISON OF THE PROPOSED VERTICAL ADDITION AND |
| | EXISTING BUILDING CAN BE COMPARED, VERTICAL ADDITIONS |
| | VERSES HORIZONTAL ADDITIONS. |
| | |
| | 2010 EXISTING BLDG. CODE 1001.2 CREATION OR EXTENSION |
| | OF NONCONFORMITY. |
| | AN ADDITION SHALL NOT CREATE OR EXTEND ANY |
| | NONCONFORMITY IN THE EXISTING BUILDING TO WHICH THE |
| | ADDITION IS BEING MADE WITH REGARD TO ACCESSIBILITY, |
| | STRUCTURAL STRENGTH, FIRE SAFETY, MEANS OF EGRESS, OR |
| | THE CAPACITY OF MECHANICAL, PLUMBING, OR ELECTRICAL |
| | SYSTEMS. |
| | EXST. BLDG. CODE 1002.1 HEIGHT LIMITATIONS. |
| | 1002.2 AREA LIMITATIONS. |
| | 1002.3 FIRE PROTECTION SYSTEMS. |
| | |
| | EXST. BLDG. CODE 1001.3 OTHER WORK. ANY REPAIR OR |
| | ALTERATION WORK WITHIN AN EXISTING BUILDING TO WHICH AN |
| | ADDITION IS BEING MADE SHALL COMPLY WITH THE APPLICABLE |
| | REQUIREMENTS OF THE APPROPRIATE CHAPTER OF THIS CODE |
| | FOR THE LEVEL OF REHABILITATION UNDERTAKEN. |
| | |
| | 8) 2010 FL. EXISTING BUILDING CODE PLEASE SHOW |
| | COMPLIANCE WITH: |
| | 8A) EXST. BLDG. CODE 1003.2 ADDITIONAL GRAVITY LOADS. |
| | EXISTING STRUCTURAL ELEMENTS SUPPORTING ANY ADDITIONAL |
| | GRAVITY LOADS AS A RESULT OF ADDITIONS SHALL COMPLY |
| | WITH THE FLORIDA BUILDING CODE, BUILDING. |
| | EXCEPTIONS: 1. STRUCTURAL ELEMENTS WHOSE STRESS IS NOT |
| | INCREASED BY MORE THAN 5 PERCENT. |
| | |
| | 8B) EXST. BLDG. CODE 1003.3 LATERAL-FORCE-RESISTING |
| | SYSTEM. THE LATERAL-FORCE-RESISTING SYSTEM OF EXISTING |
| | BUILDINGS TO WHICH ADDITIONS ARE MADE SHALL COMPLY WITH |
| | SECTIONS 1003.3.1, 1003.3.2 AND 1003.3.3. |
| | EXCEPTIONS: 1003 (2.) IN OTHER EXISTING BUILDINGS WHERE |
| | THE LATERAL-FORCE STORY SHEAR IN ANY STORY IS NOT |
| | INCREASED BY MORE THAN 10 PERCENT CUMULATIVE. |
| | |
| | 8C) PLEASE SEE SHEET S5.1 CODES AND STANDARDS WIND |
| | LOADS WERE DESIGNED TO 170 MPH VULT AND C EXPOSURE. |
| | |
| | 8C)(1) WIND DESIGN TO 170 MPH VULT. PLEASE REVIEW THE |
| | 2010 FBC-B TABLE 1604.5 RISK CATEGORY OF BUILDINGS AND |
| | OTHER STRUCTURES. RISK CATEGORY IV STRUCTURES INCLUDE |
| | GROUP I-2 OCCUPANCIES AND OTHER STRUCTURES DESIGNED AS |
| | ESSENTIAL FACILITIES HAVING SURGERY OR EMERGENCY |
| | TREATMENT FACILITIES. PLEASE REVIEW THE 2010 FBC-B |
| | TABLE 1609B FOR RISK CATEGORY III AND IV BUILDINGS AND |
| | STRUCTURES. THE FIGURE SHOWS THIS LOCATION AS A 180 |
| | MPH, VULT WIND ZONE. |
| | |
| | 2010 FBC-B 419.3 N ADDITION TO THE CODES AND STANDARDS |
| | REFERENCED IN SECTION 419.2 OF THIS CODE, THE FOLLOWING |
| | MINIMUM STANDARDS OF CONSTRUCTION AND SPECIFIED MINIMUM |
| | ESSENTIAL FACILITIES, SHALL APPLY TO ALL NEW HOSPITALS |
| | AND ALL ADDITIONS, ALTERATIONS OR RENOVATIONS TO AN |
| | EXISTING LICENSED HOSPITAL, AS DESCRIBED IN SECTION |
| | 419.1 OF THIS CODE AND LISTED IN SECTION 419.3 OF THIS |
| | CODE. |
| | |
| | 8C)(2) SHEET S5.1 WIND DESIGN OF C EXPOSURE. WHEN YOU |
| | SHOOT A VECTOR TO THE N.E. TO PALM BEACH COUNTRY CLUB A |
| | DISTANCE OF OVER 7,000 FT. OF WATER IS ENCOUNTERED, |
| | WHEN A VECTOR TO THE S. E. TO # 1 VIA SUNNY , PALM BCH. |
| | A DISTANCE OF 5,562 FT. IS ENCOUNTERED. DEPENDING ON |
| | WHERE THE DISTANCE FROM SHORELINE WITH NO OBSTRUCTIONS |
| | YOU GET 508FT, 588 FT. OR 414 FT. TO THE FRONT OF THE |
| | BUILDING. |
| | |
| | 2010 FBC-B 1609.4.3. EXPOSURE D. EXPOSURE D SHALL APPLY |
| | WHERE THE GROUND SURFACE ROUGHNESS, AS DEFINED BY |
| | SURFACE ROUGHNESS D, PREVAILS IN THE UPWIND DIRECTION |
| | FOR A DISTANCE OF AT LEAST 5,000 FEET (1524 M) OR 20 |
| | TIMES THE HEIGHT OF THE BUILDING, WHICHEVER IS GREATER. |
| | EXPOSURE D SHALL EXTEND INLAND FROM THE SHORELINE FOR A |
| | DISTANCE OF 600 FEET (183 M) OR 20 TIMES THE HEIGHT OF |
| | THE BUILDING, WHICHEVER IS GREATER FROM AN EXPOSURE D |
| | CONDITION AS DEFINED IN THE PREVIOUS SENTENCE. |
| | |
| | FBC-B HOSPITALS. 419.4.2.3 STRUCTURAL STANDARDS. |
| | WIND LOAD DESIGN OF THE BUILDING STRUCTURE AND EXTERIOR |
| | ENVELOPE INCLUDING EXTERIOR WALL SYSTEMS SHALL BE |
| | DESIGNED IN ACCORDANCE WITH THE CODE. |
| | |
| | 9) PLEASE PROVIDE COMPLIANCE WITH: 2010 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS & |
| | CLADDING. |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) EXTERIOR COOLER, FREEZERS & PRE-ENGINEERED A/C |
| | STANDS |
| | |
| | 9A) 2010 FBC-B 419.4.2.4 ROOFING STANDARDS. |
| | 419.4.2.4.1 |
| | ROOFING MEMBRANE MATERIAL SHALL RESIST THE UPLIFT |
| | FORCES SPECIFIED IN THE CODE. ROOF COVERINGS SHALL BE |
| | INSTALLED ACCORDING TO THE SPECIFICATIONS PROVIDED BY |
| | THE MANUFACTURER. |
| | 419.4.2.4.2 LOOSE-LAID BALLASTED ROOFS SHALL NOT BE |
| | PERMITTED. |
| | |
| | 419.4.2.4.3 ALL NEW ROOF APPENDAGES SUCH AS DUCTS, |
| | TANKS, VENTILATORS, RECEIVERS, DX CONDENSING UNITS AND |
| | DECORATIVE MANSARD ROOFS AND THEIR ATTACHMENT SYSTEMS |
| | SHALL BE STRUCTURALLY ENGINEERED TO MEET THE WIND LOAD |
| | REQUIREMENTS OF THE APPLICABLE BUILDING CODE. ALL OF |
| | THESE ATTACHMENT SYSTEMS SHALL BE CONNECTED DIRECTLY TO |
| | THE UNDERLYING ROOF STRUCTURE OR ROOF SUPPORT |
| | STRUCTURE. |
| | |
| | 9B) 2010 FBC-B 419.4.2.5 EXTERIOR UNIT STANDARDS. |
| | 419.4.2.5.1 |
| | ALL EXTERIOR WINDOW UNITS, SKYLIGHTS, EXTERIOR LOUVERS |
| | AND EXTERIOR DOOR UNITS INCLUDING VISION PANELS AND |
| | THEIR ANCHORING SYSTEMS SHALL BE IMPACT RESISTANT OR |
| | PROTECTED WITH AN IMPACT RESISTANT COVERING MEETING THE |
| | REQUIREMENTS OF THE TESTING APPLICATION STANDARDS (TAS) |
| | 201, 202, AND 203 OF THIS CODE IN ACCORDANCE WITH THE |
| | REQUIREMENTS OF SECTIONS 1626.2 THROUGH 1626.4 OF THIS |
| | CODE. THE IMPACT RESISTANT COVERINGS MAY BE EITHER |
| | PERMANENTLY ATTACHED OR MAY BE REMOVABLE IF STORED ON |
| | SITE OF THE FACILITY. |
| | |
| | 10) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE |
| | PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 11) ONCE THE WIND DESIGN & PRESSURES ARE CODE COMPLIANT |
| | IF EITHER THE DESIGNER OF RECORD OR CONTRACTOR WOULD |
| | PREFER TO SUBMIT THE PRODUCT APPROVALS AFTER THE |
| | ISSUANCE OF THE PERMIT THROUGH: |
| | 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS |
| | SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| | PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| | TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| | THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| | DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| | APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| | THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| | FOR REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR |
| | DEFERRED SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE |
| | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | WHO SHALL REVIEW THEM AND FORWARD THEM TO THE BUILDING |
| | OFFICIAL WITH A NOTATION INDICATING THAT THE DEFERRED |
| | SUBMITTAL DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE |
| | IN GENERAL CONFORMANCE TO THE DESIGN OF THE BUILDING. |
| | THE DEFERRED SUBMITTAL ITEMS SHALL NOT BE INSTALLED |
| | UNTIL THE DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN |
| | APPROVED BY THE BUILDING OFFICIAL. |
| | |
| | 12) SHEET A1.1 THE MAIN LOBBY-192 SHOWS AN EXIT |
| | DIRECTIONAL SIGN FOR EXITING THROUGH THE ELEVATOR LOBBY |
| | 193. THE SOUTH END OF THE ELEVATOR LOBBY DOES NOT SHOW |
| | AN ENCLOSURE AS DOES THE ELEVATOR LOBBY JUST TO THE |
| | EAST ELEVATOR LOBBY 195 SHEET A5.3 THIS AREA SEEMS TO |
| | BE ATRIUM OVERLOOK AREA. THE 2010 FBC-B 708.14.1 |
| | EXCEPTION 4 DOES NOT APPLY TO GROUP I-2 OCCUPANCIES. |
| | ALSO SEE FLORIDA BUILDING CODE INFORMAL INTERPRETATION: |
| | DATE: WED SEP 7 2005 |
| | REPORT #: 3887 |
| | CODE: BUILDING |
| | SECTION: 707.14.1 |
| | QUESTION: |
| | CAN THE PATH OF EXIT TRAVEL GO FROM AN EXIT ACCESS |
| | CORRIDOR THROUGH AN ELEVATOR LOBBY TO THE EXIT STAIRS? |
| | ANSWER: |
| | NO, THE SECTION SPECIFICALLY REQUIRES A LOBBY OF FIRE |
| | RATED CONSTRUCTION TO SEPARATE THE ELEVATOR FROM THE |
| | CORRIDOR BY FIRE RATED PARTITIONS AND PROTECTED |
| | OPENING(S). |
| | COMMENTARY: |
| | NONE. |
| | NOTICE: |
| | THE BUILDING OFFICIALS ASSOCIATION OF FLORIDA, IN |
| | COOPERATION WITH THE FLORIDA BUILDING COMMISSION, THE |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, ICC, AND |
| | INDUSTRY AND PROFESSIONAL EXPERTS OFFER THIS |
| | INTERPRETATION OF THE FLORIDA BUILDING CODE IN THE |
| | INTEREST OF CONSISTENCY IN THEIR APPLICATION STATEWIDE. |
| | THIS INTERPRETATION IS INFORMAL, NON-BINDING AND |
| | SUBJECT TO ACCEPTANCE AND APPROVAL BY THE LOCAL |
| | BUILDING OFFICIAL. |
| | |
| | 13) SHEET A1.1 NOTE THIS IS THE LIFE SAFETY PLAN, THERE |
| | IS NO DIMENSIONAL PLAN IN THE 1ST OR 2ND FLOORS. ON |
| | SHEET A1.1 THE SOILED LAUNDRY ROOM NOT DIMENSIONED MAY |
| | HAVE A ACCESSIBILITY ISSUE WITH DOORS IN SERIES, 2010 |
| | FLORIDA ACCESSIBILITY CODE 404.2.6. |
| | |
| | 13A) THE PLANS INDICATE THAT THE ADDITION IS BEING |
| | BUILT AS UNDER THE HIGH-RISE PROVISIONS OF THE CODE FOR |
| | THE ADDITIONAL STORIES TO BE ADDED ON IN THE FUTURE. |
| | DOES THE BUILDING CURRENTLY CONTAIN A FIRE COMMAND |
| | CENTER (FBC-B 403.4.5) IN COMPLIANCE WITH FBC-B SECTION |
| | 911? ] 911.1.1 LOCATION AND ACCESS. THE LOCATION AND |
| | ACCESSIBILITY OF THE FIRE COMMAND CENTER SHALL BE |
| | APPROVED BY THE FIRE CHIEF. |
| | |
| | 13B) IS THIS ADDITION ONLY TO MEET THE HIGH-RISE |
| | REQUIREMENTS (FBC-B SECTION 403) OR WILL THE WHOLE |
| | FACILITY MEET THE HIGH RISE REQUIREMENTS SINCE THE |
| | PLANS DO NOT SHOW A 4 HOUR FIRE WALL SECTION 706? |
| | |
| | 13C) DOES THIS FACILITY OR ADDITION HAVE A HYPERBARIC |
| | FACILITIES (FBC-B 407.9) HYPERBARIC FACILITIES IN GROUP |
| | I-2 OCCUPANCIES SHALL MEET THE REQUIREMENTS CONTAINED |
| | IN CHAPTER 20 OF NFPA 99. |
| | |
| | 13D) PLEASE SHOW COMPLIANCE WITH FBC-B 419.4.2.11 |
| | EXTERNAL EMERGENCY COMMUNICATIONS STANDARDS. |
| | (REFERENCE CHAPTER 59A-3.081 FLORIDA ADMINISTRATIVE |
| | CODE FOR REQUIREMENTS.) |
| | |
| | 13E) PLEASE PROVIDE WHICH OPTION THE SITE HAS CHOSEN AS |
| | AN OPTION, SHOW COMPLIANCE WITH; |
| | FBC-B 419.4.2.10.1 IF THE FACILITY REQUIRES FIRE |
| | SPRINKLERS AS PART OF ITS FIRE PROTECTION, EITHER OF |
| | THE FOLLOWING SHALL BE MET: AND WHO WILL PERFORM THE |
| | FIRE WATCH IF THIS METHOD IS CHOSEN. |
| | |
| | 14) SHEET A1.1 VS. A1.2, SHEET A1.2 THE 2ND LEVEL SHOWS |
| | A TEMPORARY STAIR TOWER AND TEMPORARY BUCK-HOIST |
| | LOCATION NOT SHOWN ON THE 1ST FLOOR PLANS. PLEASE |
| | PROVIDE HOW WILL THE OCCUPANTS BE PROTECTED DURING |
| | CONSTRUCTION AND IN COMPLIANCE WITH FBC-B 3306.7 |
| | COVERED WALKWAYS. THE TEMPORARY STAIRS DOES NOT ADDRESS |
| | THIS ISSUE OF THE EXITING OF THE 1ST FLOOR |
| | |
| | 15) SHEET A1.1 VS. A1.2, SHEET A1.2 THE 2ND FLOOR LEVEL |
| | ALSO SHOWS THE 2ND FLOOR TO BE A ATRIUM, THE PLANS ARE |
| | NOT CLEAR AS TO ON THE 2ND LEVEL IF THIS IS A HANDRAIL |
| | OR A 1 HOUR GLASS WALL WITH FIRE SPRINKLERS, THIS IS AN |
| | EXIT ACCESS CORRIDOR THAT WOULD NEED TO BE PROTECTED. |
| | FBC-B 404.6. |
| | |
| | 16) SHEET A1.2 ALSO INDICATES THAT THIS EXIT WILL BE |
| | TEMPORARILY CLOSED AND THE EXIT SIGN REMOVED. PLEASE |
| | PROVIDE A CODE COMPLIANT EXIT PLAN DURING THE TIME THE |
| | EXIT WILL NOT BE AVAILABLE. IN ESSENCE IT CREATES A |
| | DEAD END FOR BOTH THE NORTH AND SOUTH CORRIDORS. FBC-B |
| | 1018.4. |
| | |
| | 17) LIFE SAFETY SHEET A1.3 & SHEET A5.3A SHOW 1 HOUR |
| | FIRE RATED WALLS: |
| | |
| | 17A) STAFF CORRIDOR 317 SHOWS (2) A TYPE DOORS WITH |
| | CARD ENTRY. DOOR FROM CORRIDOR TO PREP & PACKING AREA |
| | ON THE DOOR SCHEDULE IS MISSING 45 MIN. RATING PER |
| | FBC-B TABLE 715.4. |
| | |
| | 17B) DOOR FROM STAFF CORRIDOR TO CART WASH AREA |
| | (LABELED A) IS NOT ON THE DOOR SCHEDULE. 107.2.1.3 |
| | ADDITIONAL INFORMATION/ FBC-B TABLE 715.4. |
| | |
| | |
| | 17C) SHEET A5.3A THE DOORS TO ROOMS 323, 324,& 340 ARE |
| | NOT LABELED NOR SHOW UP ON THE DOOR SCHEDULE? 107.2.1.3 |
| | ADDITIONAL INFORMATION IS REQUIRED. FBC-B TABLE 715.4. |
| | |
| | 17D) THE DUMBWAITER LOCATED WITHIN CORRIDOR 304A SHOWS |
| | A (2 HOUR SHAFT) BUT THE DOOR SCHEDULE DOES NOT |
| | INDICATE A DOOR WITH 1 ? HOUR OPENING PROTECTIVE. 2010 |
| | FBC-B TABLE 715.4. |
| | |
| | 17E) WITHIN ROOM 305 HOLD/ STORAGE ROOM SHOWS A |
| | DUMBWAITER WITH A 2 HOUR FIRE RATING, THE DOOR SCHEDULE |
| | DOES NOT PROVIDE OPENING PROTECTIVE IN ACCORDANCE WITH |
| | 2010 FBC-B TABLE 715.4. |
| | |
| | 17F) ROOM 306 BREAKDOWN ROOM THERE ARE NO DIMENSIONS ON |
| | THIS PLAN, MAY OR MAY NOT COMPLY WITH 2010 FLORIDA |
| | ACCESSIBILITY CODE 404.2.6. |
| | |
| | 17G) NOTE DOES THE OVERLOOK 330 & 569 HAVE 1 HOUR |
| | PROTECTION IS THIS CONSIDERED PART OF AN ATRIUM? THERE |
| | IS NO 2ND FLOOR PLANS IN THE 500 SERIES DRAWINGS IS |
| | THIS A ATRIUM A 3 STORY ATRIUM REQUIRING SMOKE CONTROL |
| | A NOTE ON THE PLANS INDICATES A PRIVATE BRIDGE BELOW? |
| | FBC-B 404.5. SHEET A5.5A THE 5TH LEVEL, SECTION 404.6 |
| | EXCEPTION # 3 ONLY ALLOWS FOR THE ADJACENT SPACES OF |
| | ANY THREE FLOORS OF THE ATRIUM SHALL NOT BE REQUIRED TO |
| | BE SEPARATED FROM THE ATRIUM WHERE SUCH SPACES ARE |
| | ACCOUNTED FOR IN THE DESIGN OF THE SMOKE CONTROL |
| | SYSTEM. NOTE THIS IS THE 5TH LEVEL OF THE BUILDING. |
| | |
| | 18) SHEET A5.4A: THIS SHEET SHOWS A 2 FT. DIFFERENCE IN |
| | ELEVATION AT THE NEW 2 HR. SHAFT. THE DETAIL INDICATED |
| | ON SECTION 3 OF A11.3 DOES NOT SHOW WHERE THE 2 FT. |
| | ELEVATION CHANGES WITHIN THE DETAIL CONFIGURATION. IT |
| | SHOWS THE BLOCK SHAFT THAT WAS REMOVED. AS BUILT IT |
| | APPEARS THAT THERE WILL BE A 2 ? INCH PIECE OF SHAFT |
| | LINER PANEL, THIS WOULD BE DIFFICULT FOR THE INSTALLER |
| | TO CUT MAINTAIN THE INTEGRITY OF THE LINER PANEL. IS |
| | THERE A MINIMUM WIDTH THE MANUFACTURER RECOMMENDS FOR |
| | ONE INCH SHAFT WALL? |
| | |
| | 18A) THE DRINKING FOUNTAINS IN FRONT OF RESTROOMS 417 & |
| | 418 (COMMON STATEMENT FOR THE 4TH & 5TH FLOOR WHERE |
| | DRINKING FOUNTAINS ARE IN THIS CONFIGURATION) ARE NOT |
| | PROTECTED BY WING WALLS, SHEET A16.1 THE LOW DRINKING |
| | FOUNTAIN MEETS THE REQUIREMENTS OF THE FL. ACCESS. CODE |
| | 307.2 PROTRUDING OBJECTS BUT THE HIGH DRINKING FOUNTAIN |
| | WILL END UP WITH THE BOTTOM OF THE UNIT ABOVE 27 |
| | INCHES, EITHER A WING WALL OR SKIRT WOULD BE REQUIRED |
| | FOR CODE COMPLIANCE WITH 307.2 OR BY ANY METHOD THAT |
| | MEETS CODE COMPLIANCE. 2010 FBC-B FIRE-RESISTANT JOINT |
| | SYSTEMS SECTION 714,1 EXCEP. 2 . FLOORS WHERE THE JOINT |
| | IS PROTECTED BY A SHAFT ENCLOSURE IN ACCORDANCE WITH |
| | SECTION 708. |
| | |
| | 18B) THE (2) NEW DUMBWAITERS ON THIS FLOOR SHOW A 2 |
| | HOUR FIRE RATED WALL, DOES THE DUMBWAITER STOP ON THIS |
| | FLOOR, THERE APPEARS TO BE NO DOORWAY? 107.2.1.3 |
| | ADDITIONAL INFORMATION & FBC-B 715.4 OPENING |
| | PROTECTIVE. |
| | |
| | 18C) NOTE IN BOTH AREAS OF MECHANICAL ROOM 403 & 404 |
| | THERE ARE CHASES IN THE FLOOR UNPROTECTED THE PLANS |
| | INDICATE THEY ARE TO BE FOR HVAC, PLEASE IDENTIFY THE |
| | TYPE OF FIRE RATED ASSEMBLIES TO PROTECT THE FLOOR OR |
| | HORIZONTAL FIRE BARRIER. FBC-B 713.4 HORIZONTAL |
| | ASSEMBLIES. |
| | |
| | 19) SHEET A5.5A : |
| | |
| | 19A) ALUMINUM SUN SHADE DEVICES WILL NEED TO SHOW |
| | ENGINEERING (DESIGN AND ANCHORING) FOR THE APPROPRIATE |
| | WIND SPEED WITH EXPOSURE D WITH HEIGHT MULTIPLIERS. |
| | ASCE 7-10. |
| | |
| | 19B) DUMBWAITERS BOTH THE SOILED DUMBWAITER FOUND IN |
| | ROOM 526 AND THE O. R. DUMBWAITER DO NOT SHOW THE 90 |
| | MINUTE OPENING PROTECTIVE AS REQUIRED BY FBC-B TABLE |
| | 715.4 OPENING PROTECTIVE. |
| | |
| | 19C) PLEASE PROVIDE THE MANUFACTURERS SPECIFICATION |
| | SHEETS FOR THE DUMBWAITERS IN ACCORDANCE WITH 3001.5.1 |
| | FLORIDA ELEVATOR SAFETY CODE AND 3001.2 REFERENCED |
| | STANDARDS. |
| | |
| | 19D) PLEASE SHOW COMPLIANCE WITH FBC-B 3004.3 AREA OF |
| | VENTS. |
| | |
| | 20) SHEET A5.6A DIMENSION PLAN. APPEARS NOT TO BE |
| | COMPLETE, SOME OF THE WALLS ARE DIMENSIONED, MANY ARE |
| | NOT, THERE IS NO WALL IDENTIFICATION AS TO TYPE OF WALL |
| | RATINGS AND THE SAME WITH THE DOORS. SHEET A1.6 THE |
| | LIFE SAFETY SHEET SHOWS FUTURE ROOMS ON THE WEST END |
| | ONLY. 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 21) ON SHEETS A11.3 & A11.4 THE DETAIL BUBBLES ARE NOT |
| | FILED IN, DETAIL AND SHEET. 107.2.1.3 ADDITIONAL |
| | INFORMATION IS REQUIRED. |
| | |
| | 22) SHEET A16.1 DETAIL FOR ACCESSIBLE DRINKING |
| | FOUNTAINS DEPENDING ON THE ACTUAL LOCATION THE UPPER |
| | DRINKING FOUNTAIN MAY OR MAY NOT NEED A SKIRT/ GUARD TO |
| | COMPLY WITH THE 2010 FLORIDA ACCESSIBILITY CODE SECTION |
| | 307.2 PROTRUDING OBJECTS. IT APPEARS THE BOTTOM OF THE |
| | UPPER SHROUD UNIT WILL BE ABOVE THE REQUIRED 27 INCHES. |
| | |
| | 23) SHEETS A13.1 AND A13.5 BOTH SHOW WALL DETAILS AND |
| | PENETRATIONS FOR RATED WALLS. THE PLANS DO NOT PROVIDE |
| | FIRE RESISTANCE RATED ASSEMBLIES FOR HORIZONTAL |
| | ASSEMBLIES AND COMPLIANCE WITH FBC-B 713.4.1.1 THROUGH |
| | PENETRATIONS. |
| | |
| | 24) IMPACT FEES BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| | ISSUED, IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. |
| | THE ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 25) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |