Plan Review Details - Permit 15020227
Plan Review Stops For Permit 15020227
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2015-05-08 Cont ID  
Sent By rmcdouga Date 2015-05-08 Time 09:00 Rev Time 0.00
Received By rmcdouga Date 2015-05-08 Time 07:15 Sent To E
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2015-04-17 Cont ID  
Sent By rmcdouga Date 2015-04-17 Time 14:29 Rev Time 0.00
Received By rmcdouga Date 2015-04-16 Time 19:09 Sent To  
Notes
2015-04-17 14:29:17PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) ONE SET OF THE PLANS IS MISSING SETS A-20, A-21 AND
 A-22. TWO COMPLETE SETS OF PLANS ARE REQUIRED. FBC
 107.1
  
 2) A PRODUCT APPROVAL NOA NO. 12-0612.15 WAS SUBMITTED
 FOR EXTERIOR DOORS. IT IS FOR FIBERGLASS DOORS WITH
 SIDELITES WITH A OXX OR XXO CONFIGURATION AND A MAXIMUM
 FRAME WITDTH OF 108-1/2". THERE ARE NOT ANY DOORS LIKE
 THIS SPECIFIED ON THE PLANS. THE DOOR SCHEDULE
 SPECIFIES METAL DOORS. THERE ARE SINGLE AND DOUBLE
 FRENCH DOORS AND DOUBLE FRENCH DOORS WITH SIDELITES ON
 BOTH SIDES ON THE PLANS.
  
 3) SUBMIT TWO SETS OF PRODUCT APPROVALS WITH
 INSTALLATION INSTRUCTIONS AND DESIGN WIND LOAD
 PRESSURES FOR THE CLAY BARREL ROOF TILE AS REQUIRED BY
 DCA RULE 9N-3. SPECIFY WHICH ONE OF THE ATTACHMENT
 METHODS WITH ADEQUATE UPLIFT RESISTANCE THAT ARE LISTED
 IN THE PRODUCT APPROVAL WILL BE USED. IF A ROOF TILE
 ADHESIVE IS TO BE USED, THEN SUBMIT TWO COPIES OF IT'S
 PRODUCT APPROVALS. FBC 107.2.1 AND FBC-R301.1
  
 4) ONE SET OF PRODUCT APPROVALS WERE SUBMITTED FOR
 SEALOFLEX ROOF SYSTEMS FOR CONCRETE (NOA NO.
 12-0418.04), ONE FOR SEALOFLEX WATERPROOFING SYSTEM FOR
 CONCRETE (NOA NO.10-0608.04) AND ONE FOR SEALOFLEX
 WATERPROOFING SYSTEM FOR LIGHTWEIGHT CONCRETE (NOA
 NO.10-0608.03). SPECIFY WHERE EACH WILL BE INSTALLED
 AND INDICATE THE SPECIFIC ASSEMBLY AND ITS DESIGN
 PRESSURE. FBC 107.2.1 AND FBC-R301.1

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2015-03-17 Cont ID  
Sent By rmcdouga Date 2015-03-17 Time 14:08 Rev Time 0.00
Received By rmcdouga Date 2015-03-16 Time 17:15 Sent To  
Notes
2015-03-17 11:04:33PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PROVIDE STRUCTURAL DETAILS FOR THE PROPOSED PERGOLA
 AT THE POOL HOUSE. FBC-R 301.1
  
 2) PROVIDE STRUCTURAL DRAWINGS FOR THE ARCHED BEAMS
 THAT SHOW THE STEEL PLACEMENT. FBC 107.2.1
  
 3) IN THE FLAT BEAM SCHEDULE ON SHEET S-21, THERE ARE
 TWO FB-1 MARKS LISTED. IT APPEARS THAT THE SECOND ONE
 SHOULD BE FB-2. FBC 107.2.1
  
 4) PROVIDE SCUPPER SIZING CALCULATIONS AND SPECIFY THE
 SIZES OF THE ROOF SCUPPERS AND OVERFLOW SCUPPERS FOR
 THE NEW POOL HOUSE LOW SLOPE ROOF ON THE PLANS. FBC-R
 903.4
  
 5) R318.6 PROTECTION AGAINST DECAY AND TERMITES.
 CONDENSATE LINES, IRRIGATION/SPRINKLER SYSTEM RISERS
 FOR SPRAY HEADS, AND ROOF DOWNSPOUTS SHALL DISCHARGE AT
 LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS OR
 SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON
 ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM)
 HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON
 A ROOF ABOVE ANOTHER ROOF.
  
 6) SHOW COMPLIANCE WITH FBC 807.1 FOR ATTIC ACCESS.
 BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF CONSTRUCTION
 SHALL HAVE AN ATTIC ACCESS OPENING TO ATTIC AREAS THAT
 EXCEED 30 SQUARE FEET (2.8 M2) AND HAVE A VERTICAL
 HEIGHT OF 30 INCHES (762 MM) OR GREATER. THE VERTICAL
 HEIGHT SHALL BE MEASURED FROM THE TOP OF THE CEILING
 FRAMING MEMBERS TO THE UNDERSIDE OF THE ROOF FRAMING
 MEMBERS.
 THE ROUGH-FRAMED OPENING SHALL NOT BE LESS THAN 22
 INCHES BY 30 INCHES (559 MM BY 762 MM) AND SHALL BE
 LOCATED IN A HALLWAY OR OTHER READILY ACCESSIBLE
 LOCATION. WHEN LOCATED IN A WALL, THE OPENING SHALL BE
 A MINIMUM OF 22 INCHES WIDE BY 30 INCHES HIGH. WHEN THE
 ACCESS IS LOCATED IN A CEILING, MINIMUM UNOBSTRUCTED
 HEADROOM IN THE ATTIC SPACE SHALL BE 30 INCHES (762 MM)
 AT SOME POINT ABOVE THE ACCESS MEASURED VERTICALLY FROM
 THE BOTTOM OF CEILING FRAMING MEMBERS. SEE SECTION
 M1305.1.3 FOR ACCESS REQUIREMENTS WHERE MECHANICAL
 EQUIPMENT IS LOCATED IN ATTICS.
  
 7) ON SHEET S-20, THE INCORRECT EDITIONS OF ACI AND TMS
 ARE REFERENCED. THE 2008 EDITIONS ARE THE ONES
 REFERENCED IN CHAPTER 43 OF THE 2010 FBC.
  
 8) SUBMIT TWO COPIES OF THE EVALUATION REPORT FOR THE
 SPRAY FOAM INSULATION THAT WILL BE INSTALLED. FBC-R316
  
 9) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 THAT HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD. PROVIDE TWO COMPLETE PRODUCT
 APPROVALS WITH FL OR NOA NUMBERS INCLUDING INSTALLATION
 INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES FOR EACH OF
 THE DIFFERENT ROOFING MATERIALS, WINDOW/GLASS TYPES,
 STRUCTURAL MULLIONS AND EXTERIOR DOOR TYPES.
 -THE FOLLOWING IS A LINK TO THE MIAMI - DADE PRODUCT
 APPROVAL WEBSITE.
 HTTP://WWW.MIAMIDADE.GOV/BUILDING/PC-SEARCH_APP.ASP
 -THE FOLLOWING IS A LINK TO THE FLORIDA PRODUCT
 APPROVAL WEBSITE.
 HTTPS://FLORIDABUILDING.ORG/PR/PR_APP_SRCH.ASPX
  
 10) THE FOLLOWING CONNECTORS DO NOT HAVE THEIR PRODUCT
 APPROVAL NUMBERS LISTED ON THE PLANS AND WILL REQUIRE
 PRODUCT APPROVALS TO BE SUBMITTED IF THEY ARE NOT
 PROVIDED ON THE PLANS: HUS 210, THA 413 AND LTT19.
  
 11) SHOP DRAWING SUBMITTALS WILL BE REQUIRED FOR THE
 METAL BALCONY GUARDS. FBC-R 312 & R 301.5
  
 12) IN ORDER TO REDUCE PLAN REVIEW TIMES AND PROVIDE
 CLARIFICATION, PLEASE SUBMIT A RESPONSE LETTER
 INDICATING HOW EACH OF THE REVIEW COMMENTS HAS BEEN
 ADDRESSED.
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2015-05-09 Cont ID  
Sent By dhayes Date 2015-05-09 Time 16:02 Rev Time 0.00
Received By dhayes Date 2015-05-09 Time 15:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2015-04-22 Cont ID  
Sent By dhayes Date 2015-04-22 Time 09:00 Rev Time 0.00
Received By dhayes Date 2015-04-22 Time 08:12 Sent To  
Notes
2015-04-22 09:00:484/22/2015
 PROJECT: 235 BELMONTE
 PERMIT#: 15020227
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 2ND ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) INDICATE THE LOCATION ON THE BUILDING(S) ALL
 ELECTRICAL PANELS, ELECTRICAL SERVICE ENTANCE
 SWITCHGEAR AND EQUIPMENT SUCH AS DISCONNECTS FOR A/C
 EQUIPMENT, WATER HEATERS, POOL EQUIPMENT, IRRIGATION
 EQUIPMENT, GATE CONTROLLERS, ETC...
  
 2) DISCONNECTING MEANS SHALL BE LOCATED WITHIN SIGHT
 FROM AND READILY ACCESSIBLE FROM THE AIR-CONDITIONING
 OR REFRIGERATING EQUIPMENT. THE DISCONNECTING MEANS
 SHALL BE PERMITTED TO BE INSTALLED ON OR WITHIN THE
 AIR-CONDITIONING OR REFRIGERATING EQUIPMENT. NEC 440.14
  
 3) PROVIDE A GFI RECEPTACLE AT AN ACCESSIBLE LOCATION
 WITHIN SIGHT OF A/C EQUIPMENT.. NEC 210.63 NEC 210.8
  
 4) VERIFY LUMINAIRES IN CLOTHES CLOSETS SHALL BE
 INSTALLED IN ACCORDANCE WITH THE PROVISIONS OF THE NEC
 410.16(A) AND (B).
  
 5) VERIFY SPACING AS REQUIRED. SEE NEC 210.52(A)(1)
 THROUGH (A)(3). AND NEC 210.52(C)(1)
  
 6) VERIFY ALL HABITABLE ROOMS HAVE A SWITCHED LIGHTING
 OUTLET. SEE NEC 210.70. PLEASE NOTE A DUPLEX RECEPTACLE
 THAT IS SWITCHED ENTIRELY AND IS NOT FED WITH A
 CONTINUOUS HOT FOR AT LEAST ONE HALF OF THE DEVICE,
 DOES NOT COUNT AS ONE OF THE OUTLETS REQUIRED IN NEC
 210.70
  
 7) OCCUPIABLE BALCONIES AND PORCHES OVER 20 SQ FT MUST
 HAVE A RECEPTACLE OUTLET GFCI PROTECTED. NEC
 210.52(E)(3).
  
 8) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR GENERATORS. ATS, NG FUEL SYSTEM, FIRE
 ALARM, ACCESS CONTROL SYSTEM, SECURITY, CCTV,
 AUDIO/VIDEO, NETWORK, DATA, AND, COMMUNICATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2015-03-16 Cont ID  
Sent By dhayes Date 2015-03-16 Time 11:31 Rev Time 0.00
Received By dhayes Date 2015-03-16 Time 10:27 Sent To  
Notes
2015-03-16 11:31:513/16/2015
 PROJECT: 235 BELMONTE
 PERMIT#: 15020227
 CODE: 2008 EDITION OF THE NEC, 2010 EDITION OF THE FBC
 ,2010 WPB AMENDMENTS TO THE FBC, CHAPTER 1,
 ADMINISTRATION, 2012 FBC SUPPLEMENTS.
 1ST ELECTRICAL PLAN REVIEW
 ACTION: DENIED
  
 1) FBC-R 314, 315
 ADD SMOKE DETECTORS AS REQUIRED FOR THE POOL HOUSE AND
 MAIN HOUSE SLEEPING ROOMS AND ADDITIONAL LANDINGS 1ST
 AND 2ND FLS .
  
 2) INDICATE CIRCUIT NUMBERS ON THE FLOOR PLANS
 CORREPSPONDING WITH THE ELECTRICAL PANEL SCHEDULES OCPD
 AND WIRE SIZES
  
 3) ALL NEW GENERAL PURPOSE OUTLETS MUST BE TAMPER
 RESISTANT AND AFCI PROTECTED. NEC 210.12, 406.11
  
 4) ALL EXISTING AREAS NOT INVOLVED IN THE CURRENT SCOPE
 OF WORK INDICATED ON THESE DESIGN DOCUMENTS SHALL BE IN
 COMPLIANCE WITH THE FBC- EXISTING CHAPTERS, 6,7,AND 8.
  
 5) SEPARATE PERMIT APPLICATIONS ACCOMPANIED BY
 MANUFACTURERS EQUIPMENT SUBMITTALS, AND SHOP DRAWINGS
 ARE REQUIRED FOR GENERATORS. ATS, NG FUEL SYSTEM, FIRE
 ALARM, ACCESS CONTROL SYSTEM, SECURITY, CCTV,
 AUDIO/VIDEO, NETWORK, DATA, AND, COMMUNICATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. SEE LINK:
 HTTP://WPB.ORG/DEVELOPMENT/WP-CONTENT/UPLOADS/SITES/33/
 2013/09/APPLICATION_RESUBMITTAL_FORM_04132010.PDF
  
 ADDITIONALLY, IT IS REQUIRED TO INSERT THE CORRECTED
 PAGES INTO THE DENIED SUBMITTAL PACKAGE. VOID THE
 PREVIOUSLY REVIEWED SHEETS AND LEAVE FOR COMPARATIVE
 REVIEW.
  
 DAVID HAYES, ELECTRICAL PLANS EXAMINER, PX3421,
 561-805-6717 OR [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2015-04-18 Cont ID  
Sent By tklarge Date 2015-04-18 Time 07:48 Rev Time 0.00
Received By tklarge Date 2015-04-18 Time 07:31 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2015-02-12 Cont ID  
Sent By tklarge Date 2015-02-12 Time 05:08 Rev Time 0.00
Received By tklarge Date 2015-02-11 Time 11:11 Sent To  
Notes
2015-02-11 11:21:491) INDICATE ON THE PLAN IF THE FIREPLACE IS GAS OR WOOD
 BURNING. IF IT IS GAS, THE BTU LOAD SHALL BE INCLUDED
 ON THE GAS DRAWING. WPB AMEND. TO 2010 FBC SEC.
 107.2.1.
 2) PLANS SHOW A FUTURE GENERATOR. INDICATE ON THE PLAN
 IF THE GENERATOR WILL BE CONNECTED TO THE NATURAL GAS
 SYSTEM. IF SO IT SHALL BE INCLUDED ON THE GAS RISER.WPB
 AMEND. TO 2010 FBC SEC. 107.2.1.
 3) SHOW THE LOCATION OF THE GAS METER ON THE PLANS.WPB
 AMEND. TO 2010 FBC SEC. 107.2.1.
 4) SUBMIT MANUF. SPECIFICATION SHEETS/INSTALLATION
 MANUAL FOR ALL APPLIANCES FOR REVIEW. APPLIANCES SHALL
 BE LISTED PER 2010 FBCR SEC.G2404.3.WPB AMEND. TO 2010
 FBC SEC. 107.2.1.
 5) SUBMIT A GAS PLAN SHOWING THE LOCATION OF THE PE GAS
 PIPE.PE PIPE SHALL BE INSTALLED OUTDOORS UNDERGROUND
 ONLY PER THE FBCR G2415.15.1. IT APPEARS THAT THE PE
 PIPE MAY BE RUNNING UNDER THE BUILDING SLAB.
 6) THE CSST LINE TO THE COOKTOP SHALL BE A MIN. OF 1"
 PER THE 2010 FBCR TABLE G 2413.4 (5) FOR A DEVELOPED
 LENGTH OF 40 FT.
 7) SHOW THE CORRESPONDING EHD FOR ALL CSST PIPE SIZES
 PER 2010 FBCR TABLE G 2413.4 (5).
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2015-03-02 Cont ID  
Sent By fmittner Date 2015-03-02 Time 15:33 Rev Time 0.00
Received By fmittner Date 2015-03-02 Time 15:33 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2015-05-12 Cont ID  
Sent By rmcdouga Date 2015-05-12 Time 10:59 Rev Time 0.00
Received By rmcdouga Date 2015-04-24 Time 06:55 Sent To  
Notes
2015-04-27 07:01:18SENT TO R MCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2015-04-22 Cont ID  
Sent By dhayes Date 2015-04-22 Time 09:01 Rev Time 0.00
Received By dhayes Date 2015-04-07 Time 17:59 Sent To  
Notes
2015-04-07 17:59:46RE-SUBMITTAL SENT TO R30 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2015-03-17 Cont ID  
Sent By rmcdouga Date 2015-03-17 Time 14:08 Rev Time  
Received By rmcdouga Date 2015-02-06 Time   Sent To  
Notes
2015-02-07 06:39:14INCOMING SENT TO R-27.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 4 Status P Date 2015-05-13 Cont ID  
Sent By skennedy Date 2015-05-13 Time 12:24 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status F Date 2015-05-08 Cont ID  
Sent By rmcdouga Date 2015-05-08 Time 13:55 Rev Time 0.00
Received By rmcdouga Date 2015-05-08 Time 13:55 Sent To E
Notes
2015-05-08 13:56:09BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2015-04-20 Cont ID  
Sent By rmcdouga Date 2015-04-20 Time 10:59 Rev Time 0.00
Received By rmcdouga Date 2015-04-20 Time 10:59 Sent To  
Notes
2015-04-20 10:59:53SEE PREVIOUS COMMENTS.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2015-03-16 Cont ID  
Sent By rmcdouga Date 2015-03-16 Time 17:20 Rev Time 0.00
Received By rmcdouga Date 2015-03-16 Time 17:18 Sent To  
Notes
2015-03-16 17:19:25BEFORE A PERMIT TO CONSTRUCT CAN BE ISSUED, IMPACT FEES
 MUST BE PAID TO PALM BEACH COUNTY. UPON APPROVAL, ONE
 SET OF PLANS SHALL BE SIGNED OUT AND SUBMITTED TO PALM
 BEACH COUNTY FOR AN IMPACT FEE REVIEW. THE PLANS WITH
 THE IMPACT FEE STAMP AND A COPY OF THE PAID RECEIPT
 MUST BE RETURNED TO THE CITY BUILDING DEPARTMENT BEFORE
 THE BUILDING PERMIT CAN BE ISSUED. FOR INFORMATION CALL
 PALM BEACH COUNTY IMPACT FEES AT (561) 233-5025.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2015-05-08 Cont ID  
Sent By rmcdouga Date 2015-05-08 Time 13:08 Rev Time 0.00
Received By rmcdouga Date 2015-05-08 Time 07:15 Sent To  
Notes
2015-05-08 13:07:52APPROVED WITH EXCEPTION. THIS PLAN HAS BEEN APPROVED
 PROVISIONALLY. FAILURE TO CORRECT THE LISTED
 DEFICIENCIES IN THIS PLAN PRIOR TO INSPECTION WILL
 RESULT IN FAILED INSPECTION(S) AND ASSESSMENT OF
 RE-INSPECTION FEE(S).
  
 FBC-R - M1305.1.3 APPLIANCES IN ATTICS.
 ATTICS CONTAINING APPLIANCES SHALL BE PROVIDED WITH AN
 OPENING AND A CLEAR AND UNOBSTRUCTED PASSAGEWAY LARGE
 ENOUGH TO ALLOW REMOVAL OF THE LARGEST APPLIANCE, BUT
 NOT LESS THAN 30 INCHES (762 MM) HIGH AND 22 INCHES
 (559 MM) WIDE AND NOT MORE THAN 6 FEET (1829 MM) LONG
 MEASURED ALONG THE CENTERLINE OF THE PASSAGEWAY FROM
 THE OPENING TO THE APPLIANCE. THE PASSAGEWAY SHALL HAVE
 CONTINUOUS SOLID FLOORING IN ACCORDANCE WITH CHAPTER 5
 NOT LESS THAN 24 INCHES (610 MM) WIDE. A LEVEL SERVICE
 SPACE AT LEAST 30 INCHES (762 MM) DEEP AND 30 INCHES
 (762 MM) WIDE SHALL BE PRESENT ALONG ALL SIDES OF THE
 APPLIANCE WHERE ACCESS IS REQUIRED. THE CLEAR ACCESS
 OPENING DIMENSIONS SHALL BE A MINIMUM OF 20 INCHES BY
 30 INCHES (508 MM BY 762 MM), AND LARGE ENOUGH TO ALLOW
 REMOVAL OF THE LARGEST APPLIANCE.
  
  
 FBC-R - M1305.1.3.1 ELECTRICAL REQUIREMENTS.
 A LUMINAIRE CONTROLLED BY A SWITCH LOCATED AT THE
 REQUIRED PASSAGEWAY OPENING AND A RECEPTACLE OUTLET
 SHALL BE INSTALLED AT OR NEAR THE APPLIANCE LOCATION IN
 ACCORDANCE WITH CHAPTER 34.
  
 FBC-R - M1305.1.3.2 AIR-HANDLING UNITS.
 AIR-HANDLING UNITS SHALL BE ALLOWED IN ATTICS IF THE
 FOLLOWING CONDITIONS ARE MET:
 1. THE SERVICE PANEL OF THE EQUIPMENT IS LOCATED WITHIN
 6 FEET (1829 MM) OF AN ATTIC ACCESS.
 2. A DEVICE IS INSTALLED TO ALERT THE OWNER OR SHUT THE
 UNIT DOWN WHEN THE CONDENSATION DRAIN IS NOT WORKING
 PROPERLY.
 3. THE ATTIC ACCESS OPENING IS OF SUFFICIENT SIZE TO
 REPLACE THE AIR HANDLER.
 4. A NOTICE IS POSTED ON THE ELECTRIC SERVICE PANEL
 INDICATING TO THE HOMEOWNER THAT THE AIR HANDLER IS
 LOCATED IN THE ATTIC. SAID NOTICE SHALL BE IN ALL
 CAPITALS, IN 16 POINT TYPE, WITH THE TITLE AND FIRST
 PARAGRAPH IN BOLD:
  
 NOTICE TO HOMEOWNER
  
 A PART OF YOUR AIR CONDITIONING SYSTEM, THE AIR
 HANDLER, IS LOCATED IN THE ATTIC. FOR PROPER, EFFICIENT
 AND ECONOMIC OPERATION OF THE AIR CONDITIONING SYSTEM,
 YOU MUST ENSURE THAT REGULAR MAINTENANCE IS PERFORMED.
 YOUR AIR CONDITIONING SYSTEM IS EQUIPPED WITH ONE OR
 BOTH OF THE FOLLOWING:
  
 1) A DEVICE THAT WILL ALERT YOU WHEN THE CONDENSATION
 DRAIN IS NOT WORKING PROPERLY OR
  
 2) A DEVICE THAT WILL SHUT THE SYSTEM DOWN WHEN THE
 CONDENSATION DRAIN IS NOT WORKING.
  
 TO LIMIT POTENTIAL DAMAGE TO YOUR HOME, AND TO AVOID
 DISRUPTION OF SERVICE, IT IS RECOMMENDED THAT YOU
 ENSURE PROPER WORKING ORDER OF THESE DEVICES BEFORE
 EACH SEASON OF PEAK OPERATION.
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2015-04-20 Cont ID  
Sent By rmcdouga Date 2015-04-20 Time 11:00 Rev Time 0.00
Received By rmcdouga Date 2015-04-17 Time 14:29 Sent To E
Notes
2015-04-20 11:21:56PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY MECHANICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS.
 ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN. IN ADDITION TO
 THE NAME AND SIGNATURE, SPECIFY THE MECHANICAL
 CONTRACTOR'S LICENSE NUMBER ON THE PLANS.
  
 2) FBC ENERGY CONSERVATION - SECT. 103.2.3.2 CODE
 COMPLIANCE CERTIFICATION. THE BUILDING?S OWNER, THE
 OWNER?S ARCHITECT, OR OTHER AUTHORIZED AGENT LEGALLY
 DESIGNATED BY THE OWNER SHALL CERTIFY THAT THE BUILDING
 IS IN COMPLIANCE WITH THE CODE, AS PER SECTION 553.907,
 FLORIDA STATUTES, PRIOR TO RECEIVING THE PERMIT TO
 BEGIN CONSTRUCTION OR RENOVATION. OWNER/AGENT IS
 REQUIRED TO SIGN THE ENERGY FORM.
  
 3) THE FIRST THREE MECHANICAL NOTES ON THE SECOND
 MECHANICAL SHEET ARE JUMBLED AND ARE NOT ACCEPTABLE FOR
 PUBLIC RECORD. FBC 107.2.1.4 QUALITY OF BUILDING PLANS.
 BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH
 SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE
 MEDIUM. THIS POLICY MAY INCLUDE SUCH THINGS AS MINIMUM
 SIZE, SHAPE, CONTRAST, CLARITY, OR OTHER ITEMS RELATED
 TO RECORDS MANAGEMENT.
  
 4) FBC-R - M1305.1.3 APPLIANCES IN ATTICS.
 ATTICS CONTAINING APPLIANCES SHALL BE PROVIDED WITH AN
 OPENING AND A CLEAR AND UNOBSTRUCTED PASSAGEWAY LARGE
 ENOUGH TO ALLOW REMOVAL OF THE LARGEST APPLIANCE, BUT
 NOT LESS THAN 30 INCHES (762 MM) HIGH AND 22 INCHES
 (559 MM) WIDE AND NOT MORE THAN 6 FEET (1829 MM) LONG
 MEASURED ALONG THE CENTERLINE OF THE PASSAGEWAY FROM
 THE OPENING TO THE APPLIANCE. THE PASSAGEWAY SHALL HAVE
 CONTINUOUS SOLID FLOORING IN ACCORDANCE WITH CHAPTER 5
 NOT LESS THAN 24 INCHES (610 MM) WIDE. A LEVEL SERVICE
 SPACE AT LEAST 30 INCHES (762 MM) DEEP AND 30 INCHES
 (762 MM) WIDE SHALL BE PRESENT ALONG ALL SIDES OF THE
 APPLIANCE WHERE ACCESS IS REQUIRED. THE CLEAR ACCESS
 OPENING DIMENSIONS SHALL BE A MINIMUM OF 20 INCHES BY
 30 INCHES (508 MM BY 762 MM), AND LARGE ENOUGH TO ALLOW
 REMOVAL OF THE LARGEST APPLIANCE.
 FBC-R - M1305.1.3.1 ELECTRICAL REQUIREMENTS.
 A LUMINAIRE CONTROLLED BY A SWITCH LOCATED AT THE
 REQUIRED PASSAGEWAY OPENING AND A RECEPTACLE OUTLET
 SHALL BE INSTALLED AT OR NEAR THE APPLIANCE LOCATION IN
 ACCORDANCE WITH CHAPTER 34.
  
  
  
  
  
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2015-03-16 Cont ID  
Sent By rmcdouga Date 2015-03-16 Time 18:54 Rev Time 0.00
Received By rmcdouga Date 2015-03-16 Time 17:15 Sent To  
Notes
2015-03-16 18:54:36PLAN REVIEW COMMENTS
  
 1ST REVIEW: FBC 2010
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC-R - M1401.3 SIZING. HEATING AND COOLING
 EQUIPMENT SHALL BE SIZED BASED ON BUILDING LOADS
 CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR OTHER
 APPROVED HEATING AND COOLING CALCULATION METHODOLOGIES.
 PROVIDE EQUIPMENT SIZING CALCULATIONS FOR THE MAIN
 HOUSE ADDITION.
  
 2) FBC-R - M 1602.4 PROVIDE BALANCED RETURN AIR.
 RESTRICTED RETURN AIR OCCURS IN BUILDINGS WHEN RETURNS
 ARE LOCATED IN CENTRAL ZONES AND CLOSED INTERIOR DOORS
 IMPEDE AIR FLOW TO THE RETURN GRILL OR WHEN CEILING
 SPACES ARE USED AS RETURN PLENUMS AND FIRE WALLS
 RESTRICT AIR MOVEMENT FROM ONE PORTION OF THE RETURN
 PLENUM TO ANOTHER. PROVISIONS SHALL BE MADE IN BOTH
 RESIDENTIAL AND COMMERCIAL BUILDINGS TO AVOID
 UNBALANCED AIR FLOWS AND PRESSURE DIFFERENTIALS CAUSED
 BY RESTRICTED RETURN AIR. PRESSURE DIFFERENTIALS ACROSS
 CLOSED DOORS WHERE RETURNS ARE CENTRALLY LOCATED SHALL
 BE LIMITED TO 0.01 INCH WC (2.5 PASCALS) OR LESS.
 PRESSURE DIFFERENTIALS ACROSS FIRE WALLS IN CEILING
 SPACE PLENUMS SHALL BE LIMITED TO 0.01 INCH WC (2.5
 PASCALS) BY PROVIDING AIR DUCT PATHWAYS OR AIR TRANSFER
 PATHWAYS FROM THE HIGH PRESSURE ZONE TO THE LOW ZONE.
 EXCEPTIONS:
 1. TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE
 RETURN TRANSFER 11/2 TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT ENTERING THE ROOM OR
 SPACE IT IS SERVING AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCH UNDERCUT TO ACHIEVE PROPER RETURN
 AIR BALANCE.
 2. TRANSFER GRILLES SHALL USE 50 SQUARE INCHES (OF
 GRILLE AREA) TO 100 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND USING AN
 UNRESTRICTED 1 INCH UNDERCUTTING OF DOORS TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 3. HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET THESE
 REQUIREMENTS FOR PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY ROOMS,
 EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE SHALL
 BE INCLUDED.
 (MAIN HOUSE ADDITION) THE RETURN AIR DUCT FROM THE
 MASTER BEDROOM IS UNDER SIZED. ALL SUPPLY AIR INTO THE
 MASTER SUITE SHALL BE ACCOUNTED FOR.
 (POOL HOUSE) THE AIR HANDLER CLOSET IS LOCATED INSIDE
 OF A CLOTHES CLOSET AT ONE END OF THE POOL HOUSE. THERE
 IS A SOLID DOOR ON THE CLOTHS CLOSET AND THERE ARE
 OTHER DOORS THAT EFFECTIVELY WILL ISOLATE THE UNIT FROM
 THE REST OF THE STRUCTURE INCLUDING THE BEDROOM ON THE
 OPPOSITE END. SHOW HOW THE BALANCED AIR REQUIREMENTS
 WILL BE MET.
  
 3) THE HEATING AND COOLING EQUIPMENT SCHEDULE ON THE
 PLANS DOES NOT MATCH THE ENERGY FORMS OR THE SIZING
 CALCULATIONS (POOL HOUSE) THAT WERE SUBMITTED. FOR THE
 POOL HOUSE THE PLANS HAVE 2 TONS AND THE CALCULATION
 AND ENERGY FORM HAS 2.5 TONS. FOR THE MAIN HOUSE
 ADDITION THE PLANS HAVE 3.5 TONS AND THE ENERGY FORM
 HAS 3 TONS. FBC 107.2.1
  
 4) THE ENERGY FORM FOR THE POOL HOUSE IS REQUIRED TO BE
 SIGNED BY THE OWNER/AGENT. FBC ENERGY CONSERVATION
 103.2.3.2
  
  
  
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2015-04-23 Cont ID  
Sent By tklarge Date 2015-04-18 Time 07:23 Rev Time 0.00
Received By tklarge Date 2015-04-18 Time 05:37 Sent To  
Notes
2015-04-23 03:54:05APPROVED.

Review Stop P PLUMBING
Rev No 1 Status P Date 2015-02-11 Cont ID  
Sent By tklarge Date 2015-02-11 Time 11:10 Rev Time 0.00
Received By tklarge Date 2015-02-11 Time 09:26 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2015-05-11 Cont ID  
Sent By fmittner Date 2015-05-11 Time 11:28 Rev Time 0.00
Received By fmittner Date 2015-05-11 Time 11:28 Sent To B
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2015-03-02 Cont ID  
Sent By fmittner Date 2015-03-02 Time 15:34 Rev Time 0.00
Received By fmittner Date 2015-03-02 Time 15:34 Sent To  
Notes
2015-02-10 10:48:442-10-15