Plan Review Details - Permit 15020296
Plan Review Stops For Permit 15020296
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2015-07-05 Cont ID  
Sent By shill Date 2015-07-05 Time 15:11 Rev Time 0.00
Received By shill Date 2015-07-05 Time 15:11 Sent To Z
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2015-04-14 Cont ID  
Sent By shill Date 2015-04-14 Time 07:06 Rev Time 0.00
Received By shill Date 2015-04-14 Time 07:06 Sent To  
Notes
2015-04-14 07:15:46****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. AS DRAWN, THE FOOTER WILL ENCROACH THE PROPERTY
 LINE.
  
 EITHER REVISE THE WALL DETAIL (ECCENTRIC FOOTER) OR
 REVISE THE SITE PLAN TO SHOW THE FOOTER IN RELATION TO
 THE PROPERTY LINE.
  
 2ND COMMENT ADDED ON 4/16:
  
 2. WHEN RESUBMITTING, PLEASE PROVIDE AN EMAIL ADDRESS.
 AN ATTEMPT WAS MADE TO CALL TO INFORM THAT THE PLAN WAS
 DENIED, BUT THE CALLER WAS UNABLE TO LEAVE A MESSAGE.
 FOR YOUR CONVENIENCE, PROVIDE AN EMAIL ADDRESS SO YOU
 CAN BE NOTIFIED WHEN THE NEXT REVIEW CYCLE IS COMPLETE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-03-06 Cont ID  
Sent By shill Date 2015-03-06 Time 17:34 Rev Time 0.00
Received By shill Date 2015-03-06 Time 17:34 Sent To  
Notes
2015-03-06 17:36:44COMMENTS FROM PREVIOUS LIST, NOT ADDRESSED:
  
  
 BUILDING PLAN REVIEW
 PERMIT: 15020296
 ADD: 750 HOLLYWOOD PL.
 CONT: O/B MENDEZ, LEONOKILDA
 TEL: (561)914-1749
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 IMPORTANT NOTICE: EFFECTIVE MAY 11, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE
  
  
 1) ONLY A SITE PLANS WAS SUBMITTED. 2010 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION, :
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES.
  
 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS MANAGEMENT.
  
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.3 RESIDENTIAL (ONE AND TWO-FAMILY)
 SITE REQUIREMENTS
 SET BACK/SEPARATION (ASSUMED PROPERTY LINES)
 STRUCTURAL REQUIREMENTS SHALL INCLUDE:
 DESIGN LOADS
 WALL SECTION FROM FOUNDATION THROUGH THE TOP OF THE
 MASONRY WALL.
 WIND REQUIREMENTS
 FOUNDATION/ WALL SYSTEMS MISSING THE SIZE OF THE
 FOUNDATION, SIZE AND QUANITY OF REINFORCING BARS IN THE
 FOUNDATION, COLUMNS AND BEAM, MINIMUM STRENGTH OF THE
 CONCRETE, / GROUT OR PUMP MIX, FOUNDATION DISTANCE FROM
 THE PROPERTY LINE, IF THE FOUNDATION IS TO BE OFFSET,
 AND SIZED TO RESIST THE MOMENT OF OVERTURNING.
  
 THE DESIGNER OF RECORD HAS NOT INDICATED IF THE
 PROPOSED WALL IS TO BE USED AS A RETAINING WALL? IF SO
 THE PLACEMENT OF THE VERTICAL STEEL AND SIZE OF STEEL
 WILL NEED TO BE ENGINEERED AS WELL AS THE FOOTER.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-02-24 Cont ID  
Sent By jwitmer Date 2015-02-24 Time 15:53 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2015-02-24 15:53:37BUILDING PLAN REVIEW
 PERMIT: 15020296
 ADD: 750 HOLLYWOOD PL.
 CONT: O/B MENDEZ, LEONOKILDA
 TEL: (561)914-1749
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 IMPORTANT NOTICE: EFFECTIVE MAY 11, 2015
 ALL PERMIT APPLICATION PLAN REVIEWS WILL BE PERFORMED
 ELECTRONICALLY
 UPON APPLICATION AND FEE PAYMENT DESIGN DOCUMENTS
 SUBMISSION OPTIONS ARE AS FOLLOWS:
 1 UPLOAD VIA THE PROJECTDOX PORTAL WITH DIGITAL
 SIGNATURES OF DESIGN PROFESSIONALS AS APPLICABLE; USE
 THE REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 2 INCLUDE ON A CD IF DESIGN PROFESSIONAL DIGITAL
 SIGNATURES ARE PROVIDED AS REQUIRED; USE THE REQUIRED
 NAMING CONVENTION FOR EACH DOCUMENT
 3 INCLUDE ON A CD WITH ONE SET OF TRADITIONAL PAPER
 DESIGN DOCUMENTS SIGNED AND SEALED AS REQUIRED; USE THE
 REQUIRED NAMING CONVENTION FOR EACH DOCUMENT
 4 ONE SET OF TRADITIONAL PAPER DESIGN DOCUMENTS SUBJECT
 TO ADMINISTRATIVE FEES TO DIGITIZE THE DOCUMENTS
 ADDITIONAL INFORMATION WILL BE PROVIDED WHEN IT BECOMES
 AVAILABLE
  
 1ST REVIEW
 DATE: TUES. FEB. 24/2015
 ACTION: DENIED
  
 1) ONLY A SITE PLANS WAS SUBMITTED. 2010 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATION, :
  
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL
 CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE,
 AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS
 ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES.
  
 107.2.1.4 QUALITY OF BUILDING PLANS. BUILDING PLANS
 SHALL BE DRAWN TO A MINIMUM 1/8 INCH SCALE UPON
 SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE MEDIUM.
 THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, OTHER STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. THIS POLICY MAY INCLUDE SUCH
 THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, CLARITY, OR
 OTHER ITEMS RELATED TO RECORDS MANAGEMENT.
  
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.3 RESIDENTIAL (ONE AND TWO-FAMILY)
 SITE REQUIREMENTS
 SET BACK/SEPARATION (ASSUMED PROPERTY LINES)
 STRUCTURAL REQUIREMENTS SHALL INCLUDE:
 DESIGN LOADS
 WALL SECTION FROM FOUNDATION THROUGH THE TOP OF THE
 MASONRY WALL.
 WIND REQUIREMENTS
 FOUNDATION/ WALL SYSTEMS MISSING THE SIZE OF THE
 FOUNDATION, SIZE AND QUANITY OF REINFORCING BARS IN THE
 FOUNDATION, COLUMNS AND BEAM, MINIMUM STRENGTH OF THE
 CONCRETE, / GROUT OR PUMP MIX, FOUNDATION DISTANCE FROM
 THE PROPERTY LINE, IF THE FOUNDATION IS TO BE OFFSET,
 AND SIZED TO RESIST THE MOMENT OF OVERTURNING.
  
 THE DESIGNER OF RECORD HAS NOT INDICATED IF THE
 PROPOSED WALL IS TO BE USED AS A RETAINING WALL? IF SO
 THE PLACEMENT OF THE VERTICAL STEEL AND SIZE OF STEEL
 WILL NEED TO BE ENGINEERED AS WELL AS THE FOOTER.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2015-06-16 Cont ID  
Sent By mgonzale Date 2015-06-16 Time 09:34 Rev Time 0.00
Received By mgonzale Date   Time   Sent To B
Notes
2015-06-16 09:36:29PROVISOS:
  
 NO CONFLICTS WITH PROPERTY LINES.
  
 NO CONFLICT WITH PUBLIC UTILITIES; HOWEVER CALL 811
 BEFORE DIGG.
  
 MANUEL JULIAN GONZALEZ
 ENGINEERING PROJECT COORDINATOR
 PUBLIC WORKS DEPARTMENT
 401 CLEMATIS STREET, 4TH FLOOR
 WEST PALM BEACH, FL 33401
 (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402)
 MOBILE (561) 319-2695
 MAIN PHONE: (561) 822-1200
 DIRECT: (561) 494-1085
 FAX: (561) 494-1116
 EMAIL: [email protected]
 WWW.WPB.ORG/ENGINEERING

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2015-07-07 Cont ID  
Sent By shill Date 2015-07-07 Time 13:23 Rev Time 0.00
Received By shill Date 2015-07-05 Time 15:11 Sent To  
Notes
2015-07-05 15:12:08TO SG DESK
 (OLD PLAN DID NOT HAVE A DETAIL; NEW PLAN SHOWS A
 DETAIL WITH A 6' WALL, COLUMN CAPS WHICH EXCEED 6' -
 NEW ZONING REVIEW REQUIRED)
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-04-14 Cont ID  
Sent By shill Date 2015-04-14 Time 07:15 Rev Time 0.00
Received By shill Date 2015-04-07 Time 14:52 Sent To  
Notes
2015-04-07 14:53:22RE-SUBMITTAL SENT TO SAMANTHA HILL FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-03-06 Cont ID  
Sent By shill Date 2015-03-06 Time 17:36 Rev Time 0.00
Received By shill Date 2015-02-24 Time   Sent To  
Notes
2015-02-26 18:25:26SENT TO ZONING

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2015-02-24 Time   Rev Time  
Received By   Date 2015-02-24 Time   Sent To  
Notes
2015-02-10 08:24:07ROUTEDTO ZONING

Review Stop Z ZONING
Rev No 3 Status P Date 2015-07-07 Cont ID  
Sent By shill Date 2015-07-07 Time 13:22 Rev Time 0.00
Received By shill Date 2015-07-07 Time 13:22 Sent To  
Notes
2015-07-07 13:23:18REDLINED PLAN - WALL WITH COLUMN CAPS WILL NOT EXCEED
 6'
 (SITE PLAN ALREADY APPROVED BY SG WITH NOTE THAT WALL
 CANNOT EXCEED 6')
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2015-03-02 Cont ID  
Sent By sgraham Date 2015-03-02 Time 15:45 Rev Time 0.00
Received By sgraham Date 2015-03-02 Time 15:45 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2015-02-10 Cont ID  
Sent By sgraham Date 2015-02-10 Time 10:47 Rev Time 0.00
Received By sgraham Date 2015-02-10 Time 10:47 Sent To B
Notes
2015-02-10 10:50:272/10/15 ZONING FAILED
  
 1. PROVIDE TWO COPIES OF AN UP TO DATE SURVEY, SHOWING
 THE LOCATION OF CONCRETE WALL.